Meaning Of The Leds On The Braking Module - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Note
Applying a high signal to terminal X21.1 inhibits the Braking Module. On a falling edge,
pending error signals are acknowledged.
The pre-warning for I*t monitoring is output as a high level on reaching 80% of the maximum
braking resistor ON time.
Only braking resistors approved by Siemens for this component are identified automatically.
6.1.3.5

Meaning of the LEDs on the Braking Module

Table 6-3
Braking Module Booksize – description of the LEDs
LED
Color
-
off
Green
Continuous
Red
Continuous
READY
-
off
DC LINK
Green
Flashing
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
Status
Electronics power supply is missing or outside permissible
tolerance range.
Component deactivated via terminal.
Component is ready to operate.
Overtemperature
Overcurrent switch-off
I
t monitoring activated.
2
Ground fault/short-circuit.
Note:
In the event of an overtemperature, the error cannot be
acknowledged until a cooling time has elapsed.
Electronics power supply is missing or outside permissible
tolerance range.
Component not active.
Component active (DC link discharge via braking resistor in
progress).
Description, cause
Booksize DC Link Components
6.1 Braking Modules
Remedy
Diagnose fault (via
output terminals) and
acknowledge it (via
input terminal)
407