10.4.

Log send and microSD save settings

Using the setup software you can set when log files are sent via FTP/email or SMS. The same
times apply for log write on microSD.
Note: When selecting variable acquisition and log send times, keep the following factors in mind:
1. Send time must be a whole multiple of acquisition time. For example, 15 minute
acquisition time and send in "Minutes" every 25 minutes are NOT possible. Easy MyAlarm2
software automatically rounds send time so that it is a multiple of variable acquisition
time. In this case the new value will be 30.
If send type is "Daily", the acquisition time will instead be rounded to be within an exact
day (corresponding to 1440 minutes). Easy MyAlarm2 will display an alert message with
the new variable acquisition time value.
2. Variable acquisition time refers to the internal clock; this means that the first acquisition is
not run after the set minutes starting from configuration send, but at the set time. For
example, if the user sets MYALARM2 to acquire variables every 10 minutes and sends the
configuration at 10:01, the device will run the first acquisition at 10:10.
10.5.

Log file settable fields

Log file settable field meanings are the following:
FIELD 1 - INDEX
It is always the sequential number of sampling run from the last time MyALARM2 was turned off.
If MyALARM2 is turned off and turned back on, the index value will be reset.
FIELD 2 - TYPE
It is always the type of log for future use, currently the message "LOG" appears.
FIELD 3 - TIMESTAMP
It is always the MyALARM2 date-time in dd/month/year hour:minutes:seconds format
FIELD 4 "DIGITAL FLAGS"
If set, the following digital inputs/outputs are included:
DIN1
DIN2