Siemens SINAMICS S120 Equipment Manual page 312

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules Booksize
3.8 Smart Line Modules (5 kW und 10 kW) with external air cooling
Internal air cooling
Rated power
Circuit-breaker type designation
(status 07/2007 and later)
Rated current
Short-circuit current rating SCCR at 400 V
Circuit-breaker type designation
UL489/CSA C22.2 No. 5-02
Rated current
Rated short circuit current SCCR
UL safety fuse type AJT Class J
Rated current
Short-circuit current rating SCCR at 600 V
Safety fuses NH
Rated current
Sound pressure level
Cooling air requirement
Rated voltage for rated data 380 V 3 AC
Weight
1) The specified values apply to 380 V
2) For an overview, see the power loss tables in Cabinet Design chapter.
312
6SL3131–
kW
A
kA
AC
A
kA
A
kA
AC
A
dB(A)
m
/h
3
kg
6AE15–0AAx
5
3RV1042-4BA10
14 ... 20
100
To be added
AJT16
16
200
3NA3 805
16
< 60
29.6
5.3
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
6AE21–0AAx
10
3RV1042-4FA10
28 ... 40
100
To be added
AJT35
35
200
3NA3 814
35
< 60
29.6
5.4
Booksize power units