UPS5000-H-600 kVA-FTN
User Manual (Singapore, 100 kVA Power Modules)
Check Item
Cable and circuit breaker
through-current capacity
7.2 Lead-Acid Battery Maintenance
Before operating batteries, read through the battery user manual, safety
precautions, and correct connection methods provided by the battery
manufacturer.
Before installing and maintaining batteries, pay attention to the following points:
● Use insulated tools to avoid electric shocks.
● Wear protective goggles and take other necessary protective measures.
● Wear insulated gloves and a protective coat to guard against electrolyte
● When moving batteries, avoid handling batteries upside down, handle them
● Keep the battery switch off when installing or maintaining the batteries.
7.2.1 Precautions for Battery Maintenance
●
●
●
●
●
●
Issue 02 (2023-11-07)
NO TICE
overflow.
gently, and pay attention to personal safety.
Use insulated tools during battery maintenance. Do not place any objects on
the top of batteries.
Do not use any organic solvent to clean batteries.
Do not remove the safety valve or fill anything into batteries.
Do not smoke or use an open flame around batteries.
After batteries are discharged, charge them in time to avoid affecting their
lifespan.
Only professionals are allowed to perform the maintenance tasks.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Expected Result
● The circuit breakers
and cables meet load
requirements.
● The allowed through-
current capacity of
cables is greater than
the circuit breaker
specifications.
7 Maintenance
Troubleshooting
● Replace the circuit
breakers.
● Replace the cables.
149