UPS5000-H-600 kVA-FTN
User Manual (Singapore, 100 kVA Power Modules)
1.
2.
Step 4 Set each UPS in the system that is defined as the slave system to BSC slave
system.
1.
2.
Step 5 Check that the RMS phase voltage difference between UPS systems is less than 5
V.
----End
Issue 02 (2023-11-07)
On the LCD, choose System Info > Settings > System Settings and set BSC
mode to Standard BSC
On the LCD, choose System Info > Settings > System Settings and set BSC
master/slave mode to BSC master system
On the LCD, choose System Info > Settings > System Settings and set BSC
mode to Standard BSC
On the LCD, choose System Info > Settings > System Settings and set BSC
master/slave mode to BSC slave system
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Parallel System Commissioning
144