Line Modules Booksize
3.8 Smart Line Modules (5 kW und 10 kW) with external air cooling
3.8.3.6
X24 24 V terminal adapter
Table 3-63
Terminal block X24
Terminal
+
M
The 24 V terminal adapter is supplied as standard
Max. connectable cross-section: 6 mm
Type: Screw terminal 5 (see Connection Methods)
3.8.3.7
Meaning of the LEDs on the Smart Line Module
Table 3-64
5 kW and 10 kW Smart Line Modules – description of the LEDs
LED
Color
READY
–
Green
Yellow
Red
DC LINK
–
Yellow
Red
Hazardous DC link voltages may be present at any time regardless of the state of the "DC
link" LED.
The warning information on the components must be carefully observed!
302
Designation
24 V power supply
Ground
2
State
OFF
Electronics power supply is missing or outside
permissible tolerance range.
Continuous
Component is ready to operate.
Continuous
Pre-charging not yet complete.
bypass relay dropped out
EP terminals not supplied with 24 V DC.
Continuous
Overtemperature
Overcurrent switch-off
OFF
Electronics power supply is missing or outside
permissible tolerance range.
Continuous
DC link voltage within permissible tolerance range.
Continuous
DC link voltage outside permissible tolerance range.
Line supply fault.
DANGER
Technical specifications
24 V DC supply voltage
Electronic ground
Description, cause
–
–
–
Diagnostics fault (via
output terminals) and
acknowledge it (via input
terminal)
–
–
Check the supply voltage.