SERIES
SENECA s.r.l.
Via Austria, 26 – 35127 –PADOVA – ITALY
Tel. +39.049.8705355 – 8705359 Fax. +39.049.8706287
Web site:
www.seneca.it
Technical service:
supporto@seneca.it
Commercial information:
commerciale@seneca.it
MI00344-33-EN
(IT),
support@seneca.it
(IT),
Page 1
(Other)
sales@seneca.it
(Other)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MyALARM2 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Seneca MyALARM2 Series

  • Page 1 (Other) This document is property of SENECA srl. Duplication and reproduction of its are forbidden (though partial), if not authorized. Contents of present documentation refers to products and technologies described in it. Though we strive for reach perfection continually, all technical data contained in this document may be modified or added due to technical and commercial needs;...
  • Page 2 USER MANUAL - MyALARM2 SERIES Date Revision Changes 04/06/2013 MyALARM2 GPS chapter corrections GPS Signal chapter corrections GSM level scale changed System log file “syslog.csv” modified Changed GSM signal log from /7 to value in SMS command added: Get GSM...
  • Page 3 USER MANUAL - MyALARM2 SERIES 28/10/2020 SMS commands related to temperature control fixed 29/06/2023 Added new MyALARM2 hardware support with 4G modem 18/09/2023 Removed references to Easy Setup Deleted chapter 25.2. “…Log of gate opening requests with Syslog system log…”...
  • Page 4: Table Of Contents

    USER MANUAL - MyALARM2 SERIES Contents SENECA MYALARM2 ....................... 10 1. PRELIMINARY INFORMATION ................. 10 2. FIRST INSTALLATION ....................12 3. FEATURES ......................... 12 4. BASIC NOTIONS ......................13 5. MYALARM2 HARDWARE VERSIONS ..............15 5.1. AVAILABLE MYALARM2 MODELS ............... 15 6.
  • Page 5 USER MANUAL - MyALARM2 SERIES 10.2. LOG FILE ......................24 10.3. LOGGER SETUP ....................25 10.4. LOG SEND AND MICROSD SAVE SETTINGS ........... 26 10.5. LOG FILE SETTABLE FIELDS ................26 10.6. LOG SMS ......................31 10.7. TAG CUSTOMISATION IN DATALOGGER ............31 10.8.
  • Page 6 USER MANUAL - MyALARM2 SERIES 13.3. "ADMINISTRATOR" CONTACT ................36 13.4. DELIVERY GROUPS ................... 37 SUPPORTED COMMANDS ..................38 14.1. SMS COMMANDS ....................38 14.1.1. SET THE TELEPHONE SMS CHARACTER ALPHABET ........ 38 14.1.2. LIST OF SUPPORTED SMS COMMANDS ............38 14.2.
  • Page 7 USER MANUAL - MyALARM2 SERIES 17.2. ALARM ON HIGH AND MAXIMUM ..............53 17.3. ALARM ON LOW AND MINIMUM ............... 54 17.4. ALARM FILTER ....................55 17.5. ALARM INHIBITION TIME ................... 55 ALARMS ON DIGITAL INPUTS ................56 18.1. DIGITAL INPUT FILTER ..................57 18.2.
  • Page 8 USER MANUAL - MyALARM2 SERIES AUTOMATIC GATE CONTROL ................65 25.1. EXTENDED ADDRESS BOOK FOR RING COMMAND ........65 ALARM ON SOLAR PANEL MALFUNCTION ............65 PUMP AND POOL LIGHT ON CONTROL .............. 66 ACTIONS ON ALARM EVENT ................67 “MYALARM2 SECURITY AUDIO”...
  • Page 9 USER MANUAL - MyALARM2 SERIES 30.9. CURRENT POSITION ON SMS AND DIRECT DISPLAY ON GOOGLE MAPS™ 30.10. ADDITIONAL SMS COMMANDS FOR THE MYALARM2 GPS MODEL ..79 30.11. ADDITIONAL ACTIONS FOR THE MYALARM GPS MODEL ......80 FIRMWARE UPDATE....................80 UPDATE VIA USB (USING EASY MYALARM2 SOFTWARE) .......
  • Page 10: Seneca Myalarm2

    The use of MYALARM2 in data roaming (for example, abroad with an Italian SIM card) may generate unexpected costs. Contact your telephone provider for further information. IN NO CASE MAY SENECA OR ITS SUPPLIERS BE HELD LIABLE FOR ANY INCOMING DATA OR PROFIT LOSSES DUE TO INDIRECT, CONSEQUENTIAL OR INCIDENTAL CAUSES (INCLUDING NEGLIGENCE) CONNECTED WITH THE USE OR INABILITY TO USE MYALARM2, EVEN IF SENECA WAS INFORMED OF THE POTENTIAL OF THESE DAMAGES.
  • Page 11 USER MANUAL - MyALARM2 SERIES sent. Typically, a 2-Kbyte data log takes about 10-15 seconds to be sent (via a 2G network) in addition to the time necessary to establish the connection (from 5 to 30 seconds) and the time due to any server login attempts.
  • Page 12: First Installation

    USER MANUAL - MyALARM2 SERIES 2. FIRST INSTALLATION See the "MyALARM2 Quick Guide" and "MyALARM2 installation guide" before opening the package. 3. FEATURES MYALARM2 is a GSM/ GPRS or 4G LTE device available to control industrial and domestic domotic and security applications.
  • Page 13: Basic Notions

    USER MANUAL - MyALARM2 SERIES 4. BASIC NOTIONS MYALARM2 is equipped with 4 counters and 4 totalizers. Up to a maximum of 30 Hz signals can be acquired, 4 digital inputs, 2 analog inputs and 2 relay digital outputs. MyALARM2 I/O can be logged and the log sent as a file in csv format (comma separated values) via ftp or email.
  • Page 14 USER MANUAL - MyALARM2 SERIES MyAlarm2 recognises and runs a series of commands also via SMS. A set of "FAST" commands can also be set. These commands can be linked to the text in SMS 0, 1 up to 15.
  • Page 15: Myalarm2 Hardware Versions

    USER MANUAL - MyALARM2 SERIES 5. MyALARM2 Hardware Versions You can recognize the version of MyALARM2 you are using from the label on the back of the device. 5.1. Available MyALARM2 models The MyALARM2 model can be found on the label on the back of MyALARM2:...
  • Page 16: Display

    USER MANUAL - MyALARM2 SERIES 6. Display 6.1. Main page The main MyALARM2 display page provides the following information: A = GSM/LTE signal level B = Output 1 status C = Output 2 status D = Digital input 1 status...
  • Page 17: Changing The Displayed Page

    USER MANUAL - MyALARM2 SERIES 6.2. Changing the displayed page To change the displayed page, press the SCR key. The key is illustrated in the figure: 6.3. The MAIN menu Press and hold down the left PWR key for several seconds to open the main MyALARM2 menu.
  • Page 18: Page Context Menus

    USER MANUAL - MyALARM2 SERIES 6.4. PAGE CONTEXT menus Some pages let you view other information via a context menu. The context menu can be opened by opening the required page and pressing and holding down the right SCR key for several seconds.
  • Page 19: Supported Sim Cards

    USER MANUAL - MyALARM2 SERIES 7. SUPPORTED SIM CARDS MyALARM2 supports the following types of SIM CARDs: Top-up voice SIM CARD Subscription voice SIM CARD Data transmission only SIM CARD Operations can be run "at zero cost" for voice type SIM CARDs by ringing so that MyALARM2 will run set operations.
  • Page 20: Gsm/Lte Signal

    USER MANUAL - MyALARM2 SERIES 8. GSM/LTE SIGNAL Through the display or through the Easy MyALARM2 software it is possible to know the GSM/LTE signal level of MYALARM2 (in the configuration test section). To view the GSM/LTE signal level, the SIM CARD supplied by the telephone service provider must be inserted (signal may change radically based on the selected provider).
  • Page 21 SIGNAL LEVEL 5 = VERY GOOD SIGNAL SIGNAL LEVEL 6 = EXCELLENT SIGNAL SIGNAL LEVEL 7 = EXCELLENT SIGNAL To increase the GSM/LTE signal level, Seneca provides various GSM/LTE antenna models for MYALARM2 to reach the minimum signal level in most situations. Visit www.seneca.it...
  • Page 22: Data Connection

    USER MANUAL - MyALARM2 SERIES Please remember that mobile phone service providers also consider the entire communication that permits file transmission (and thus data transmission overhead, the number of connection attempts, etc.) and not just the dimensions as data traffic in each GPRS transaction.
  • Page 23: Datalogger

    USER MANUAL - MyALARM2 SERIES 10. DATALOGGER The Datalogger allows data to be acquired from the MYALARM2 built-in IO and sends the following via FTP or email or saves it on microSD card: .acquisition index -Date/time -the value of totalizers with the delta over the previous value.
  • Page 24: Log File

    USER MANUAL - MyALARM2 SERIES in these cases, the time remains unreliable until the next synchronisation. 10.2. Log file The file saved on microSD, sent via FTP or email, is in CSV format, for example: INDEX;TYPE;TIMESTAMP;TOT1;DELTA;TOT2;DELTA;TOT3;DELTA;TOT4;DELTA 1;LOG;11/07/2012 11:17:00;+881;+10;+881;+10;+881;+10;+881;+10 once opened by Microsoft EXCEL ™ or OpenOffice Calc ™ type software, the following is obtained (setting “;”...
  • Page 25: Logger Setup

    USER MANUAL - MyALARM2 SERIES -Keep in mind that the software/site used to receive emails could consider MyALARM2 emails as SPAM. 10.3. Logger setup The following can be set for the logger function: • Variable acquisition time in logger. •...
  • Page 26: Log Send And Microsd Save Settings

    USER MANUAL - MyALARM2 SERIES 10.4. Log send and microSD save settings Using the setup software you can set when log files are sent via FTP/email or SMS. The same times apply for log write on microSD. Note: When selecting variable acquisition and log send times, keep the following factors in mind: 1.
  • Page 27 USER MANUAL - MyALARM2 SERIES DIN3 DIN4 DOUT1 DOUT2 VBAT POWER Where the meanings are the following DINx is the xth digital input value. If OFF = input open, if ON = input closed DOUTx is the xth output value. If OFF = output open, if ON = output closed VBAT indicates backup battery operations.
  • Page 28 USER MANUAL - MyALARM2 SERIES MAX ANALOG1 = maximum analog 1 value in the log variable acquisition period (scaled if necessary) FIELD 7 - "ANALOG INPUT 2" If set, it displays analog input 2 status: ANALOG2 = real-time scaled value of analog input 2...
  • Page 29 USER MANUAL - MyALARM2 SERIES FIELD 11- “HOUR 2” HOUR2 If set, it is the time in seconds tied to input 2 hour counter FIELD 12 - "TOTALIZER/COUNTER 3" If set, it displays the totalizer and/or counter 3 status and delta, scaled if necessary:...
  • Page 30 USER MANUAL - MyALARM2 SERIES If -115 dBm the signal is null.
  • Page 31: Log Sms

    USER MANUAL - MyALARM2 SERIES 10.6. Log SMS Since only a limited number of characters can be sent via SMS, the SMS only includes the last row of the log file and is, for example: 11/07/2012 11:17:00 +881 +10 +881 +10 +881 +10 +881 +10 Where the order of the values is given by the corresponding log file.
  • Page 32: Log Save On Microsd Card

    USER MANUAL - MyALARM2 SERIES 10.8. Log save on microSD card Logs can be saved on a microSD card formatted with the FAT16 or FAT32 filesystem (microSD cards <= 32 Gbytes are usually already formatted this way). Log files are saved in the microSD folder/log in .csv text format.
  • Page 33: Log File Gprs (2G) Send Times

    The lowest performance is obtained with MyAlarm models with 2G modem. Send time can be estimated based on the various tests conducted in Seneca laboratories. A 1440- row log file (about 200Kbytes) takes an average of about 14 minutes to send in 2G.
  • Page 34: Configuration Test For Sms Send/Receive

    USER MANUAL - MyALARM2 SERIES 11.1. Configuration test for SMS send/receive A command is available to be sent via SMS to test SMS send and receive The SMS command is sent by a mobile phone saved in the address book as "administrator". It can...
  • Page 35: Sending The "Syslog.csv" File

    USER MANUAL - MyALARM2 SERIES 12.1. SENDING THE “SYSLOG.CSV” FILE The Syslog.csv file can be sent via FTP or EMAIL (to the first administrator) using the following SMS commands: email syslog It sends the text file in an email attachment to the first administrator...
  • Page 36: User" Contact

    USER MANUAL - MyALARM2 SERIES 13.1. "User" contact A "User" type contact is only enabled to receive alarms. 13.2. "Operator" contact An "Operator" type contact is enabled to receive alarms and send SMS commands. 13.3. "Administrator" contact An “Administrator” type contact is enabled to receive all alarms (since automatically included in all groups), send commands and receive administrator SMS messages.
  • Page 37: Delivery Groups

    USER MANUAL - MyALARM2 SERIES 13.4. Delivery groups A group of contacts can be selected to receive alarm SMS or EMAILS for each alarm. MYALARM2 can manage up to 30 different delivery groups. Each group can contain up to 20 contacts (SMS or EMAIL).
  • Page 38: Supported Commands

    USER MANUAL - MyALARM2 SERIES SUPPORTED COMMANDS 14.1. SMS COMMANDS 14.1.1. SET THE TELEPHONE SMS CHARACTER ALPHABET Some Smartphones send SMS with UNICODE characters instead of using the GSM alphabet. MyALARM2 runs SMS commands with both GSM or UNICODE alphabet.
  • Page 39 USER MANUAL - MyALARM2 SERIES SET CNTn mmmmm… Load the mmmmm... scaled value in the nth counter RESET WRKn Resets the n-th work time SMS COMMANDS FOR ANALOG INPUTS GET AIN Returns the analog input values in technical units GET AINn...
  • Page 40 USER MANUAL - MyALARM2 SERIES SMS COMMANDS FOR DIGITAL OUTPUTS GET DOUT Returns the value of the digital output GET DOUTn Returns the value of the nth digital output SET DOUTn.OPEN Opens the nth digital output SET DOUTn.CLOSE Closes the nth digital output...
  • Page 41 USER MANUAL - MyALARM2 SERIES SMS COMMANDS FOR ADDRESS BOOKS SET PHONE +nnnnnnn Add number +nnnnnn to address book as administrator RESET PHONE +nnnnnnn Remove number +nnnnnn from the address book SET EMAIL nnn@nnn.nnn Add email nnn@nnn.nnn to address book as...
  • Page 42 USER MANUAL - MyALARM2 SERIES SMS COMMANDS PER DATE/TIME GET RTC Returns the current date / time value SET RTC.OFFSET +SS Adds SS seconds to the current time value SET RTC.OFFSET -SS Deducts SS seconds from the current time value SET RTC.DATE GG/MM/AAAA HH:MM:SS...
  • Page 43 USER MANUAL - MyALARM2 SERIES path the FTP server folder where files are sent name_ip IP address or FTP server name port is the ftp server port user FTP server login user name password FTP server login password for example: SET /prova/ 192.168.180.33 21 pippo pluto...
  • Page 44: Fast" Commands

    USER MANUAL - MyALARM2 SERIES EMAIL DIN1 sends an email with the value of the digital input 1 EMAIL DIN2 sends an email with the value of the digital input 2 EMAIL DIN3 sends an email with the value of the...
  • Page 45 USER MANUAL - MyALARM2 SERIES For these commands, the SMS sender number must be enabled (thus it must come from an operator or administrator). An SMS text can also be tied to a fast command, for example: "OUTPUT ON" It can be tied to the output 2 close command, etc.
  • Page 46 USER MANUAL - MyALARM2 SERIES STOP LOGGER (TIMER 1) Stops the datalogger START TIMER Starts timer 2 or 3...10 STOP TIMER Stops timer 2 or 3...10 ENABLE ALARM ON POWER OUTAGE Enables the power outage alarm with set parameters DISABLE ALARM ON POWER OUTAGE...
  • Page 47: Zero Cost" Commands (Ring)

    USER MANUAL - MyALARM2 SERIES ENABLE ALARM ON STRING STREAM CONTROL Enables alarm on string stream control DISABLE ALARM ON STRING STREAM CONTROL Disables alarm on string stream control TEMPERATURE SENSOR TEMPERATURE SEND Sends the read temperature value SEND STATUS MESSAGE...
  • Page 48: Command Passwords

    USER MANUAL - MyALARM2 SERIES -Not all mobile service providers let you receive rings from data SIM. Check whether the servicer is offered by your provider. 14.4. COMMAND PASSWORDS MyALARM2 lets you run SMS commands even if the command is not sent by a number in the address book.
  • Page 49: Timers

    USER MANUAL - MyALARM2 SERIES TIMERS Up to 10 timers are available to run actions: There are 2 types of timers available: periodic timers and calendar timers. 15.1. PERIODIC TIMERS Each periodic timer can run up to 3 actions. The timer start and end date and timer trip frequency can be selected.
  • Page 50: Sunrise And Sunset Calculations

    USER MANUAL - MyALARM2 SERIES WEDNESDAY - CLOSE OUTPUT 1 AT 14:00:00, OPEN AT 18:00:00 THURSDAY - CLOSE OUTPUT 1 AT 08:00:00, OPEN AT 12:30:00 THURSDAY - CLOSE OUTPUT 1 AT 14:00:00, OPEN AT 18:00:00 FRIDAY - CLOSE OUTPUT 1 AT 08:00:00, OPEN AT 12:00:00 15.3.
  • Page 51: Email Use

    USER MANUAL - MyALARM2 SERIES 16. EMAIL USE 16.1. Basic information on sending emails An email is sent via connections with an SMTP type server (Simple Mail Transfer Protocol). This server is assigned to delivering the email to the required addresses.
  • Page 52: Main Smtp Server Settings With Ssl Protected Connection

    The user name typically coincides with the first part of the email address (for example: info), or with the entire email address (for example info@seneca.it). ATTENTION! • Seneca recommends you ALWAYS SEND EMAILS via SMTP server with SSL protected connection. 16.4. Main SMTP server settings with SSL protected...
  • Page 53: Alarms On Analog Inputs

    Voltage or current can be set for each of the 2 analog inputs in the “Analog Input Setup” section. Input acquisition time is 50ms. Seneca recommends you ALWAYS enable analog input filter ("read filter on" item) to obtain the most stable reading not influenced by external disturbances.
  • Page 54: Alarm On Low And Minimum

    USER MANUAL - MyALARM2 SERIES ALARM ON MAXIMUM ALARM ON MAXIMUM ALARM ON MAXIMUM RESET ALARM ON MAXIMUM RESET Alarm on high works in the same way. 17.3. Alarm on Low and Minimum “Low” and “Minimum” alarms let you enable two different maximum alarms. A hysteresis can also be set (shown as “ist”...
  • Page 55: Alarm Filter

    USER MANUAL - MyALARM2 SERIES 17.4. Alarm filter A filter can be selected on the analog input, defined in seconds. The resulting effect is a filter on both the alarm and reset, as illustrated below: ALARM ON MAXIMUM T alarm...
  • Page 56: Alarms On Digital Inputs

    USER MANUAL - MyALARM2 SERIES 18. ALARMS ON DIGITAL INPUTS Each of the 4 digital inputs can be set in the "Digital Input Settings" section. 5 types of alarms are available: Alarm on status change from open to closed The alarm is active when status changes from open to closed...
  • Page 57: Digital Input Filter

    USER MANUAL - MyALARM2 SERIES 18.1. Digital input filter A digital alarm filter can be enabled. This filter is expressed in seconds (with tenth of a second resolution). The filter lets you eliminate effects due to input rebounds. Setting a filter T time, the...
  • Page 58: Totalizer/Counter Alarms

    USER MANUAL - MyALARM2 SERIES 19. TOTALIZER/COUNTER ALARMS A counter/totalizer alarm value can be set in the "Totalizer/counter settings" section. Both totalizers and counters are included because counters can be used as partial values. 19.1. Alarm inhibition time An inhibition time on the next alarm can be set. The alarm is ignored during inhibition time. This time is reset after each alarm.
  • Page 59: Alarm On Totalizer Increase

    USER MANUAL - MyALARM2 SERIES 21. ALARM ON TOTALIZER INCREASE Up to 4 alarms can be set in the "Alarm on input increase" section (1 per input) for high or low totalizer increase. These alarms monitor flows (gas, liquid, etc.) or warn in the event of energy generator malfunctions (photovoltaic, panels, wind generators, etc.).
  • Page 60: Alarm On Plant Loss

    USER MANUAL - MyALARM2 SERIES 22. ALARM ON PLANT LOSS The alarm on plant loss generates an alarm in the event of loss (for example plumbing leaks) in a plant. The basic concept is that in normal operations, in observation time T, plant flow must be less than Q for at least the count time t.
  • Page 61 USER MANUAL - MyALARM2 SERIES MYALARM2 monitors number 4 independent hour meter contacts. This function generates an alarm if the number of hours set in which the digital input is in a certain logic status is exceeded. The typical application is an automatic pump, boiler, utility, oven, etc.
  • Page 62: Boiler Control

    USER MANUAL - MyALARM2 SERIES 24. BOILER CONTROL 24.1. Operating mode The boiler control application monitors the boiler via SMS commands. The boiler control can be used in three ways: Temperature control mode Program mode Manual mode A comfort temperature (T comfort) and energy savings temperature (T economy) can be set for the first two modes.
  • Page 63: Temperature Control Mode

    USER MANUAL - MyALARM2 SERIES 24.2. Temperature control mode In the temperature control mode, MyALARM2 attempts to maintain the set TEconomy or TComfort temperature. An SMS command can be sent to switch from Comfort to economy temperature. For the system to maintain the comfort temperature: SET HVAC.MODE HC...
  • Page 64: Manual Mode

    USER MANUAL - MyALARM2 SERIES 24.4. Manual mode In manual mode, MyALARM2 turns the boiler on/off according to the received SMS commands, no temperature is regulated, this must be managed manually. To set the manual mode, send the SMS: SET HVAC.MODE OFF The SMS command: SET DOUT1.OPEN...
  • Page 65: Automatic Gate Control

    USER MANUAL - MyALARM2 SERIES 25. AUTOMATIC GATE CONTROL The automatic gate control opens the gate by sending a simple ring from the address book or extended address book. 25.1. Extended address book for ring command MyALARM2 allows you to manage, in addition to the classic address book, an extended address book which resides on the SIM card memory or on an SD card (depending on the MyALARM2 model).
  • Page 66: Pump And Pool Light On Control

    TEMPERATURE SENSOR WITH CURRENT OUTPUT CONNECTED TO ANALOG INPUT 1 PUMP ON/OFF CONNECTED TO RELAY OUTPUT 1 LIGHTS ON/OFF CONNECTED TO RELAY OUTPUT 2 Contact Seneca srl to purchase the temperature sensor. ATTENTION! The pool pump control application uses the datalogger to read the previous day's average water...
  • Page 67: Actions On Alarm Event

    USER MANUAL - MyALARM2 SERIES 28. ACTIONS ON ALARM EVENT In the event of an alarm, MyALARM2, in addition to sending the alarm via SMS/EMAIL, can also perform up to 2 actions. The list of actions that MyALARM2 can perform is listed here (for an exhaustive list, refer to...
  • Page 68 USER MANUAL - MyALARM2 SERIES DISABLE ALARM ON POWER OUTAGE Disables the power outage alarm ENABLE ALARM ON DIGITAL INPUT Enables alarm on digital input 1, 2, 3 or 4 DISABLE ALARM ON DIGITAL INPUT Disables alarm on digital input 1, 2, 3 or 4...
  • Page 69 USER MANUAL - MyALARM2 SERIES SEND STATUS MESSAGE Sends the machine status command with configurable content (see Easy MyAlarm2 software) SEND COUNTER VALUES Sends counter values SEND TOTALIZER VALUES Sends totalizer values ENABLE ALARM ON ALL DIGITAL INPUTS Enables alarm on all 4 digital inputs...
  • Page 70: Myalarm2 Security Audio" Model

    • DO NOT hang up while MyALARM2 is making a call since the SIM answering machine may answer. In this case, MyALARM2 will consider the call answer valid. • Seneca recommends turning off the answering machine on phone numbers authorised to receive audio calls.
  • Page 71: Running Fast Commands From The Phone Keypad

    USER MANUAL - MyALARM2 SERIES MyALARM2 will call in sequence all the numbers in the address book enabled to receive the alarm in progress; the call cycle will be interrupted when one of the recipients answers the call and confirms receipt of the audio message by pressing the “*”...
  • Page 72: Myalarm2 Gps" Model

    In addition to these alarm, the current MyALARM2 position can be send on Google maps™ both via SMS and via E-MAIL. For indoor applications or with low signal, an external GPS antenna can be connects. Visit www.seneca.it, MyALARM2 GPS section for further information.
  • Page 73: Myalarm2 Gps Context Menu

    USER MANUAL - MyALARM2 SERIES 30.2. MyALARM2 GPS context menu The MyALARM2 GPS model comes with a context menu that permits some operations to be directly run using the two MyALARM2 GPS keys. To open the context menu, press the right SCR key to open the GPS menu. At this point, hold down the right SCR key for several seconds until the menu appears: You can now select an option from the menu using the SCR key and confirming with the left PWR key.
  • Page 74: Alarm On Maximum Speed

    USER MANUAL - MyALARM2 SERIES 30.4. Alarm on maximum speed MyALARM2 GPS lets you set a speed limit to generate an alarm. This ensures that your vehicle never exceeds a safety speed. To generate the maximum speed alarm, the set limit (in Km/h) must be exceeded for at least 2 GPS acquisitions.
  • Page 75: Alarm On Virtual Origin: Connection Example

    USER MANUAL - MyALARM2 SERIES An alarm is generate if the vehicle is moved and exits the virtual origin: When the alarm is turned off, the vehicle can be moved without generating an alarm and turned back on at the next dock or park.
  • Page 76: Tracker" Function

    USER MANUAL - MyALARM2 SERIES 30.6. "Tracker" function A function can be set to track the GPS position at settable times (default: 2 minutes) via SMS or EMAIL. The "tracker" function can be set to automatically turn on in the event of alarm or on SMS command.
  • Page 77: Sending An Alarm Via Audio Message

    • DO NOT hang up while MyALARM2 GPS is making a call since the SIM answering machine may answer. In this case, MyALARM2 GPS will consider the call answer valid. • Seneca recommends turning off the answering machine on phone numbers authorised to receive audio calls.
  • Page 78 USER MANUAL - MyALARM2 SERIES...
  • Page 79: Additional Sms Commands For The Myalarm2 Gps Model

    USER MANUAL - MyALARM2 SERIES 30.10. Additional SMS commands for the MyALARM2 GPS model SMS COMMANDS SPECIFIC TO THE MyALARM2 GPS MODEL GET GPS Returns the current position link to Google maps™ via SMS. EMAIL GPS Returns an email to administrators with the current position link to Google maps™.
  • Page 80: Additional Actions For The Myalarm Gps Model

    USER MANUAL - MyALARM2 SERIES 30.11. Additional actions for the MyALARM GPS model Compared to other MyALARM2 models, the GPS version adds the following actions that can be used for events and as fast commands. ACTION COMMENT USE COORDINATES AS ORIGIN Uses current GPS coordinates as the centre of the virtual origin and to calculate sunrise/sunset.
  • Page 81: Update Via Usb (Using Easy Myalarm2 Software)

    Proceed as follows to update MYALARM2 firmware: 1. Copy the filed called “MYALM2.BIN” containing firmware to a microSD card; the file is included in the free Easy MyALARM2 software (available for download at www.seneca.it) and is automatically copied during installation to folder “\Documents\Seneca\Easy MyALARM2\update”.
  • Page 82 USER MANUAL - MyALARM2 SERIES -The firmware code (4 numbers) followed by the build (2 numbers) appears on the screen when the device is turned on. -Connecting MYALARM2 to setup software, the firmware version (at the bottom left: “Connected to MYALARM2 FW 2XXX”) has changed.
  • Page 83: Troubleshooting

    -Try using another mobile service provider's SIM -Move the MyALARM2 installation -Use an optional external antenna: for further information, contact Seneca or visit the MyALARM2 section at www.seneca.it. Residual credit is not sent for the SIM -Check the method used to receive residual credit from the mobile service provider (ring or SMS, SMS request text).
  • Page 84 USER MANUAL - MyALARM2 SERIES -The SIM is not top-up but subscription MYALARM2 worked correctly for a few days/months -No SIM credit. Top-up the SIM card. but stopped sending SMS and logs. -The SIM card expired because credit was never topped up for more than one year.

This manual is also suitable for:

Myalarm2my2g-0-0-m-gMyalarm2 my2g-r-0-m-gMyalarm2 my2gl-0-0-m-bMyalarm2 my2gl-r-0-m-gMyalarm2 my2s-0-0-m-gMyalarm2 my2s-0-0-m-b ... Show all

Table of Contents