Emerson Rosemount OCX8800 Instruction Manual
Emerson Rosemount OCX8800 Instruction Manual

Emerson Rosemount OCX8800 Instruction Manual

Oxygen and combustibles transmitter, hazardous location probe with integral electronics
Hide thumbs Also See for Rosemount OCX8800:
Table of Contents

Advertisement

Quick Links

I n s t r u c t i o n Ma n u a l
Rev 1.3
IM-106-880C-OI
April 2017
Rosemount
OCX8800 Oxygen and
TM
Combustibles Transmitter
Hazardous Location Probe with Integral Electronics

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Rosemount OCX8800

  • Page 1 I n s t r u c t i o n Ma n u a l Rev 1.3 IM-106-880C-OI April 2017 Rosemount OCX8800 Oxygen and Combustibles Transmitter Hazardous Location Probe with Integral Electronics...
  • Page 3 S i g n a l wo rd s and s y m b o l s Pay special attention to the following signal words, safety alert symbols and statements: Safety alert symbol This is a safety alert symbol. It is used to alert you to potential physical injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
  • Page 4 • Read all instructions prior to installing, operating, and servicing the product. • If you do not understand any of the instructions, contact your Emerson representative for clarification. • Follow all warnings, cautions, and instructions marked on and supplied with the product.
  • Page 5 The remaining sections contain detailed procedures and information necessary to install and service the transmitter. Before contacting Emerson concerning any questions, first consult this manual. It describes most situations encountered in your equipment's operation and details necessary action. The purpose of this manual is to provide a comprehensive understanding of the Hazardous Area OCX 8800 components, functions, installation, and maintenance.
  • Page 6 D e f i n i t i o n s The following definitions apply to WARNINGS, CAUTIONS, and NOTES found throughout this publication. Highlights an operation or maintenance procedure, practice, condition, statement, etc. If not strictly observed, could result in injury, death, or long-term health hazards of personnel.
  • Page 7 S y m b o l s NOTE TO USERS The number in the lower right corner of each illustration in this publication is a manual illustration number. It is not a part number, and is not related to the illustration in any technical manner. NOTE Read this manual before working with the product.
  • Page 8 If this instruction manual is not the correct manual for you Rosemount product, call Rosemount at 800 854 8257, and Rosemount will provide you with the requested manual. You may also download the manual from www.Emerson.com/RosemountGasAnalysis. • Use only replacement parts specified by Rosemount. Unauthorized parts and procedures can affect this product's performance and safety and invalidate the warranty.
  • Page 9 Product names used herein are for manufacturer or supplier identification only and may be trademarks/registered trademarks of these companies. Rosemount and the Rosemount logo are registered trademarks of Rosemount. The Emerson logo is a trademark and service mark of Emerson Electric Co.
  • Page 10 Wa r r a n t y LIMITED WARRANTY: Subject to the limitations contained in Section 2 herein, Rosemount warrants that the licensed firmware embodied in the Goods will execute the programming instructions provided by Rosemount and that the Goods manufactured by Rosemount will be free from defects in materials or workmanship under normal use and care and Services will be performed by trained personnel using proper equipment and instru- mentation for the particular Service provided.
  • Page 11: Table Of Contents

    Instruction Manual Table of IM-106-880C, OI Contents April 2017 Contents Preface Signal words and symbols Essential Instructions Preface Definitions Symbols Notice Warranty Section 1:Description and Specifications 1.1 Section contents ....................1 1.2 Component Checklist ................... 1 1.3 System Overview ....................2 1.3.1 Scope .....................
  • Page 12 Instruction Manual Table of IM-106-880C, OI Contents April 2017 2.5 Pneumatic Installation ..................30 2.5.1 Reference Air Set Option (only) ............. 30 2.5.2 Reference Air Set and Solenoids Option without COe Zero Function ..33 2.5.3 Reference Air Set and Solenoids Option with COe Zero Function .... 33 2.5.4 Reference Air Set, Solenoids, and Blowback Option with COe Zero Function35...
  • Page 13 Instruction Manual Table of IM-106-880C, OI Contents Communicator - HART ................54 April 2017 3.9.2 Configuring the Calibration Tolerance Feature with the Field Communicator - Fieldbus .............. 54 3.9.3 Configuring the COe Zero Feature with the LOI ........55 3.10 OCX 8800 Reset Procedure................. 55 3.10.1 OCX Reset with the LOI ................
  • Page 14 Table of Instruction Manual Contents April 2017 IM-106-880C, OI Section 6: Field Communicator 6.1 Section contents ....................79 6.2 Overview ......................79 6.3 Field Communicator Connections ............... 79 6.3.1 Connecting to a HART loop ..............79 6.3.2 Connecting to a Fieldbus Segment ............80 6.4 Off-Line and On-Line Operations ................
  • Page 15 Instruction Manual Table of IM-106-880C, OI Contents April 2017 7.11 Analog Input (AI) Function Block ..............114 7.11.1 Introduction ..................114 7.11.2 Simulation ................... 117 7.11.3 Filtering ....................118 7.11.4 Signal Conversion ................118 7.11.5 Direct signal conversion ..............118 7.11.6 Indirect signal conversion ..............
  • Page 16 7.15.5 Status Handling ................... 162 7.15.6 Application Information ..............162 7.15.7 Troubleshooting ................. 164 7.16 Operation with Emerson DeltaV ............... 164 7.16.1 About AMS and DeltaV Software ............164 Section 8: Troubleshooting 8.1 Section contents ....................167 Overview ....................... 167 8.2.1...
  • Page 17 Instruction Manual Table of IM-106-880C, OI Contents April 2017 9.4.13 Install O2 Cell and Heater Strut Assembly ..........213 9.4.14 Install Terminals Insulator and Cover ........... 213 9.4.15 Sensor Housing Leak Test ..............214 9.5 Repair Electronics Housing ................. 214 9.5.1 Electronics Housing Disassembly ............
  • Page 18 Table of Instruction Manual Contents April 2017 IM-106-880C, OI Appendix A: Safety Data Appendix contents ..................233 Safety Instructions ..................233 Safety Data Sheet for Ceramic Fiber Products ..........255 High Pressure Gas Cylinders ................262 A.4.1 General Precautions For Handling And Storing High Pressure Gas Cylinders ...................
  • Page 19 Instruction Manual List of IM-106-880C, OI Tables April 2017 List of Tables Table 1-1 Product Matrix - Hazardous Area OCX 8800 ..............14 Table 1-2 Accessories ........................15 Table 4-1. LOI Status Codes ......................60 Table 7-1 OCX Implemented Function Blocks .................. 94 Table 7-2 Hazardous Area OCX 8800 PWA ..................
  • Page 20 List of Instruction Manual Tables April 2017 IM-106-880C, OI Table 7-29 Alarm priority levels ....................... 139 Table 7-30 Troubleshooting ......................148 Table 7-31 Arithmetic (ARTHM) Block ..................... 150 Table 7-32 BLOCK_ERR Parameters....................152 Table 7-33 Alarm Level Priorities ..................... 153 Table 7-34 Troubleshooting ......................
  • Page 21 Instruction Manual List of Figures IM-106-880C, OI April 2017 List of Figures Figure 1-1 Typical System Package ....................2 Figure 1-2 System Operation Diagram....................6 Figure 1-3 Communication Connections and AFigure 1-3 AMS Application - Hazardous Area OCX 8800 with Integral Electronics .................. 8 Figure 1-4 Typical System Installation - Integral Electronics ..............
  • Page 22 List of Figures Instruction Manual April 2017 IM-106-880C, OI Figure 4-2. LOI Components Mounting .................... 57 Figure 4-3 LOI Assembly ........................58 Figure 4-4 ‘Z’ Pattern Entry ......................59 Figure 4-5 LOI Menu Tree (Sheet 1 of 4)................... 61 Figure 4-6 LOI Menu Tree (Sheet 2 of 4) ..................
  • Page 23 Instruction Manual List of Figures IM-106-880C, OI April 2017 Figure 7-19 PID Function Block Diagram for Steam Heater Control Example........143 Figure 7-20 PID Function Block Feedforward Control Example ............143 Figure 7-21 PID Function Block Diagram for Feedfoward Control ............. 144 Figure 7-22 PID Function Block Cascade Control Example ..............
  • Page 24 List of Figures Instruction Manual April 2017 IM-106-880C, OI Figure 9-17 Installation of Eductor and COe Sensor ................ 206 Figure 9-18 Eductor Alignment Matchmarks .................. 207 Figure 9-19 Band Heater Height ..................... 208 Figure 9-20 COe Sensor Holder Alignment ..................209 Figure 9-21 COe Sensor, Thermocouple, and Heater Connections ..........
  • Page 25: Section 1:Description And Specifications

    Use this complete model number for any correspondence with Emerson. A list of accessories for use with the Hazardous Area OCX 8800 is provided in Table 1-2.
  • Page 26: System Overview

    Hazardous Area OCX 8800. Signal conditioning electronics outputs a digital signal representing oxygen (O ) and combustibles (COe) values. This information, plus additional details, can be accessed with the 375 Field communicator or Emerson AMS software. The optional local operator interface (LOI) also provides a communications interface with the electronics.
  • Page 27: System Description

    Instruction Manual Section 1: Description and Specifications IM-106-880C, OI April 2017 1.3.2 System Description The Hazardous Area OCX 8800 is designed to measure oxygen and combustible concentrations in flue gas temperatures up to 2600°F (1427°C). Electrical connections, power and communications are made through two 3/4 NPT ports in the flameproof electronics enclosure using fittings and cables provided by the customer.
  • Page 28: System Configuration

    Section 1: Description and Instruction Manual Specifications IM-106-880C, OI April 2017 The Hazardous Area OCX 8800 combustibles sensor is a catalytic sensor consisting of two Resistance Devices (RTD). One RTD is the reference element covered with an inert coating. The other RTD element is active, coated with a catalyst. As the sample gases flow by the sensor, the combustible gases oxidize on the surface of the active element.
  • Page 29: System Features

    Device Description (DD) software specific to the Hazardous Area OCX 8800. The DD software will be supplied with many Model 375 units, but can also be programmed into existing units at most Emerson service offices. Refer to Section 6, Field Communicator, for additional information.
  • Page 30: System Operation

    Section 1: Description and Instruction Manual Specifications IM-106-880C, OI April 2017 1.3.5 System Operation Figure 1-2 shows the relationship between the components of the Hazardous Area OCX 8800. The sensors and the electronics are contained in separate housings. The sensor housing and probe mounts to a duct or process wall so that the probe protrudes into the flue gas stream.
  • Page 31: Handling The Hazardous Area Ocx 8800

    Instruction Manual Section 1: Description and Specifications IM-106-880C, OI April 2017 1.3.6 Handling the Hazardous Area OCX 8800 It is important that printed circuit boards and integrated circuits are handled only when adequate anti-static precautions have been taken to prevent possible equipment damage. The Hazardous Area OCX 8800 is designed for industrial application.
  • Page 32: Figure 1-3 Communication Connections And Afigure 1-3 Ams Application - Hazardous Area Ocx 8800 With Integral Electronics

    Section 1: Description and Instruction Manual Specifications IM-106-880C, OI April 2017 Figure 1-3 Communication Connections and AFigure 1-3 AMS Application - Hazardous Area OCX 8800 with Integral Electronics Model 375 OCX 8800 with Field Integral Electronics Communicator Signal Output (Twisted Pairs) Customer’s Laptop with AMS Termination in...
  • Page 33: Figure 1-5 Typical System Installation - Remote Electronics

    Instruction Manual Section 1: Description and Specifications IM-106-880C, OI April 2017 Figure 1-5 Typical System Installation - Remote Electronics Gases OCX 8800 with REMOTE ELECTRONICS Duct Stack Heater Power Cable [up to 150 ft (46 m)] Signal Cable [up to 150 ft (46 m)] Test Gas Flow Meter Signal Outputs...
  • Page 34: Figure 1-6 Optional Sample Tube Support

    Section 1: Description and Instruction Manual Specifications IM-106-880C, OI April 2017 Figure 1-6 Optional Sample Tube Support System Considerations...
  • Page 35: Figure 1-7. Optional In-Situ Filters

    Instruction Manual Section 1: Description and Specifications IM-106-880C, OI April 2017 Figure 1-7. Optional In-Situ Filters Figure 1-8. Optional Panel Mounted Blowback and Calibration/Reference Air Set (19” Rack or Wall Mount) System Considerations...
  • Page 36: Specifications

    Section 1: Description and Instruction Manual Specifications IM-106-880C, OI April 2017 Specifications Specifications Net O Range 0-1% to 0-40% O , fully field selectable Combustibles 0-1000 ppm to 0-5%, fully field selectable Accuracy Oxygen ± 0.75% of reading or 0.05% O (whichever is greater) Combustibles ±...
  • Page 37 Section 1: Description and Instruction Manual Specifications IM-106-880C, OI April 2017 Specifications ≥ Blowback Air (optional) Clean, dry, instrument quality air (20.95% O2) regulated to 60 psi (413 kPa) or greater and ambient ≥ temperature of 0 °F (-18 °C) Sensors Housing Type 4X, IP66 with fitting and pipe on reference exhaust port to clean, dry atmosphere, two 3/4-14 NPT conduit ports...
  • Page 38: Product Matrix - Hazardous Area Ocx 8800

    Instruction Manual Section 1: Description and Specifications IM-106-880C, OI April 2017 Product Matrix - Hazardous Area OCX 8800 Table 1-1 Product Matrix - Hazardous Area OCX 8800 OCX88CO /Combustibles Transmitter - Flameproof Code Probe Length and Material No Probe or Exhaust Tube 18 in.
  • Page 39: Table 1-2 Accessories

    Section 1: Description and Instruction Manual Specifications IM-106-880C, OI April 2017 Cont’d Code In-Situ Filter None High Surface Area Stainless Steel Hastelloy Code Accessories None Cal. Gas/Flow Rotometers & Ref. Gas Set Cal. Gas/Flow Rotometers & Ref. Gas Set w/ Blowback Cal.
  • Page 40: Section 2: Installation

    Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 Section 2: Installation Section contents Product Safety .....................page Mechanical Installation ..................page Electrical Installation ...................page Pneumatic Installation ..................page Initial Startup .......................page Product Safety Before installing this equipment, read the “Safety instructions for the wiring and installation of this apparatus”...
  • Page 41 Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 Section contents...
  • Page 42: Mechanical Installation

    Section 2: Instruction Manual Installation IM-106-880C, OI April 2017 Mechanical Installation 2.3.1 Selecting a location The location of the Hazardous Area OCX 8800 in the stack or flue is most important for maximum accuracy in the oxygen analyzing process. The probe must be positioned so the gas it measures is representative of the process.
  • Page 43: Figure 2-2 Installation, Hazardous Area Ocx 8800 With Integral Electronics

    Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 NOTE: If process temperatures will exceed 392 °F (200 °C), use anti-seize compound on stud threads to ease future removal of the Hazardous Area OCX 8800. 7. Insert sample and exhaust tubes through the opening in the mounting flange and bolt the unit to the flange. Uninsulated stacks or ducts may cause ambient temperatures in the electronics housing to exceed 185 °F (85 °C) and damage the electronics.
  • Page 44: Figure 2-3 Installation, Hazardous Area Ocx 8800 With Remote Electronics

    Section 2: Instruction Manual Installation IM-106-880C, OI April 2017 Figure 2-3 Installation, Hazardous Area OCX 8800 with Remote Electronics Installatio...
  • Page 45: Figure 2-4 Adapter Plate Installation

    Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 Figure 2-4 Adapter Plate Installation Installatio...
  • Page 46: Figure 2-5 Wall Or Pipe Mounting Of Electronics Housing

    Section 2: Instruction Manual Installation IM-106-880C, OI April 2017 Figure 2-5 Wall or Pipe Mounting of Electronics Housing Installatio...
  • Page 47: Figure 2-6 Installation With Drip Loops

    Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 Figure 2-6 Installation with Drip Loops Duct Wall Conduit Drip Loops Conduit Drip Loop Conduit Drip Loop Duct Wall Installatio...
  • Page 48: Electrical Installation

    Section 2: Instruction Manual Installation IM-106-880C, OI April 2017 Electrical Installation All wiring must conform to local and national codes. For reference, factory wired solenoid power connections are shown in Figure 2-7. Disconnect and lock out power before connecting the unit to the power supply. Failure to lock out power could result in serious injury or death.
  • Page 49: Electrical Connections

    Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 To maintain explosion-proof protection of the OCX88C in hazardous areas, the sample   entering the sensor housing must not exceed 195 C (383 NOTE: To maintain proper earth grounding, ensure a positive connection exists between the sensor housing, the electronics housing, and earth.
  • Page 50: O2 4-20 Ma Signal

    Section 2: Instruction Manual Installation IM-106-880C, OI April 2017 2.4.5 COe 4-20 mA Signal Another 4-20 mA signal at the AOUT 2 terminals represents the COe value. 2.4.6 Foundation Fieldbus Signal The Foundation Fieldbus signal provides all output information and is accessible through a Model 375 Handheld communicator.
  • Page 51: Figure 2-7 Line Voltage, Earth, And 4-20 Ma Connections

    Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 Figure 2-7 Line Voltage, Earth, and 4-20 mA Connections Heater Power Connections...
  • Page 52 Section 2: Instruction Manual Installation IM-106-880C, OI April 2017 Figure 2-8. Electrical Connections Between Remote Electronics and Sensor Housing Heater Power Connections...
  • Page 53: Figure 2-9 Customer-Furnished Interconnect Wiring Or Cables

    Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 Figure 2-9 Customer-Furnished Interconnect Wiring or Cables Heater Power Connections...
  • Page 54: Pneumatic Installation

    Section 2: Instruction Manual Installation IM-106-880C, OI April 2017 Pneumatic Installation Pneumatic system connections depend on whether reference air set, calibration solenoids, and/ or blowback equipment options are equipped on your transmitter. Refer to the following paragraphs and select the option that applies to your transmitter configuration. 2.5.1 Reference Air Set Option (only) When no options or only the reference air set option is equipped, use the following procedure to...
  • Page 55: Figure 2-10 Pneumatic Installation, Ocx With Reference Air Set Without Autocalibration

    Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 Figure 2-10 Pneumatic Installation, OCX with Reference Air Set without Autocalibration Reference Air Set Option (only)
  • Page 56: Figure 2-11 Pneumatic Installation, Ocx With Reference Air Set, Solenoids And Autocalibration

    Section 2: Instruction Manual Installation IM-106-880C, OI April 2017 Figure 2-11 Pneumatic Installation, OCX with Reference Air Set, Solenoids and Autocalibration, without COe Zero Function Reference Air Set Option (only)
  • Page 57: Reference Air Set And Solenoids Option Without Coe Zero Function

    Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 2.5.2 Reference Air Set and Solenoids Option without COe Zero Function When the reference air set and test gas solenoids are included with your Hazardous Area OCX 8800, use the following procedure to install the pneumatic system components.
  • Page 58: Reference Air Set And Solenoids Option With Coe Zero Function

    Section 2: Instruction Manual Installation IM-106-880C, OI April 2017 Figure 2-12 Pneumatic Installation, OCX with Reference Air Set, Solenoids and Autocalibration, with COe Zero Function Reference Air Set and Solenoids Option with COe Zero Function...
  • Page 59: Reference Air Set, Solenoids, And Blowback Option With Coe Zero Function

    Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 2.5.4 Reference Air Set, Solenoids, and Blowback Option with COe Zero Function Figure 2-14 shows the piping arrangement for the Hazardous Area OCX 8800 with the blowback and autocalibration options when the COe Zero Function is used. The arrangement is similar to Figure 2-13 except instrument air is used as the Hi O...
  • Page 60: Figure 2-13 Pneumatic Installation, Ocx With Reference Air Set, Solenoids, Blowback And

    Section 2: Instruction Manual Installation IM-106-880C, OI April 2017 Figure 2-13 Pneumatic Installation, OCX with Reference Air Set, Solenoids, Blowback and Autocalibration, without COe Zero Function Reference Air Set, Solenoids, and Blowback Option without COe Zero Function...
  • Page 61 Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 Figure 2-14 Pneumatic Installation, OCX with Reference Air Set, Solenoids, Blowback and Autocalibration, with COe Zero Function Reference Air Set, Solenoids, and Blowback Option without COe Zero Function...
  • Page 62: Reference Air Set And Blowback Panels

    Section 2: Instruction Manual Installation IM-106-880C, OI April 2017 2.5.6 Reference Air Set, Solenoids, and Blowback Option with COe Zero Function Figure 2-14 shows the piping arrangement for the Hazardous Area OCX 8800 with the blowback and autocalibration options when COe Zero Function is used. The arrangement is similar to Figure 2-13 except instrument air is used as the Hi O...
  • Page 63: Figure 2-15 Pneumatic Installation, Blowback Panel Without Autocalibration Without Coe Zero Function

    Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 Figure 2-15 Pneumatic Installation, Blowback Panel without Autocalibration without COe Zero Function Reference Air Set and Blowback Panels...
  • Page 64: Figure 2-16 Pneumatic Installation, Blowback Panel With Autocalibration Without Coe Zero Function

    Section 2: Instruction Manual Installation IM-106-880C, OI April 2017 Figure 2-16 Pneumatic Installation, Blowback Panel with Autocalibration without COe Zero Function Reference Air Set and Blowback Panels...
  • Page 65: Figure 2-17 Pneumatic Installation, Blowback Panel With Autocalibration With Coe Zero Function

    Instruction Manual Section 2: Installation IM-106-880C, OI April 2017 Figure 2-17 Pneumatic Installation, Blowback Panel with Autocalibration with COe Zero Function Reference Air Set and Blowback Panels...
  • Page 66: Initial Startup

    Section 2: Instruction Manual Installation IM-106-880C, OI April 2017 Initial Startup Observe the following Caution and Note. Refer to Section 3, for Hazardous Area OCX 8800 startup information. Upon completing installation, make sure that the Hazardous Area OCX 8800 is turned on and operating prior to firing up the combustion process.
  • Page 67: Section 3: Configuration And Startup

    Instruction Manual Section 3: Configuration and Startup IM-106-880C, OI April 2017 Section 3: Configuration and Startup Section contents Verify Installation ....................page Initial Power Up ....................page Set Test Gas Values ....................page Calibration Solenoids .................... page Blowback Feature ....................page Calibration Verify Feature ..................
  • Page 68 Instruction Manual Section 3: Configuration and Startup IM-106-880C, OI April 2017 Hazardous Area OCX 8800 with HART electronics (Figure 3-1). SW1 determines if the O 4-20 mA signal is internally or externally powered. SW2 determines if the COe 4-20 mA signal is internally or externally powered.
  • Page 69: Figure 3-1 Hazardous Area Ocx 8800 Defaults - Hart Electronics

    Section 3: Configuration and Instruction Manual Startup IM-106-880C, OI April 2017 configures the sample line heater control circuit. All switches are accessible through holes in the electronics box. Remove power from the Hazardous Area OCX 8800 before changing defaults. If defaults are changed under power, damage to the electronics may occur.
  • Page 70: Verify Configuration - Fieldbus Electronics

    Instruction Manual Section 3: Configuration and Startup IM-106-880C, OI April 2017 • Position 2 determines the COe 4-20 mA signal rail limit. The settings are high, 21.1 mA, or low, 3.5 mA. The factory setting is high, 21.1 mA. Positions 3 and 4 must be set as shown for proper software control of the device heaters. 3.2.2 Verify Configuration - Fieldbus Electronics There is one switch on the microprocessor board which must be set for the Hazardous Area OCX...
  • Page 71: Initial Power Up

    Section 3: Configuration and Instruction Manual Startup IM-106-880C, OI April 2017 Verify that the following switch settings are correct for your Hazardous Area OCX 8800 installation: SW3 The factory sets this switch as follows: • Position 1 not used. • Position 2 not used.
  • Page 72: Setting Test Gas Values With The Loi

    Instruction Manual Section 3: Configuration and Startup IM-106-880C, OI April 2017 From O2 CAL SETUP, select O2 LOW GAS. Enter the percent O used for the low test gas From the TRANSDUCER menu select COe CAL SETUP. From COe CAL SETUP, select COe Test Gas. Enter the CO concentration (ppm) used for the COe Test Gas.
  • Page 73: Configuring The Calibration Solenoids With The Loi

    Section 3: Configuration and Instruction Manual Startup IM-106-880C, OI April 2017 From the O2 CAL SETUP/COE CAL SETUP, select Solenoids. Select Present to enable the solenoids. 3.5.3 Configuring the Calibration Solenoids with the LOI Use the "Z" pattern to enter the LOI menu tree. From the SYSTEM menu, select Calib Setup.
  • Page 74: Configuring Blowback With The Loi

    Instruction Manual Section 3: Configuration and Startup IM-106-880C, OI April 2017 From the Alarm Relay/Blowback menu, select Blowback. From the Blowback menu, select Blowback Enabled. Also set the following parameters: • Blowback Interval - Length of time between blowback events (60 minutes recommended).
  • Page 75: Performing A Calibration Verify With The Field Communicator - Hart

    Section 3: Configuration and Instruction Manual Startup IM-106-880C, OI April 2017 The calibration verify feature is only valid if the Hazardous Area OCX 8800 is supplied with calibration solenoids and the solenoids have been activated. During the Calibration Verify function the analog output signals will track the oxygen and combustibles readings.
  • Page 76: Performing A Calibration Verify With The Loi

    Instruction Manual Section 3: Configuration and Startup IM-106-880C, OI April 2017 From the METHODS menu, select OCX Cal Verify. From this menu, select the functions as follows: • Flow High O2 Gas - Flows the high O2 test gas for the time specified in the calibration setup.
  • Page 77: Calibration Tolerance Feature

    Section 3: Configuration and Instruction Manual Startup IM-106-880C, OI April 2017 Calibration Tolerance Feature The calibration tolerance feature provides a mechanism to fail a calibration if the calibration measurement does not fall within a specific tolerance of the test gas value. The tolerance is preset within the Hazardous Area OCX 8800 software and is not user adjustable.
  • Page 78: Coe Purge/ Zero Feature

    Instruction Manual Section 3: Configuration and Startup IM-106-880C, OI April 2017 COe Purge/ Zero Feature This feature provides a way to periodically flood the COe sensor with air to perform two functions; a) provide additional oxygen to help burn off any combustible residue from the COe sensor, and b) allow for optional adjustment of the COe calibration constant.
  • Page 79: Configuring The Coe Zero Feature With The Field

    Section 3: Configuration and Instruction Manual Startup IM-106-880C, OI April 2017 3.9.1 Configuring the COe Zero Feature with the Field Communicator - HART At the completion of the COe Zero Function, the COe analog output signal will change if the Zero Update parameter is set to "Yes". Use the 375 Field Communicator or AMS software to access the HART menu.
  • Page 80: Configuring The Coe Zero Feature With The Loi

    Instruction Manual Section 3: Configuration and Startup IM-106-880C, OI April 2017 • COe Zero Duration - Length of time COe zero gas flows. Range is 120 to 600 seconds. Default is 120 seconds. • COe Zero Purge Time - Length of time after COe zero is complete before oxygen/ combustibles readings are considered valid.
  • Page 81: Ocx Reset With The Loi

    Section 3: Configuration and Instruction Manual Startup IM-106-880C, OI April 2017 3.10.1 OCX Reset with the LOI Use the "Z" pattern to enter the LOI menu tree. (Refer to Section Select the SYSTEM submenu. From the SYSTEM submenu, select the Status submenu. From the Status submenu, select Reset Device.
  • Page 82: Section 4: Using The Loi

    Instruction Manual Section 4: Using the IM-106-880C, OI April 2017 Section 4: Using the LOI Section contents Overview ......................page Display Orientation ....................page LOI Controls ......................page LOI Menu Tree ...................... page Overview This section describes the installation and operation of the LOI module in the Hazardous Area OCX 8800. Display Orientation The LOI module mounts to a connector on the LOI board.
  • Page 83: Loi Controls

    Section 4: Using the Instruction Manual IM-106-880C, OI April 2017 LOI Controls 4.1.1 Overview The LOI, shown in Figure 4.1.2, utilizes a bright blue gas-fluorescent display. Intensity is adjustable. There is an Infrared LED source and a detector for each key. The detectors can detect a finger placed above the button through the glass window.
  • Page 84: Lockout

    Instruction Manual Section 4: Using the IM-106-880C, OI April 2017 4.1.4 Lockout The LOI has a lockout feature that prevents nuisance actuation by someone brushing against the glass window, raindrops, dirt, insects, etc. This lockout mode is automatically established when no buttons are pushed for 30 seconds (default).
  • Page 85: Loi Status Codes

    Section 4: Using the Instruction Manual IM-106-880C, OI April 2017 4.1.5 LOI Status Codes The LOI display shows a status code in the lower right hand corner of the display. There are nine status codes to indicate the existing status of the device during operation. The status code descriptions are shown in Table 4-1.
  • Page 86: Third And Fourth Column Submenus

    Instruction Manual Section 4: Using the IM-106-880C, OI April 2017 4.2.3 Third and Fourth Column Submenus From the second column submenus, selecting the right-pointing key moves the display into the third column submenus. The third column submenu may be another menu or a list of parameters. The up- and down-pointing keys allow the display to move to the different parameters or menus.
  • Page 87: Figure 4-6 Loi Menu Tree (Sheet 2 Of 4)

    Section 4: Using the Instruction Manual IM-106-880C, OI April 2017 Figure 4-6 LOI Menu Tree (Sheet 2 of 4) Third and Fourth Column Submenus...
  • Page 88: Figure 4-7 Loi Menu Tree (Sheet 3 Of 4)

    Instruction Manual Section 4: Using the IM-106-880C, OI April 2017 Figure 4-7 LOI Menu Tree (Sheet 3 of 4) Third and Fourth Column Submenus...
  • Page 89: Figure 4-8 Loi Menu Tree (Sheet 4 Of 4)

    Section 4: Using the Instruction Manual IM-106-880C, OI April 2017 Figure 4-8 LOI Menu Tree (Sheet 4 of 4) Third and Fourth Column Submenus...
  • Page 90: Section 5: Calibration

    Instruction Manual Section 5: Calibration IM-106-880C, OI April 2017 Section 5: Calibration Section contents Overview ........................page 65 Fully Automatic Calibration ...................page 65 Operator - Initiated Autocalibration ................page 66 Manual Calibration ......................page 67 D/A Trim Procedures - LOI .....................page 75 D/A Trim Procedures - HART ..................page 77 Overview During a calibration, two calibration gases with known O...
  • Page 91: Operator - Initiated Autocalibration

    Section 5: Instruction Manual Calibration IM-106-880C, OI April 2017 between automatic COe calibrations. To disable automatic calibration for O2 and COe, enter 0 for both CalIntrvl parameters. If desired, the O2NxtCalTm and the COeNxtCalTm (next calibration time) parameters can be changed to synchronize a calibration at a specific day or time. When setting automatic calibration times, CalIntrvl and NxtCalTm should be set so that O2 and COe are NOT calibrated simultaneously..
  • Page 92: Manual Calibration

    Instruction Manual Section 5: Calibration IM-106-880C, OI April 2017 Manual Calibration If a unit is not equipped with calibration solenoids, a calibration must be performed by an operator following prompts from the unit. Refer to the following paragraphs for manual calibration.
  • Page 93: Manual O2 Calibration Using The Field Communicator - Hart

    Section 5: Instruction Manual Calibration IM-106-880C, OI April 2017 5.5.2 Manual O Calibration using the Field Communicator - HART To perform a manual O calibration using the HART communicator or AMS, use the following procedure. If necessary, refer to Section 4, Using HART Communications, for the HART menu tree.
  • Page 94: Manual Coe Calibration Using The Field Communicator - Hart

    Instruction Manual Section 5: Calibration IM-106-880C, OI April 2017 The Calibration Status should be automatically changed to FlowO2Low and then ReadO2Low for a period of time. During this period, if an attempt is made to go to the next calibration step by pressing OK and selecting Start/Next Cal Step, you will be prompted with Operator step command is not accepted at this time.
  • Page 95 Section 5: Instruction Manual Calibration IM-106-880C, OI April 2017 The main Calibration screen should look like the following. Press OK to continue. • OCX: TAG NAME • STEP: Idle • TIME REMAIN: 0s • COe: 0.20 ppm • COe DELTA R: 0.00 ohm •...
  • Page 96: Manual O2 And Coe Calibration Using The Field Communicator - Hart

    Instruction Manual Section 5: Calibration IM-106-880C, OI April 2017 5.5.4 Manual O and COe Calibration using the Field Communica- tor - HART To perform a manual O and COe calibration using the Field Communicator or AMS, use the following procedure. If necessary, refer to Section 6, Field Communicator, for the HART menu tree.
  • Page 97 Section 5: Instruction Manual Calibration IM-106-880C, OI April 2017 Select START CAL/STEP to start applying the O Low Gas. The time to apply the test gas is specified by the Gas Time. The Calibration Status should automatically change to FIowO2Low and then ReadO2Low for a period of time.
  • Page 98: Manual O2/Coe Calibration Using The Field Communicator - Fieldbus

    Instruction Manual Section 5: Calibration IM-106-880C, OI April 2017 5.5.5 Manual O /COe Calibration using the Field Communicator - Fieldbus To perform a manual O /COe calibration using the 375 Field Communicator, use the following procedure. If necessary, refer to Section 6, Field Communicator, for the Fieldbus menu tree.
  • Page 99 Section 5: Instruction Manual Calibration IM-106-880C, OI April 2017 The Calibration Screen should look like the following, press OK to continue. The Calibration Screen should be automatically refreshed, however it may take a while for the data to refresh. • Calibration Step = Apply O2 Low Gas •...
  • Page 100: D/A Trim Procedures - Loi

    Instruction Manual Section 5: Calibration IM-106-880C, OI April 2017 D/A Trim Procedures - LOI 5.6.1 D/A trim procedure using the LOI Use the following procedure to perform the O D/A trim procedure at the LOI. Refer to the LOI menu tree in Figure 4-5.
  • Page 101: Coe D/A Trim Procedure Using The Loi

    Section 5: Instruction Manual Calibration IM-106-880C, OI April 2017 5.6.2 COe D/A trim procedure using the LOI Use the following procedure to perform the COe D/A trim procedure at the LOI. Refer to the LOI menu tree in Figure 4-5. To avoid a potentially dangerous operating condition, the Hazardous Area OCX 8800 must be removed from the automatic combustion control loop before you start the D/A trim procedure.
  • Page 102: D/A Trim Procedures - Hart

    Instruction Manual Section 5: Calibration IM-106-880C, OI April 2017 D/A Trim Procedures - HART 5.7.1 D/A trim procedure using HART Use the following procedure to perform the O D/A trim procedure using the Field Communicator. If necessary, refer to Section 6, Field Communicator, for the HART menu tree.
  • Page 103: Coe D/A Trim Procedure Using Hart

    Section 5: Instruction Manual Calibration IM-106-880C, OI April 2017 5.7.2 COe D/A trim procedure using HART Use the following procedure to perform the COe D/A trim procedure using the Field Communicator. If necessary, refer to Section 6, Field Communicator, Field Communicator, for the HART menu tree.
  • Page 104: Section Contents

    Instruction Manual Section 6: Field Communicator IM-106-880C, OI April 2017 Section 6: Field Communicator Section contents Overview ......................page 79 Field Communicator Connections .................page 79 Hart Menu Tree ....................page Fieldbus Menu Tree ....................page Overview The 375 Field Communicator is a communication interface device. It supports HART and Fieldbus devices letting you configure and troubleshoot in the field.
  • Page 105: Connecting To A Fieldbus Segment

    Section 6: Field Instruction Manual Communicator IM-106-880C, OI April 2017 Figure 6-2 375 Communicator Connections - HART 6.3.2 Connecting to a Fieldbus Segment Connect 375 Field Communicator with the supplied lead set in parallel with the device to a Fieldbus segment, Figure 6-3.
  • Page 106: Off-Line And On-Line Operations

    Instruction Manual Section 6: Field Communicator IM-106-880C, OI April 2017 Off-Line and On-Line Operations The Field Communicator can be operated both off-line and on-line. Off-line operations are those in which the communicator is not connected to the Hazardous Area OCX 8800. Off-line operations can include interfacing the Field Communicator with a PC (refer to applicable Field Communicator documentation regarding Model 375/PC applications).
  • Page 107: Hart Menu Tree

    Section 6: Field Instruction Manual Communicator IM-106-880C, OI April 2017 Hart Menu Tree This section provides a menu tree for the Field Communicator. This menu is specific to the Hazardous Area OCX 8800 applications. Figure 6-4 HART Menu Tree (Sheet 1 of 4) Hart Menu Tree...
  • Page 108: Figure 6-5 Hart Menu Tree (Sheet 2 Of 4)

    Instruction Manual Section 6: Field Communicator IM-106-880C, OI April 2017 Figure 6-5 HART Menu Tree (Sheet 2 of 4) Hart Menu Tree...
  • Page 109: Figure 6-6 Hart Menu Tree (Sheet 3 Of 4)

    Section 6: Field Instruction Manual Communicator IM-106-880C, OI April 2017 Figure 6-6 HART Menu Tree (Sheet 3 of 4) Hart Menu Tree...
  • Page 110: Figure 6-7 Hart Menu Tree (Sheet 4 Of 4)

    Instruction Manual Section 6: Field Communicator IM-106-880C, OI April 2017 Figure 6-7 HART Menu Tree (Sheet 4 of 4) Hart Menu Tree...
  • Page 111: Fieldbus Menu Tree

    Section 6: Field Instruction Manual Communicator IM-106-880C, OI April 2017 Fieldbus Menu Tree This section consists of a menu for the Field Communicator. This menu is specific for the Hazardous Area OCX 8800 Applications. Refer to the Fieldbus Parameter Descriptions for the applicable range, units, and description for the Fieldbus menu parameters.
  • Page 112: Figure 6-9 Fieldbus Menu Tree (Sheet 2 Of 3)

    Instruction Manual Section 6: Field Communicator IM-106-880C, OI April 2017 Figure 6-9 Fieldbus Menu Tree (Sheet 2 of 3) Fieldbus Menu Tree...
  • Page 113: Figure 6-10 Fieldbus Menu Tree (Sheet 3 Of 3)

    Section 6: Field Instruction Manual Communicator IM-106-880C, OI April 2017 Figure 6-10 Fieldbus Menu Tree (Sheet 3 of 3) Fieldbus Menu Tree...
  • Page 114: Section 7: Foundation Fieldbus

    Fieldbus an enabling technology. OUNDATION EMERSON offers a full range of products from field devices to the DeltaV scalable control system to allow an easy transition to Fieldbus technology. The Fieldbus retains the features of the 4-20 mA analog system, including standardized physical...
  • Page 115 Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 interface to the wire, bus powered devices on a single wire, and intrinsic safety options, and enables additional capabilities such as: • Increased capabilities due to full digital communications. • Reduced wiring and wire terminations due to multiple devices on one set of wires.
  • Page 116: Introduction

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 NOTE: The following descriptions and definitions are not intended as a training guide for Foundation Fieldbus technology but are presented as an overview for those not familiar with Fieldbus and to define device specific attributes for the Fieldbus system engineer.
  • Page 117: Device Descriptions

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Contained parameters are internal to function blocks and do not appear as normal input and output parameters. However, they may be accessed and modified remotely, as specified by the function block. Input events may affect the operation of the algorithm.
  • Page 118: Instrument-Specific Function Blocks

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 the bus. Instead their displays and interactions with devices are driven from the device descriptions. Device descriptions may also include a set of processing routines called methods. Methods provide a procedure for accessing and manipulating parameters within a device. 7.2.5 Instrument-Specific Function Blocks In addition to function blocks, Fieldbus devices contain two other block types to support the...
  • Page 119: Network Communication

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Network Communication Figure 7-3 illustrates a simple Fieldbus network consisting of a single segment (link). Figure 7-3 Single Link Fieldbus Network 7.5.1 Link Active Scheduler (LAS) All links have one and only one Link Active Scheduler (LAS). The LAS operates as the us arbiter for the link.
  • Page 120: Device Addressing

    Fieldbus uses addresses between 0 and 255. Addresses 0 through 15 are reserved for group addressing and for use by the data link layer. For all EMERSON Fieldbus devices addresses 20 through 35 are available to the device. If there are two or more devices with the same address, the first device to start will use its programmed address.
  • Page 121: Resource Block

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Resource Block 7.7.1 PlantWeb Alerts The PlantWeb Alerts (PWA) software supports three groups of alarms for three severity levels: 1) Failed, 2) Maintenance, and 3) Advisory. Each PWA can be configured for one or more of the three alarm groups.
  • Page 122: Mapping Of Pwa

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.7.2 Mapping of PWA Description of the PlantWeb Alerts that are supported by the Hazardous Area OCX 8800 Fieldbus Output Board are listed in Table 7-3. Table 7-3 Description of PlantWeb Alerts. What does the alert Recommended...
  • Page 123 Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 What does the alert Recommended Alerts Alarms indicate? Action Description Sensor Heater Transducer This alert Check heater Mechanical or thermal stress may eventually Malfunction Block Heater indicates that circuit for lose or cause the sensor heater to fail.
  • Page 124 Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 What does the alert Recommended Alerts Alarms indicate? Action Description Calibration Transducer Calib- This alert Check instrument Oxygen cells will degrade over time due to Recommended Block: ration indicates that accuracy and/or aging and corrosion.
  • Page 125: Pwa Simulate

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 What does Recommended the alert Alerts Alarms indicate? Action Description Line Input Out Transducer Device This alert Check line input The device power supply continuously of Range Block: Alerts indicates that power for proper monitors the line input.
  • Page 126: Fieldbus/Pwa Simulate

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.7.4 Fieldbus/PWA Simulate Fieldbus simulation and PWA simulation can be enabled and disabled using the DD method. Use the "Transmitter Options" method to enable/disable the Fieldbus or PlantWeb Alerts simulation. Selecting “Fieldbus simulation”...
  • Page 127: Figure 7-4 Simulate Pwa Screen

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Figure 7-4 Simulate PWA Screen If PWA Simulation is on, all PWA active parameters and Resource and Transducer Block status parameters are configurable. Otherwise they are read-only. To simulate PlantWeb alerts, use the "Simulate PWA" screens in the Resource Block. To simulate block alarms, use "Simulate TB Temperature Sensor - Temperature Status", "Simulate TB Temperature Status", or "Simulate TB Calibration Device - FF Status"...
  • Page 128: Configure Simulation With The Model 375 Field Communicator

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Configure Simulation with the Model 375 Field Communicator Use the following procedure to configure PWA simulation using the Model 375 Field Communicator. Run "Transmitter Options" method in the Resource Block (Resource | Methods). In the "Transmitter Options"...
  • Page 129: Support Resource Block Errors

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.8.1 Support Resource Block Errors Resource Block Out of Service • Set Whenever the resource block actual mode is OOS. Power Up • Set whenever the FF card powers up. Block Configuration Error •...
  • Page 130: Table 7-4 Transducer Block Parameter Description

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Table 7-4 Transducer Block Parameter Description Parameter Mnemonic Valid Range Units Description Table 7-8 ALARM_RELAY_EVENT1 Enumerated The first of three conditions that cause the alarm output to turn on.. Table 7-8 ALARM_RELAY_EVENT2 Enumerated The second of three conditions that cause the alarm output to turn...
  • Page 131 Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Parameter Mnemonic Valid Range Units Description COMB_PERCENT_OF_ The percent of range of the current combustibles reading. RANGE COMB_PREVIOUS_ The combustibles calibration constant from the previous good cali- CONSTANT bration. COMB_PREVIOUS_SLOPE PPM/Ohm The combustibles calibration slope from the previous good calibration.
  • Page 132 Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Parameter Mnemonic Valid Range Units Description ELECTRONICS_TEMP °C The current temperature reading of the electronics temperature sensor. The current voltage reading of the electronics temperature sensor. ELECTRONICS_TEMP_ INPUT INITIATE_BLOWBACK 1=Do a manual This initiates a blowback cycle.
  • Page 133 Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Parameter Mnemonic Valid Range Units Description O2_SLOPE 34.5-57.5 mV/Decade The O calibration slope. O2_T90 0-300 Seconds The amount of time that the O2 process variable will take to reach 90% of the actual process variable. O2_TEMP_MAX °C The highest O...
  • Page 134: Transducer Block Enumerations

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.10 Transducer Block Enumerations 7.10.1 Calibration States During a running calibration procedure, the states below reflect the current step that the calibration is running in. Refer to Table 7-5. Table 7-5 Calibration State- Values Index CAL_STATE Description Operator Ack Required to Continue...
  • Page 135: Table 7-7 Blowback State Enumerations

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Blowback States Table 7-7 Blowback State Enumerations BLOWBACK_STATE Description Idle Blow Purge Alarm Events Table 7-8 Alarm Event Enumerations ALARM_RELAY_EVENT Description In Calibration O2 Cell Temp Error O2 Heater Open O2 Cell Bad Cal Failed Cal Warn...
  • Page 136: Table 7-10 Sensor Housing Enumerations

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Sensor Housing Type Table 7-10 Sensor Housing Enumerations SENSOR_HOUSING_TYPE Description TYPE 1 TYPE 2 TYPE 3 Cal Results Table 7-11 Cal Results Bit Enumerations CAL_RESULTS Description O2 Slope Error O2 Constant Error O2 Tolerance Check Failed CO Slope Error O2 Constant Error...
  • Page 137: Table 7-14 Coe Zero State Enumerations

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 COe Zero States Table 7-14 COe Zero State Enumerations COZERO_STATE Description Idle Flowing Purging COe Out Tracks Table 7-15 COe Out Tracks Enumerations COZERO_OUTTRAK Description None Both Detailed Status Table 7-16 Detailed Status Alarm Value of Number Description...
  • Page 138: Transducer Block Channel Assignments For Ai Blocks

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Alarm Value of Number Description XD_ERROR (see FF- 903) Sample Block Temperature Low Mechanical Failure Sample Block Temperature High Mechanical Failure Sample Block Temperature Very High Mechanical Failure Sample Block Heater Failure Mechanical Failure Sample Block Heater Ramp Rate Electronics Failure...
  • Page 139: Transducer Block Channel Status

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.10.4 Transducer Block Channel Status The status of channel 1 to 4 are affected by the state of unit alarm. In all cases, the channel will read what it believes the correct sensor values. Self-Clearing alarms are reset when the alarm condition goes away.
  • Page 140: Transducer Block Simulate

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.10.5 Transducer Block Simulate Setting PWA_SIMULATE to ON also allows simulating TB status and to check the correct mapping onto the PWA’s FAILED_ACTIVE, MAINT_ACTIVE, and ADVISE_ACTIVE parameters. 7.10.6 Support Transducer Block Errors Out of Service •...
  • Page 141: Table 7-20 Definitions Of Analog Input Function Block System Parameters

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 The Analog Input (AI) function block processes field device measurements and makes them available to other function blocks. The output value from the AI block is in engineering units and contains a status indicating the quality of the measurement.
  • Page 142 Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Index Number Units Parameter Description HI_HI_LIM EU of PV_SCALE The setting for the alarm limit used to detect the HI HI alarm condition. HI_HI_PRI None The priority of the HI HI alarm. HI_LIM EU of PV_SCALE The setting for the alarm limit used to detect the HI alarm condition.
  • Page 143: Simulation

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.11.2 Simulation To support testing, you can either change the mode of the block to manual and adjust the output value, or you can enable simulation through the configuration tool and manually enter a value for the measurement value and its status.
  • Page 144: Filtering

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Figure 7-7 Analog Input Function Block Timing Diagram 7.11.3 Filtering The filtering feature changes the response time of the device to smooth variations in output readings caused by rapid changes in input. You can adjust the filter time constant (in seconds) using the PV_FTIME parameter.
  • Page 145: Indirect Signal Conversion

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.11.6 Indirect signal conversion Indirect signal conversion converts the signal linearly to the accessed channel input value (or the simulated value when simulation is enabled) from its specified range (XD_SCALE) to the range and units of the PV and OUT parameters (OUT_SCALE).
  • Page 146: Block Errors

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.11.8 Block Errors lists conditions reported in the BLOCK_ERR parameter. Conditions in italics Table 7-21 are inactive for the AI block and are given here only for your reference. Table 7-21 BLOCK_ERR Conditions Condition Number Condition Name and Description...
  • Page 147: Alarm Detection

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.11.10 Alarm Detection A block alarm will be generated whenever the BLOCK_ERR has an error bit set. The types of block error for the AI block are defined above. Process Alarm detection is based on the OUT value. You can configure the alarm limits of the following standard alarms: •...
  • Page 148: Status Handling

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.11.11 Status Handling Normally, the status of the PV reflects the status of the measurement value, the operating condition of the I/O card, and any active alarm condition. In Auto mode, OUT reflects the value and status quality of the PV.
  • Page 149: Application Information

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.11.13 Application Information The configuration of the AI function block and its associated output channels depends on the specific application. A typical configuration for the AI block involves the following parameters: Channel If the device supports more than one measurement, verify that the selected channel contains the appropriate measurement or derived value.
  • Page 150: Pressure Transmitter Used To Measure Level In An Open Tank

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Figure 7-8 Analog Input Function Block Configuration for a Typical Temperature Transmitter 7.11.15 Pressure Transmitter used to Measure Level in an Open Tank Situation #1 The level of an open tank is to be measured using a pressure tap at the bottom of the tank. The level measurement will be used to control the level of liquid in the tank.
  • Page 151: Table 7-23 Analog Input Function Diagram For A Pressure Transmitter Used In Level Measurement (Situation #1)

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Solution to Situation #1 Table 7-23 lists the appropriate configuration settings, and Figure 7-9 illustrates the correct function block configuration. Table 7-23 Analog Input Function Diagram for a Pressure Transmitter used in Level Measurement (Situation #1) Parameter Configured Values...
  • Page 152: Table 7-24 Analog Input Function Diagram For A Pressure Transmitter Used In

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Situation #2 The transmitter in situation #1 is installed below the tank in a position where the liquid column in the impulse line, when the tank is empty, is equivalent to 2.0 psi (Figure 7-11).
  • Page 153: Differential Pressure Transmitter To Measure Flow

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.11.16 Differential Pressure Transmitter to Measure Flow Situation The liquid flow in a line is to be measured using the differential pressure across an orifice plate in the line, and the flow measurement will be used in a flow control loop. Based on the orifice specification sheet, the differential pressure transmitter was calibrated for 0 to 20 in H 0 for a flow of 0 to 800 gal/min, and the transducer was not configured to take the square root of the...
  • Page 154: Troubleshooting

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.11.17 Troubleshooting Refer to Table 7-26 to troubleshoot any problems that you encounter. Table 7-26 Troubleshooting Symptom Possible Cause Corrective Action Mode will not leave 1. Target mode not set 1.
  • Page 155: Proportional/ Integral/Derivative (Pid) Function Block

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.12 Proportional/ Integral/Derivative (PID) Function Block The PID function block combines all of the necessary logic to perform proportional/integral/ derivative (PID) control. The block supports mode control, signal scaling and limiting, feedforward control, override tracking, alarm limit detection, and signal status propagation.
  • Page 156: Table 7-27 Pid Function Block System Parameters

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 To further customize the block for use in your application, you can configure filtering, feedforward inputs, tracking inputs, setpoint and output limiting, PID equation structures, and block output action. Table 7-27 lists the PID block parameters and their descriptions, units of measure, and index numbers, and Figure 7-15...
  • Page 157 Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Index Parameter Number Units Description CONTROL_OPTS None Allows you to specify control strategy options. The supported control options for the PID block are Track enable, Track in Manual, SP-PV Track in Man, SP-PV Track in LO or IMAN, Use PV for BKCAL OUT, and Direct Acting.
  • Page 158 Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Index Parameter Number Units Description LO_PRI None The priority of the LO alarm. MATH_FORM None Selects equation form (series or standard). MODE_BLK None The actual, target, permitted, and normal modes of the block. Target: The mode to “go to”...
  • Page 159 Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Index Parameter Number Units Description ST_REV None The revision level of the static data associated with the function block. The revision value will be incremented each time a static parameter val- ue in the block is changed.
  • Page 160: Figure 7-15 Pid Function Block Schematic

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Figure 7-15 PID Function Block Schematic Proportional/ Integral/Derivative (PID) Function Block...
  • Page 161: Setpoint Selection And Limiting

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.12.1 Setpoint Selection and Limiting The setpoint of the PID block is determined by the mode. You can configure the SP_HI_LIM and SP_LO_LIM parameters to limit the setpoint. In Cascade or RemoteCascade mode, the setpoint is adjusted by another function block or by a host computer, and the output is computed based on the setpoint.
  • Page 162 Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Tracking You enable the use of output tracking through the control options. You can set control options in Manual or Out of Service mode only. The Track Enable control option must be set to True for the track function to operate. When the Track in Manual control option is set to True, tracking can be activated and maintained only when the block is in Manual mode.
  • Page 163: Pid Equation Structures

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.12.2 PID Equation Structures Configure the STRUCTURE parameter to select the PID equation structure. You can select one of the following choices: • PI Action on Error, D Action on PV •...
  • Page 164: Block Errors

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.12.5 Block Errors lists conditions reported in the BLOCK_ERR parameter. Conditions in italics Table 7-28 are inactive for the PID block and are given here only for your reference. Table 7-28 BLOCK _ERR Conditions Condition Number Condition Name and Description...
  • Page 165: Alarm Detection

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.12.7 Alarm Detection A block alarm will be generated whenever the BLOCK_ERR has an error bit set. The types of block error for the AI block are defined above. Process alarm detection is based on the PV value. You can configure the alarm limits of the following standard alarms: •...
  • Page 166: Status Handling

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.12.8 Status Handling If the input status on the PID block is Bad, the mode of the block reverts to Manual. In addition, you can select the Target to Manual if Bad IN status option to direct the target mode to revert to manual.
  • Page 167 Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 The MODE parameter is a switch that indicates the target and actual mode of operation. Mode selection has a large impact on the operation of the PID block: • Manual mode allows the operator to set the value of the loop output signal directly. •...
  • Page 168: Application Examples

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.12.10 Application Examples Basic PID Block for Steam Heater Control Situation A PID block is used with an AI block and an AO block to control the flow steam used to heat a process fluid in a heat exchanger.
  • Page 169: Figure 7-19 Pid Function Block Diagram For Steam Heater Control Example

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Solution The PID loop uses TT101 as an input and provides a signal to the analog output TCV101. The BKCAL_OUT of the AO block and the BKCAL_IN of the PID block communicate the status and quality of information being passed between the blocks.
  • Page 170: Cascade Control With Master And Slave Loops

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Figure 7-21 PID Function Block Diagram for Feedfoward Control 7.12.11 Cascade Control with Master and Slave Loops Situation A slave loop is added to a basic PID control configuration to measure and control steam flow to the steam heater.
  • Page 171: Figure 7-22 Pid Function Block Cascade Control Example

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Figure 7-22 PID Function Block Cascade Control Example Solution If the flow is controlled, steam pressure variations will be compensated before they significantly affect the heat exchanger temperature. The output from the master temperature loop is used as the setpoint for the slave steam flow loop.
  • Page 172: Cascade Control With Override

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Figure 7-23 PID Function Block Diagram for Cascade Control Example 7.12.12 Cascade Control with Override You can use the PID function block with other function blocks for complex control strategies. Figure 7-24 illustrates the function block diagram for cascade control with override.
  • Page 173: Figure 7-24 Function Block Diagram For Cascade Control With Override

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Figure 7-24 Function Block Diagram for Cascade Control with Override Cascade Control with Override...
  • Page 174: Troubleshooting

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.12.13 Troubleshooting Refer to Table 7-30 to troubleshoot any problems that you encounter. Table 7-30 Troubleshooting Symptom Possible Causes Corrective Action Mode will not leave 1. Target mode not set 1.
  • Page 175: Figure 7-25 Arithmetic (Arthm) Function Block

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Symptom Possible Causes Corrective Action Mode sheds from RCAS 1. Remote Cascade Value 1. Host system is not writing RCAS_IN with a quality and status of to AUTO “good cascade” within shed time (see 2 below). 2.
  • Page 176: Table 7-31 Arithmetic (Arthm) Block

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Table 7-31 Arithmetic (ARTHM) Block Index Description Number Parameter Units ALERT_KEY None The identification number of the plant unit. This information may be used in the host fro sorting alarms, etc. ARITH_TYPE None The set of 9 arithmetic functions applied as compensation to or...
  • Page 177 Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Index Number Parameter Units Description EU of OUT_SCALE or The analog output value and status. The number of outputs is an extensible Percent or EU of IN parameter in some blocks. OUT_HI_LIM EU of OUT_SCALE The maximum output value allowed.
  • Page 178: Block149 Errors

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Figure 7-26 Arithmetic Function Block Diagram 7.13.1 Block Errors Table 7-32 lists the conditions reported in the BLOCK_ERR parameter. Table 7-32 BLOCK_ERR Parameters Condition Number Condition Name and Description Other: The output has a quality of uncertain. Block Configuration Error: Select type is not configured Link Configuration Error Simulate Active...
  • Page 179: Modes

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.13.2 Modes The ARTHM block supports the following modes: • Manual (Man) – The block output (OUT) may be set manually. • Automatic (Auto) – OUT reflects the analog input measurement or the simulated value when simulation is enabled.
  • Page 180: Compensation Input Calculations

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.13.5 Compensation Input Calculations For each of the inputs IN_1, IN_3, IN_4 there is a gain and bias. The compensation terms (t) are calculated as follows: • When IN_(k) is usable: t(k) = GAIN_IN(k) * (BIAS_IN(k) + IN_(k)) •...
  • Page 181: Figure 7-27 Relative Temperature Effects On Level

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Figure 7-27 Relative Temperature Effects on Level The calculation is done by applying the level signal to the IN connector, the liquid temperature to the IN_1 connector, and the ambient air temperature to the IN_2 connector. Select the Arithmetic type (ARITH_TYPE) of Flow Compensation - Linear.
  • Page 182: Arithmetric Types

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.14 Advanced Topics 7.14.1 Arithmetric Types The parameter ARITH_TYPE determines how PV and the compensation terms (t) are combined. User may select from nine (9) commonly used math functions, depicted below. COMP_HI and COMP_LO are compensation limits.
  • Page 183: Troubleshooting

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.14.2 Troubleshooting Refer to to troubleshoot any problems that you encounter. Table 7-34 Table 7-34 Troubleshooting Symptom Possible Causes Corrective Action Model will not leave OOS Target model not set Set target mode to something other than OOS.
  • Page 184: Input Selector (Isel) Function Block

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.15 Input Selector (ISEL) Function Block Figure 7-29 Input Selector (ISEL) Function Block The Input Selector (ISEL) function block can be used to select the first good, Hot Backup, maximum, minimum, or average of as many as four input values and place it at the output. The block supports signal status propagation.
  • Page 185 Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Index Number Description Units DISABLE_2 None A Connection from another block that disables the associated input fromthe selection. DISABLE_3 None A Connection from another block that disables the associated input fromthe selection.
  • Page 186: Block Errors

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 Figure 7-30 Input Selector Function Block Schematic 7.15.1 Block Errors Table 7-36 lists the conditions reported in the BLOCK_ERR parameter. Conditions in italics are inactive for the ISEL block and are listed for reference only. Table 7-36 Block Error Conditions Condition Num- Condition Name and Description...
  • Page 187: Modes

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 7.15.2 Modes The ISEL function block supports three modes of operation as defined by the MODE_BLK parameter: • Manual (Man) The block output (OUT) may be set manually. • Automatic (Auto) OUT reflects the selected value. •...
  • Page 188: Status Handling

    Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 7.15.5 Status Handling In Auto mode, OUT reflects the value and status quality of the selected input. If the number of inputs with Good status is less than MIN_GOOD, the output status will be Bad. In Man mode, the OUT status high and low limits are set to indicate that the value is a constant and the OUT status is always Good.
  • Page 189: Table 7-38 Input Selector Function Blocks

    Instruction Manual Section 7: Foundation Fieldbus IM-106-880C, OI April 2017 Figure 7-32 Input Selector Function Block Application Example (SEL_TYPE = avg.). Figure 7-33 Input Selector Function Block Application Example (SEL_TYPE = Hot Backup) Table 7-38 Input Selector Function Blocks Selected Value Value Time...
  • Page 190: Troubleshooting

    1. STATUS_OPTS has Propagate Fault Forward bit set. This should be cleared to cause an alarm to occur. 7.16 Operation with Emerson DeltaV 7.16.1 About AMS and DeltaV Software AMS and DeltaV software allows users to manage their instrumentation, and to perform on-line configurations of their instruments.
  • Page 191: Figure 7-34 Deltav Explorer

    *.reg file. The files probably will be on a floppy disk or a CD-ROM that accompanies your device. On CD-ROMs delivered together with Emerson analyzers the files are located in the directory \Fieldbus. Dependent on the existent system use the files of the appropriate subdirectory.
  • Page 192 Section 7: Foundation Instruction Manual Fieldbus IM-106-880C, OI April 2017 About AMS and DeltaV Software...
  • Page 193: Section 8: Troubleshooting

    Instruction Manual Section 8: Troubleshooting IM-106-880C, OI April 2017 Section 8: Troubleshooting Section contents Overview ......................page Diagnostic Alarms ....................page Fault Isolation .....................page Alarm Relay Events .....................page Install all protective equipment covers and safety ground leads after troubleshooting. Failure to install covers and ground leads could result in serious injury or death. Overview The troubleshooting section describes how to identify and isolate faults that may develop in the Hazardous Area OCX 8800.
  • Page 194 Instruction Manual Section 8: Troubleshooting IM-106-880C, OI April 2017 In the event that the Hazardous Area OCX 8800 will not power up at all, check the incoming power supply to make sure power is being delivered to the Hazardous Area OCX 8800. If the incoming power supply is good, then check fuses F1 and F6 in the electronics housing.
  • Page 195: Diagnostic Alarms

    Diagnostic Alarms Instruction Manual April 2017 IM-106-880C, OI Figure 8-3 Fuse Locations Diagnostic Alarms Always install a blocking diode on the customers relay coil. Failure to install a blocking diode may create noise spikes and cause faults in the OCX electronics. The Hazardous Area OCX 8800 is equipped with a set of alarm relay contacts on the microprocessor board in the electronics housing.
  • Page 196: Fault Isolation

    Instruction Manual Fault Isolation IM-106-880C, OI April 2017 Fault Isolation Faults in the Hazardous Area OCX 8800 Transmitter are indicated by messages displayed on the 375 Field Communicator or LOI. Fault indications that can appear are listed in Table 8-1. If a fault is indicated on the Field Communicator or LOI, locate the fault indication in Table 8-2.
  • Page 197 Fault Isolation Instruction Manual April 2017 IM-106-880C, OI SB Temp Hi (Sample block heater temperature high, > 190 ºC) Probable Cause Recommended Corrective Action High noise in OCX power supply Check power supply for line noise or voltage fluctuations. Install power line filter (PN 6A00171G01) or high quality line filter for input power.
  • Page 198 Instruction Manual Fault Isolation IM-106-880C, OI April 2017 SB TC Open (Sample block heater thermocouple open) Probable Cause Recommended Corrective Action Sample block thermocouple or Check sample block thermocouple and circuit wires for breaks or loose thermocouple circuit open connections per Figure 8-5 and Repair breaks or loose connections or replace failed thermocouple.
  • Page 199 Fault Isolation Instruction Manual April 2017 IM-106-880C, OI ADC Failure (Voltage to digital conversion could not complete) ADC Ref Error (Voltage to digital conversion not accurate) Probable Cause Recommended Corrective Action Incorrect wiring between electronics and Check all wiring between the electronics and sensor housings per Figure 8-5. sensor housings Correct wiring faults.
  • Page 200: Figure 8-4. Oxygen And Cell Output

    Instruction Manual Fault Isolation IM-106-880C, OI April 2017 Cal Warning (Calibration warning) Cal Failed (Calibration failed) Probable Cause Recommended Corrective Action COe sensor degraded Replace COe sensor or increase warning level (SYSTEM, CALIB SETUP, COe Slope Warn via HART.) • COe Slope Error (Slope not between 200 ppm/Ohm to 4,500 ppm/Ohm)
  • Page 201 Fault Isolation Instruction Manual April 2017 IM-106-880C, OI Board Temp Hi (Electronics temperature maximum exceeded, > 85 ºC) Probable Cause Recommended Corrective Action Electronics housing exposed to high Insulate housing from source of high temperature and/or install cooling fan to ambient temperature remove heat from housing.
  • Page 202 Instruction Manual Fault Isolation IM-106-880C, OI April 2017 Line Voltage High (AC power line voltage above maximum, > 278 VAC) Probable Cause Recommended Corrective Action High noise or voltage fluctuations in power Check power supply for line noise or voltage fluctuations. Install power line filter supply kit (PN 6A00171G01) or high quality line filter for input power.
  • Page 203: Figure 8-5 Electrical Connections Between Electronics And Sensor Housing

    Fault Isolation Instruction Manual April 2017 IM-106-880C, OI Figure 8-5 Electrical Connections Between Electronics and Sensor Housing Fault Isolation...
  • Page 204: Alarm Relay Events

    Instruction Manual Alarm Relay Events IM-106-880C, OI April 2017 Alarm Relay Events The Hazardous Area OCX 8800 contains an alarm relay that can be configured to activate on one of twelve different groups of events. These event groups, and the conditions that trigger them, are listed in Table 8-2.
  • Page 205 Alarm Relay Events Instruction Manual April 2017 IM-106-880C, OI Alarm Relay Events...
  • Page 206: Section 9:Maintenance And Service

    Instruction Manual Section 9: Maintenance and Service IM-106-880C, OI April 2017 Section 9: Maintenance and Service Section contents Overview ............................page OCX 8800 Removal and Installation ....................page Repair Sensor Housing ........................page Repair Electronics Housing ......................page Electronics Housing Assembly ......................pag e Replace Tube Fittings ..............
  • Page 207: Ocx 8800 Removal And Installation

    OCX 8800 Removal and Instruction Manual Installation IM-106-880C, OI April 2017 OCX 8800 Removal and Installation Use the following procedures to remove or install the Hazardous Area OCX 8800. 9.3.1 OCX with Integral Electronics Remove Hazardous Area OCX 8800 Turn off power to the system. Shut off the test gases at the cylinders and shut off the instrument air.
  • Page 208 Instruction Manual OCX 8800 Removal and Installation IM-106-880C, OI April 2017 Remove the cover from the electronics housing to expose the electronics housing terminal blocks, Figure 9-2. Disconnect and remove the power leads from the AC power input terminal block and remove the ground lead from the ground stud.
  • Page 209: Figure 9-2 Electronics Housing Terminal Blocks

    OCX 8800 Removal and Instruction Manual Installation IM-106-880C, OI April 2017 Figure 9-2 Electronics Housing Terminal Blocks OCX with Integral Electronics...
  • Page 210: Install Hazardous Area Ocx 8800

    Instruction Manual OCX 8800 Removal and Installation IM-106-880C, OI April 2017 9.3.2 Install Hazardous Area OCX 8800 Observe the following cautions when installing the Hazardous Area OCX 8800 in a hot process stack. If the process is shut down and cooled, the transmitter can be installed in the stack prior to connecting the pneumatics and wiring.
  • Page 211: Figure 9-3 Ocx With Remote Electronics

    OCX 8800 Removal and Instruction Manual Installation IM-106-880C, OI April 2017 Figure 9-3 OCX with Remote Electronics Remove the cover from the sensor housing to expose the sensor housing terminal blocks, Figure 9-4. Disconnect the signal cable from the O and T/C terminal blocks, and from the CO and CJC terminal blocks.
  • Page 212: Install Sensor Housing

    Instruction Manual OCX 8800 Removal and Installation IM-106-880C, OI April 2017 Figure 9-4 Sensor Housing Terminals 9.3.4 Install Sensor Housing Insert and bolt the sensor housing in the stack and install insulation. Connect the test gas, reference air, eductor air, and dilution air lines to the sensor housing.
  • Page 213: Remove Remote Electronics Housing

    OCX 8800 Removal and Instruction Manual Installation IM-106-880C, OI April 2017 Connect the signal cable to O and T/C terminal blocks and to the CO and CJC terminal blocks, Figure 9-4. Connect the heater power cable to the HTR terminal blocks. Refer to Figure 9-3 and make sure all test gas lines and electrical connectors are...
  • Page 214: Figure 9-5 Electronics Housing Terminal Blocks

    Instruction Manual OCX 8800 Removal and Installation IM-106-880C, OI April 2017 Figure 9-5 Electronics Housing Terminal Blocks Remove Remote Electronics Housing...
  • Page 215: Install Remote Electronics Housing

    OCX 8800 Removal and Instruction Manual Installation IM-106-880C, OI April 2017 Figure 9-6 Remote Electronics Housing Cable Connections 9.3.6 Install Remote Electronics Housing Mount remote electronics housing on wall or pipe within distance of signal and heater cables in use. Remove the electronics housing cover.
  • Page 216: Repair Sensor Housing

    Instruction Manual Repair Sensor Housing IM-106-880C, OI April 2017 Connect the heater cable leads to the heater power connector (J3). Connect the line (L1 wire) to the L1 terminal, and the neutral (N wire) to the N terminal on the AC power input terminal block, Figure 9-6.
  • Page 217: Figure 9-7 Removal Of O2 Cell And Heater Strut Assembly

    Repair Sensor Instruction Manual Housing IM-106-880C, OI April 2017 Figure 9-7 Removal of O Cell and Heater Strut Assembly Sensor Housing Disassembly...
  • Page 218: Remove O2 Cell And Heater Strut Assembly

    Instruction Manual Repair Sensor Housing IM-106-880C, OI April 2017 9.4.2 Remove O Cell and Heater Strut Assembly Remove reference air tube (7, Figure 9-7) from sensor housing (8). Figure 9-8. Disconnect and tag O heater wires, O cell and return wires, and thermocouple wires at the sensor housing terminals.
  • Page 219: Remove Coe Sensor Assembly

    Repair Sensor Instruction Manual Housing IM-106-880C, OI April 2017 Figure 9-8 O Cell, Thermocouple, and Heater Connections 9.4.4 Remove COe Sensor Assembly Disconnect COe heater, thermocouple, and sensor wires from terminal blocks. Refer to Figure 9-9. Remove insulator (1, Figure 9- 10).
  • Page 220: Figure 9-9 Coe Sensor, Thermocouple, And Heater Connections

    Instruction Manual Repair Sensor Housing IM-106-880C, OI April 2017 Remove tubes (2, 3, and 4) from COe sensor assembly (5), eductor fittings (12 and 15), and sensor housing (7). Unfasten bayonet connector of COe thermocouple (8) and remove thermocouple. Loosen clamp screw of COe band heater (9) until heater rotates freely on sensor holder (11).
  • Page 221: Figure 9-10 Removal Of Coe Sensor Assembly

    Repair Sensor Instruction Manual Housing IM-106-880C, OI April 2017 Figure 9-10 Removal of COe Sensor Assembly Remove COe Sensor Assembly...
  • Page 222: Figure 9-11 Alignment Of Coe Sensor Assembly

    Instruction Manual Repair Sensor Housing IM-106-880C, OI April 2017 Figure 9-11. Using straightedge on the sensor holder flat, as shown, matchmark upper flange of sensor housing to show correct alignment of sensor holder. With one wrench holding eductor elbow (12, Figure 9-10), and one wrench on flats of sensor holder (11), unthread and remove COe sensor assembly (5).
  • Page 223: Remove Eductor

    Repair Sensor Instruction Manual Housing IM-106-880C, OI April 2017 Figure 9-12 Eductor Alignment Matchmarks 9.4.5 Remove Eductor The O cell and heater strut assembly (9, Figure 9-7) and the COe sensor assembly Figure 9-10) must be removed before you start this procedure. Use straightedge to matchmark alignment of eductor flat and elbow, as shown in Figure 9-12.
  • Page 224 Instruction Manual Repair Sensor Housing IM-106-880C, OI April 2017 Use heat resistant gloves when removing mating parts from the eductor. The mating parts are bonded with a thread sealing compound. The compound softens at 450 ° F (232 ° C). The heated parts can cause severe burns. Use a propane torch to heat the eductor (6) to 450 °F (232 °C), minimum.
  • Page 225: Figure 9-13 Removal Of Sample And Exhaust Tubes

    Repair Sensor Instruction Manual Housing IM-106-880C, OI April 2017 Remove Sample and Exhaust Tubes Use heat resistant gloves when removing the probe tube or exhaust tube. The tubes are bonded with a thread sealing compound. The compound softens at 450 ° F (232 °...
  • Page 226 Instruction Manual Repair Sensor Housing IM-106-880C, OI April 2017 Secure the sensor housing (1, Figure 9-13) in soft (plastic, wood, or brass) vice jaws. Use a propane torch to heat the sample tube (2) or exhaust tube (3) to 450 °F (232 °C), minimum. Apply the heat near the threaded end of the tube. While heating the tube, use a pipe wrench to apply removal torque to part being removed.
  • Page 227: Figure 9-14 O2 Cell, Heater, And Thermocouple, Exploded View

    Repair Sensor Instruction Manual Housing IM-106-880C, OI April 2017 Do not remove the O2 cell unless you are certain it needs to be replaced. Removal may damage the cell and platinum pad. Remove the O2 cell for cell replacement only Figure 9-14 O Cell, Heater, and Thermocouple, Exploded View Remove...
  • Page 228 Instruction Manual Repair Sensor Housing IM-106-880C, OI April 2017 Disassemble O Cell and Heater Strut Assembly Do not attempt to replace the O cell until all other possibilities for poor performance have been considered. If cell replacement is needed, order the O cell replacement kit (Refer to Section 10, Replacement...
  • Page 229: Disassemble Coe Sensor Assembly

    Repair Sensor Instruction Manual Housing IM-106-880C, OI April 2017 9.4.6 Disassemble COe Sensor Assembly Carefully remove screws (1, 9-15), lockwashers (2), and COe sensor (3) Figure from sensor holder (4). Remove and discard gasket (5). If damaged, use the following procedure to remove thermocouple adaptor (6) from sensor holder (4): Use a propane torch to heat the thermocouple adaptor to 450 °F (232 °C), minimum.
  • Page 230: Sensor Housing Assembly

    Instruction Manual Repair Sensor Housing IM-106-880C, OI April 2017 Always remove the stainless steel balls (approximately 200) from sensor holder before removing or installing pre-heater. Turning pre-heater in the sensor holder with the stainless steel balls in place will cause permanent damage to the pre-heater If pre-heater (7) is to be removed, clamp flats of sensor holder (4) in vise jaws with plug (8) pointing up.
  • Page 231: Figure 9-16 Coe Sensor And Pre-Heater Alignment

    Repair Sensor Instruction Manual Housing IM-106-880C, OI April 2017 Install and tighten plug (8). Use care when installing the combustibles (COe) sensor. The RTD elements are fragile and correct alignment in sensor holder is required for proper OCX operation. Lubricate and install COe sensor gasket (5). Apply anti-seize compound to threads of screws (1).
  • Page 232: Assemble O2 Sensor And Heater Strut Assembly

    Instruction Manual Repair Sensor Housing IM-106-880C, OI April 2017 9.4.8 Assemble O Sensor and Heater Strut Assembly 9-14. Assemble O cell (2), gasket (5), and heater tube (3). Make sure Figure the test gas passage holes line up with each other in all components. Apply a small amount of anti-seize compound to the screw threads and use screws (1) to secure assembly.
  • Page 233: Install Eductor

    Repair Sensor Instruction Manual Housing IM-106-880C, OI April 2017 9.4.10 Install Eductor If installed, the O cell and heater strut assembly (9, 9-7) must be removed from sensor Figure housing (8), before you install the eductor. Apply pipe thread sealant (Loctite #567) to the external pipe threads of eductor (6, Figure 9-17).
  • Page 234: Figure 9-18 Eductor Alignment Matchmarks

    Instruction Manual Repair Sensor Housing IM-106-880C, OI April 2017 Install and tighten eductor (6) in eductor holder (14). Install and tighten elbow (12) on eductor (6). Male port of elbow must point up and be in line with long axis of eductor. Apply anti-seize compound to the external pipe threads of eductor holder (14).
  • Page 235: Install Coe Sensor Assembly

    Repair Sensor Instruction Manual Housing IM-106-880C, OI April 2017 9.4.11 Install COe Sensor Assembly Figure 9-19 Band Heater Height Apply pipe thread sealant (Loctite #567) to the exposed pipe threads of eductor elbow (12, Figure 9-17). Do not apply sealant to the first turn of the pipe threads.
  • Page 236: Figure 9-20 Coe Sensor Holder Alignment

    Instruction Manual Repair Sensor Housing IM-106-880C, OI April 2017 Figure 9-20 COe Sensor Holder Alignment Install and fasten thermocouple (8, Figure 9-17). Position band heater as shown in Figure 9-19 Figure 9-20 and tighten band heater clamp screw. The heater insulator (9) end joint must line up with the band gap of the COe band heater (10).
  • Page 237: Figure 9-21 Coe Sensor, Thermocouple, And Heater Connections

    Repair Sensor Instruction Manual Housing IM-106-880C, OI April 2017 Figure 9-21 COe Sensor, Thermocouple, and Heater Connections Install COe Sensor Assembly...
  • Page 238: Figure 9-22 Installation Of O2 Cell And Heater Strut Assembly

    Instruction Manual Repair Sensor Housing IM-106-880C, OI April 2017 Figure 9-22 Installation of O Cell and Heater Strut Assembly 1. Screw 2. Locking Clip 3. Cover 4. O-ring 5. Marking Plate 6. Terminal Insulator 7. Reference Air Tube 8. Sensor Housing 9.
  • Page 239: Install Sample Block Heater Rods

    Repair Sensor Instruction Manual Housing IM-106-880C, OI April 2017 9.4.12 Install Sample Block Heater Rods Before installing sample block heater rods (13, Figure 9-22), evenly coat the heater rods with Watlube heater release agent. Install the heater rods (13), heater clamps (12), and screws (11). Reconnect the heater rod leads at the sensor housing terminal blocks, (Figure 9-23).
  • Page 240: Install O2 Cell And Heater Strut Assembly

    Instruction Manual Repair Sensor Housing IM-106-880C, OI April 2017 9.4.13 Install O Cell and Heater Strut Assembly Rub a small amount of anti-seize compound on both sides of new gasket (10, Figure 9- 22). Apply anti-seize compound to threads of O cell and heater strut assembly (9) and sensor housing (8).
  • Page 241: Sensor Housing Leak Test

    Repair Electronics Instruction Manual Housing IM-106-880C, OI April 2017 9.4.15 Sensor Housing Leak Test Install 1/4 NPT cap on dilution air inlet fitting. Install a 1/4 NPT cap on sample tube (2, Figure 9-13) or plug 1/4 NPT sample inlet port. Capped or plugged ports must be air tight.
  • Page 242: Electronics Housing Disassembly

    Instruction Manual Repair Electronics Housing IM-106-880C, OI April 2017 9.5.1 Electronics Housing Disassembly Remove Cover Figure 9-24. Loosen screw (1) and slide locking clip (2) away from cover (3). Retighten screw (1). With two hands or strap wrench, turn cover (3) counterclockwise to loosen. Unthread and remove cover.
  • Page 243: Remove Electronics Stack

    Repair Electronics Instruction Manual Housing IM-106-880C, OI April 2017 Figure 9-24 Removal/Installation of Electronics Housing Components 9.5.2 Remove Electronics Stack Unplug power cable, signal cable, and solenoid lead connectors from terminals of electronics stack (5, Figure 9-24). Remove two screws (13) and lockwashers (14). Remove electronics stack (5).
  • Page 244: Remove Solenoid Valves

    Instruction Manual Repair Electronics Housing IM-106-880C, OI April 2017 9.5.3 Remove Solenoid Valves Disconnect solenoid leads from mating terminal connector. Remove top nut of solenoid valve (15 or 16, Figure 9-24). Remove the solenoid coil assembly and washer. Unthread and remove solenoid valve base. 9.5.4 Remove EMI Filter and Terminal Block Disconnect EMI filter wiring...
  • Page 245: Electronics Housing Assembly

    Electronics Housing Instruction Manual Assembly IM-106-880C, OI April 2017 Electronics Housing Assembly 9.6.1 Install EMI Filter and Terminal Block Install replacement EMI filter (1, Figure 9-25) and/or terminal block (3) on electronic stack. Refer to wiring details in Figure 9-25. Connect EMI filter wiring and ground wire (2) at terminal block (3).
  • Page 246: Figure 9-26 Electronics Housing Cable Connections

    Instruction Manual Electronics Housing Assembly IM-106-880C, OI April 2017 Figure 9-26 Electronics Housing Cable Connections Install LOI Module and Board...
  • Page 247: Install Cover

    Electronics Housing Instruction Manual Assembly IM-106-880C, OI April 2017 Figure 9-27 Solenoid Power Terminals 9.6.5 Install Cover If removed, install cover gasket (4, Figure 9-24). Screw cover (3) onto electronics housing. Tighten cover firmly. Align locking clip (2) with gap between cover ribs. Loosen screw (1) and slide locking clip (2) fully into gap between cover ribs.
  • Page 248: Replace Tube Fittings

    Instruction Manual Replace Tube Fittings IM-106-880C, OI April 2017 Replace Tube Fittings The OCX transmitter housings have special tube fittings that, if clogged or damaged, must be replaced with the same type of fitting. The special tube fittings have alpha or numeric codes etched on the fitting.
  • Page 249: Remove Tube Fittings

    Replace Tube Instruction Manual Fittings IM-106-880C, OI April 2017 9.7.1 Remove Tube Fittings The OCX construction includes pipe thread sealant to seal fittings in all ports that pass through to an outer wall of the instrument housing base. Use the following instructions to loosen and remove tube fittings that are secured with pipe thread sealant.
  • Page 250: Install Tube Fittings

    Instruction Manual Replace Tube Fittings IM-106-880C, OI April 2017 Figure 9-28 Removal of Tube Fittings 9.7.2 Install Tube Fittings Verify that the replacement tube fitting is identical to the item removed. Special fittings are etched with code markings. Apply pipe thread sealant (Loctite #567) to the mating threads of the tube fitting. Do not apply sealant to the first turn of the external pipe threads.
  • Page 251 Replace Tube Instruction Manual Fittings IM-106-880C, OI April 2017 Install Tube Fittings...
  • Page 252: Section 10:Replacement Parts

    Instruction Manual Section 10: Replacement Parts IM-106-880C, OI April 2017 Section 10: Replacement Parts 10.1 Section contents Section contents ..........................page Sensor Housing ..........................page Electronics Housing ........................page O2 Cell and Heater Strut Assembly ....................page 10.2 Sensor Housing Refer to Figure 10-2 Figure 10-3...
  • Page 253: Table 10-1 Sensor Housing Components (Sheet 1)

    Section 10: Replacement Instruction Manual Parts IM-106-880C, OI April 2017 Table 10-1 Sensor housing components (Sheet 1) Index No. Part Number Description Cell and Heater Assembly, Standard Cell 5R10190G02 Cell and Heater Assembly, High Sulfur Cell 5R10190G03 6P00177H01 Heater Insulator, Mica 4851B46G03 Combustibles Sensor Replacement Kit 1A99786H01...
  • Page 254: Figure 10-3 Sensor Housing Components (Sheet 2 Of 2)

    Instruction Manual Section 10: Replacement Parts IM-106-880C, OI April 2017 Figure 10-3 Sensor Housing Components (Sheet 2 of 2) Sensor Housing...
  • Page 255 Section 10: Replacement Instruction Manual Parts IM-106-880C, OI April 2017 Table 10-2 Sensor Housing Components (Sheet 2) Index No. Part Number Description 1A99089H02 Cover Gasket (O-ring) 5R10246H06 Blowback Filter, 5 Micron, Stainless Steel 1A98448H02 O-ring 5R10247H01 Fitting R10183H02 Tube, Sample, 18 in. (457 mm) 316 Stainless steel 5R10183H06 Tube, Sample, 18 in.
  • Page 256: Electronics Housing

    Instruction Manual Section 10: Replacement Parts IM-106-880C, OI April 2017 10.3 Electronics Housing Figure 10-4 Electronics Housing Components Electronics Housing...
  • Page 257: Table 10-3 Electronics Housing Parts

    Section 10: Replacement Instruction Manual Parts IM-106-880C, OI April 2017 Table 10-3 Electronics housing parts Index No. Part Number Description 1A97902H01 Hose 1A97905H02 Solenoid Valve, 3-Way 1A97905H01 Solenoid Valve, Test Gas 6A00132G01 Electronics Stack, HART 6A00387G01 Electronics Stack, Fieldbus 1A97913H06 Fuse (F1 and F6), 10 Amp, 250 VAC 1A99766H01 Fuse (F3), 4 Amp, 250 VAC...
  • Page 258: Table 10-5 O2 Cell And Heater Strut Assembly

    Instruction Manual Section 10: Replacement Parts IM-106-880C, OI April 2017 10.4 Cell and Heater Strut Assembly Figure 10-6 O Cell and Heater Strut Assembly Table 10-5 O Cell and Heater Strut Assembly Index No. Part Number Description 4851B44G01 Contact and Thermocouple Assembly 5R10211G02 Heater Strut Assembly Heater Tube...
  • Page 259 Section 10: Replacement Instruction Manual Parts IM-106-880C, OI April 2017 O2 Cell and Heater Strut Assembly...
  • Page 260: Appendix A: Safety Data

    Instruction Manual Safety Data IM-106-880C, OI April 2017 Appendix A: Safety Data Appendix contents Safety Instructions ........................page - 233 Safety Data Sheet for Ceramic Fiber Products ................page-255 High Pressure Gas Cylinders ......................page- ATEX Clarification .......................... page- Safety Instructions IMPORTANT SAFETY INSTRUCTIONS FOR THE WIRING AND INSTALLATION OF THIS APPARATUS:...
  • Page 261 Instruction Manual Safety Data IM-106-880C, OI April 2017 Appendix contents...
  • Page 262 D0LEZITE zanzeni Bezpecnostn pokyny pro zapojeni a instalaci Nasledujid lbezpecnostni pokyny se specialne vztahu na vsechny cltmske staty Pokyny e ly byt pr isne dodr.zovan y, aby se zajistifo l neni n i zke:m napeti P okud pokyny ernic e nejsou nahrazeny mistnlmi...
  • Page 263: Safety Instructions

    Instruction Manual Safety Data IM-106-880C, OI April 2017 Safety Instructions...
  • Page 264 BELANGRIJK Veiligheidsvoorschriften voor de aansluiting en installatie van dit toestel. De hierna volgende veiligheidsvoorschriften zijn vooral bedoeld voor de EU lidstaten. Hier moet aan gehouden worden om de onderworpenheid aan de Laag Spannings Richtlijn (Low Voltage Directive) te verzekeren. Niet EU staten zouden deze richtlijnen moeten volgen tenzij zij reeds achterhaald zouden zijn door plaatselijke of nationale voorschriften.
  • Page 265 Instruction Manual Safety Data IM-106-880C, OI April 2017 BELANGRIJK Veiligheidsinstructies voor de bedrading en installatie van dit apparaat. Voor alle EU lidstaten zijn de volgende veiligheidsinstructies van toepassing. Om aan de geldende richtlijnen voor laagspanning te voldoen dient men zich hieraan strikt te houden. Ook niet EU lidstaten dienen zich aan het volgende te houden, tenzij de lokale wetgeving anders voorschrijft.
  • Page 266 WICHTIG Sicherheitshinweise für den Anschluß und die Installation dieser Geräte. Die folgenden Sicherheit- shinweise sind in allen Mitgliederstaaten der europäischen Gemeinschaft gültig. Sie müssen strickt eingehalten werden, um der Niederspannungsrichtlinie zu genügen. Nichtmitgliedsstaaten der europäischen Gemeinschaft sollten die national gültigen Normen und Richtlinien einhalten. 1.
  • Page 267 Instruction Manual Safety Data IM-106-880C, OI April 2017 Safety Instructions...
  • Page 268 OLULINE TEAVE J UHTMESTIKU JA SEADME PAIGALDAMISEGA SEOTUD OHUTUSJUHISED Alljärgnevad ohutusjuhised rakenduvad eriti kõigi Euroopa Liidu liikmesriikide suhtes. Antud juhiseid tuleb täpselt järgida, et kindlustada vastavus madalpinge direktiiviga. Euroopa Liitu mittekuuluvad riigid peavad samuti alljärgnevaid juhiseid järgima, va juhul, kui on olemas vastavad kohalikud riiklikud standardid.
  • Page 269 Instruction Manual Safety Data IM-106-880C, OI April 2017 TÄRKEÄÄ Turvallisuusohje, jota on noudatettava tämän laitteen asentamisessa ja kaapeloinnissa. Seuraavat ohjeet pätevät erityisesti EU:n jäsenvaltioissa. Niitä täytyy ehdottomasti noudattaa jotta täytettäisiin EU:n matalajännitedirektiivin (Low Voltage Directive) yhteensopivuus. Myös EU:hun kuulumattomien valtioiden tulee nou-dattaa tätä ohjetta, elleivät kansalliset standardit estä...
  • Page 270 IMPORTANT Consignes de sécurité concernant le raccordement et l'installation de cet appareil. Les consignes de sécurité ci-dessous s'adressent particulièrement à tous les états membres de la communauté européenne. Elles doivent être strictement appliquées afin de satisfaire aux directives concernant la basse tension. Les états non membres de la communauté européenne doivent également appliquer ces consignes sauf si elles sont en contradiction avec les standards locaux ou nationaux.
  • Page 271 Instruction Manual Safety Data IM-106-880C, OI April 2017 Safety Instructions...
  • Page 272 IMPORTANTE Norme di sicurezza per il cablaggio e l'installazione dello strumento. Le seguenti norme di sicurezza si applicano specificatamente agli stati membri dell'Unione Europea, la cui stretta osservanza è richiesta per garantire conformità alla Direttiva del Basso Voltaggio. Esse si applicano anche agli stati non appartenenti all'Unione Europea, salvo quanto disposto dalle vigenti normative locali o nazionali.
  • Page 273 Instruction Manual Safety Data IM-106-880C, OI April 2017 Safety Instructions...
  • Page 274 SVARIGI Drosibas noradijumi sis iekartas pievienosanai un uzstadisanai Turpmakie drosibas noradijumi attiecas visam ES dalibvalstim. Tie stingri jaievero, lai nodrosinatu atbilstibu Zemsprieguma direktivai. Turpmak noraditais jaievero valstis, kas nav ES dalibvalstis, vien sos noradijumus neaizstaj vietejie vai valsts standarti. 1. Visi pieejamie ieksejie arejie zemejuma punkti atbilstosi...
  • Page 275 Instruction Manual Safety Data IM-106-880C, OI April 2017 IMPORTANT Safety Instructions...
  • Page 276 VIKTIG Sikkerhetsinstruks for tilkobling og installasjon av dette utstyret. Følgende sikkerhetsinstruksjoner gjelder spesifikt alle EU medlemsland og land med i EØS- avtalen. Instruksjonene skal følges nøye slik at installasjonen blir i henhold til lavspenningsdirek- tivet. Den bør også følges i andre land, med mindre annet er spesifisert av lokale- eller nasjonale standarder.
  • Page 277 Instruction Manual Safety Data IM-106-880C, OI April 2017 Safety Instructions...
  • Page 278 IMPORTANTE Instruções de segurança para ligação e instalação deste aparelho. As seguintes instruções de segurança aplicam-se especificamente a todos os estados membros da UE. Devem ser observadas rigidamente por forma a garantir o cumprimento da Directiva sobre Baixa Tensão. Relativamente aos estados que não pertençam à UE, deverão cumprir igualmente a referida directiva, exceptuando os casos em que a legislação local a tiver substituído.
  • Page 279 Instruction Manual Safety Data IM-106-880C, OI April 2017 Safety Instructions...
  • Page 280 POMEMBNO Varnostna navodila za povezavo in vgradnjo naprave Naslednja varnostna navodila veljajo za vse drzave clanice Zaradi zagotovitve skladnosti z nizkonapetostno direktivo morate navodila strogo upostevati. V drzavah, niso clanice EU, je treba upostevati tudi naslednje smernice, razen jih ne zamenjujejo lokalni ali nacionalnimi...
  • Page 281 Instruction Manual Safety Data IM-106-880C, OI April 2017 IMPORTANTE Instrucciones de seguridad para el montaje y cableado de este aparato. Las siguientes instrucciones de seguridad, son de aplicacion especifica a todos los miembros de la UE y se adjuntaran para cumplir la normativa europea de baja tension. 1.
  • Page 282 VIKTIGT Säkerhetsföreskrifter för kablage och installation av denna apparat. Följande säkerhetsföreskrifter är tillämpliga för samtliga EU-medlemsländer. De skall följas i varje avseende för att överensstämma med Lågspännings direktivet. Icke EU medlemsländer skall också följa nedanstående punkter, såvida de inte övergrips av lokala eller nationella föreskrifter.
  • Page 283: Safety Data Sheet For Ceramic Fiber Products

    Instruction Manual Safety Data IM-106-880C, OI April 2017 Safety Data Sheet for Ceramic Fiber Products JULY 1, 1996 SECTION I. IDENTIFICATION PRODUCT NAME Ceramic Fiber Heaters, Molded Insulation Modules and Ceramic Fiber Radiant Heater Panels. CHEMICAL FAMILY Vitreous Aluminosilicate Fibers with Silicon Dioxide. CHEMICAL NAME N.A.
  • Page 284 (Respirable dust): 10 mg/cubic meter, Intended TLV (ACGIH 1984-85) **Composition is a trade secret. SECTION IV. FIRE AND EXPLOSION DATA FLASH POINT: None FLAMMABILITY LIMITS: N.A. EXTINGUISHING MEDIA Use extinguishing agent suitable for type of surrounding fire. UNUSUAL FIRE AND EXPLOSION HAZARDS / SPECIAL FIRE FIGHTING PROCEDURES N.A.
  • Page 285 Instruction Manual Safety Data IM-106-880C, OI April 2017 EPIDEMIOLOGY At this time there are no known published reports demonstrating negative health outcomes of workers exposed to refractory ceramic fiber (RCF). Epidemiologic investigations of RCF production workers are ongoing. 1. There is no evidence of any fibrotic lung disease (interstitial fibrosis) whatsoever on x-ray. There is no evidence of any lung disease among those employees exposed to RCF that had never smoked.
  • Page 286 Instruction Manual Safety Data IM-106-880C, OI April 2017 SECTION VI. REACTIVITY DATA STABILITY/CONDITIONS TO AVOID Stable under normal conditions of use. HAZARDOUS POLYMERIZATION/CONDITIONS TO AVOID N.A. INCOMPATIBILITY/MATERIALS TO AVOID Incompatible with hydrofluoric acid and concentrated alkali. HAZARDOUS DECOMPOSITION PRODUCTS N.A. SECTION VII.
  • Page 287 SECTION IX. SPECIAL PRECAUTIONS PRECAUTIONS TO BE TAKEN IN HANDLING AND STORING General cleanliness should be followed. The Toxicology data indicate that ceramic fiber should be handled with caution. The handling practices described in this MSDS must be strictly followed. In particular, when handling refractory ceramic fiber in any application, special caution should be taken to avoid unnecessary cutting and tearing of the material to minimize generation of airborne dust.
  • Page 288: High Pressure Gas Cylinders

    Instruction Manual Safety Data IM-106-880C, OI April 2017 If airborne fiber or cristobalite concentrations are not known, as minimum protection, use NIOSH/MSHA approved half face, air purifying respirator with HEPA filter cartridges. Insulation surface should be lightly sprayed with water before removal to suppress airborne dust. As water evaporates during removal, additional water should be sprayed on surfaces as needed.
  • Page 289: Atex Clarification

    Instruction Manual Safety Data IM-106-880C, OI April 2017 ATEX Clarification A.5.1 ATEX Compliant Gas Analysis Performed Within A Flameproof Enclosure Special conditions apply to using a flameproof enclosure analyzer under the scope of the “European Directive for Equipment used in Explosive Atmosphere” (Directive 94/9/EEC; ATEX). To stay compliant to the directive please consider the following clarification sheet released by the European ATEX Notified Body Group: 264 ATEX...
  • Page 290 Safety Data Instruction Manual IM-106-880C, OI April 2017 ATEX Compliant Gas Analysis Performed Within A Flameproof Enclosure...
  • Page 291: Appendix B: Spa With Hart Alarm

    Instruction Manual SPA with HART Alarm IM-106-880C, OI April 2017 Appendix B: SPA with HART Alarm Appendix contents Overview ............................page B-265 Description ............................page B-265 Installation ............................page B-266 Setup ..............................page B-266 Overview This section describes the SPA with HART Alarm option for the Hazardous Area OCX 8800. Description The Moore Industries SPA with HART Alarm, Figure...
  • Page 292: Installation

    SPA with HART Alarm Instruction Manual IM-106-880C, OI April 2017 Figure B-2 OCX 8800 and SPA Interface Connections Installation Refer to Figure B-2 for the typical interface connections for the Hazardous Area OCX 8800 and the SPA with HART alarm. Refer to the Moore Industries SPA user's manual for additional information concerning SPA installation, setup, and operation.
  • Page 293: Jumper And Switch Settings

    Figure B-3. If the SPA with HART was factory- configured by Emerson for operation with your Hazardous Area OCX 8800, jumper and switch setting adjustments are not required. However, you may use the following procedure to verify that the jumper and switch settings are correct. Adjust or verify jumper and switch settings as...
  • Page 294: Configuration/Calibration

    SPA with HART Alarm Instruction Manual IM-106-880C, OI April 2017 Verify that the Password Jumper is set to the OFF position. If the jumper is in the ON position, reposition the jumper. Figure B-3 Check the position of the Failsafe Dip Switches. Position the dip switches as shown in Check the position of the Source Current Dip Switches.
  • Page 295 Instruction Manual SPA with HART Alarm IM-106-880C, OI April 2017 Figure B-4 . Connect a calibrated ammeter (Fluke Model 87 or equivalent, accurate to ±0.025%) to the SPA analog output terminals. Observe polarity. Connect a 90 to 260 VAC or 22 to 300 VDC power source to the SPA power terminals. When connecting an AC power source, use the AC and ACC (AC Common) terminals.
  • Page 296: Figure B-5 Spa Front Panel

    SPA with HART Alarm Instruction Manual IM-106-880C, OI April 2017 Figure B-5 SPA Front Panel Figure B-6 shows the SPA menu, submenus, and parameter values that must be selected to configure the SPA for use with the Hazardous Area OCX 8800. Use the following instructions and selections shown to properly configure the SPA.
  • Page 297: Figure B-6 Spa Configuration Menu For Hazardous Area Ocx 8800 Communication

    Instruction Manual SPA with HART Alarm IM-106-880C, OI April 2017 Figure B-6 SPA Configuration Menu for Hazardous Area OCX 8800 Communication Configuration/Calibratio...
  • Page 298 SPA with HART Alarm Instruction Manual IM-106-880C, OI April 2017 Configuration/Calibratio...
  • Page 299: Appendix C: Returning Material

    1. To expedite the return process outside of the United States, contact the nearest Rosemount representative. Within the United States, call the Emerson Instrument and Valves Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assist you with any needed information or materials.
  • Page 300: Appendix D: Index

    Instruction Manual Index IM-106-880C, OI April 2017 Manual index...
  • Page 301 Index Instruction Manual April 2017 IM-106-880C, Appendix D: Index Manual index Symbols Configuration ................43 "Z" pattern .................. 59 Configure Simulation from AMS ........100 Cover and back pages ............... 1 AI Function Block ..............114 Alarm Detection ............121 D/A Trim Procedures - HART Application Information ..........
  • Page 302 Index Instruction Manual April 2017 IM-106-880C, Install Electronics Stack ............218 Install LOI Module ..............218 Install OCX with Integral Electronics ....... 183 Install Remote Electronics Housing PlantWeb Alerts ......... 188 ................95 Install Sensor Housing Power Up ............185 ..................
  • Page 303 Instruction Manual Index IM-106-880C, OI April 2017 System Operation ..............6 System Package ................. 2 Tables, figures and cross references ......... 43 Terminals Insulator ............... 213 Total Power Loss ..............167 Transducer Block Channel Status ........113 Transducer Block Enumerations ........
  • Page 304 Index Instruction Manual April 2017 IM-106-880C, Manual index...
  • Page 306 The Emerson logo is a trademark and service mark of Emerson Electric Co. 8200 Market Boulevard Chanhassen, MN 55317 Rosemount is a mark of one of the Emerson family of companies. All other marks are the Toll Free + 1 800 999 9307 property of their respective owners.

Table of Contents