Mains Input Electrical Specifications
Item
Rated voltage (line
voltage)
Rated current
Power system
Voltage range
Rated frequency
Frequency range
Power factor
Harmonic current
Overvoltage
category
Bypass Input Electrical Specifications
Item
Rated voltage (line
voltage)
Rated current
Power system
Rated frequency
Frequency range
Input mode
Issue 02 (2023-11-07)
Specifications
380 V AC
1115 A
Three-phase three-wire + PE
0–30°C: not derated at 323–485 V, derated from 100% load to 45% load at
323–191 V, and derated from 45% load to 35% load at 191–138 V
30–40°C: not derated at 342–485 V, derated from 100% load to 45% load at
342–191 V, and derated from 45% load to 35% load at 191–138 V
50/60 Hz
40–70 Hz
● > 0.99 (100% load)
● > 0.98 (50% load)
● > 0.94 (30% load)
● THDi < 9% (30% linear load), THDi < 6% (50% linear load), THDi < 3%
(100% linear load)
● THDi < 11% (30% non-linear load), THDi < 8% (50% non-linear load),
THDi < 5% (100% non-linear load)
Remarks:
1. The preceding specifications are met when the mains input and
bypass input share a power source.
2. The input THDu is less than 2%.
OVC II
Specifications
380 V AC
912 A
Three-phase three-wire + PE
50/60 Hz
50/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6 Hz, ±2 Hz by default)
The mains input and bypass input share a power source (by default) or use
different power sources.
Copyright © Huawei Digital Power Technologies Co., Ltd.
400 V AC
1059 A
400 V AC
866 A
3 Technical Specifications
415 V AC
1021 A
415 V AC
835 A