Huawei UPS5000-H-600 User Manual page 106

Hide thumbs Also See for UPS5000-H-600:
Table of Contents

Advertisement

UPS5000-H-600 kVA-FTN
User Manual (Singapore, 100 kVA Power Modules)
● Cables have been preinstalled and bound in the inductor cabinet.
● The cables from the inductor cabinet to the UPS are configured based on the
● Cables must be bound to the nearest beam or cable bridge according to the
Figure 4-39 Installing cables from the inductor cabinet to the UPS cabinet
(1) Power cable hole
Step 6 Connect power cables to the UPS.
Issue 02 (2023-11-07)
NO TICE
longest cable length before delivery. If shorter cables are needed in the actual
installation scenario, you can cut the excess cables and crimp terminals.
route shown in the following figure.
NO TE
When installing AC input power cables, if there are a great number of cables and the wiring
holes in the mains input copper bar are insufficient, connect the cables to the
corresponding holes in the bypass input copper bar.
One power source
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
(2) Signal cable hole
98

Advertisement

Table of Contents
loading

Table of Contents