Operating a 100 kW Basic Line Module from an insulated supply (IT system)
When the 100 kW Basic Line Module is operated from an insulated supply (IT system), the
connection bracket for the interference-suppression capacitor must be removed. The
connection bracket for the interference-suppression capacitor is located on the lower side
of the component.
CAUTION
If the connection bracket for the interference-suppression capacitor is not removed, an error
message is output via the insulation monitor in the system.
Remove the connection bracket for the
interference-suppression capacitor with
a Tx25 screwdriver
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
Remove the connection bracket
3.4 Basic Line Modules with internal air cooling
Connection bracket for the
interference-suppression capacitor