NOTICE
The line/load connection must not be interchanged.
Line voltage 415 V 3 AC to 480 V AC + 10 %
● Controlled DC link voltage required, or
● limitation of the DC link voltage required due to motor isolation
2.8.3.2
Line/power connection
Table 2-16
Type of connection
Terminals
Line supply connection (line supply)
Load connection (load)
Basic Line Filter for Smart Line Modules
5 kW
10 kW
16 kW
36 kW
1) for ring cable lugs to DIN 46234
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
Designations
L1, L2, L3, PE
L1´, L2´, L3´, PE
Screw terminal: 10 mm
2
Grounding bolt: M6/6 Nm
Screw terminal: 35 mm
2
Grounding bolt: : M6/6 Nm
2.8 Basic Line Filter for Smart Line Modules
3-pin/1.5 -1.8 Nm (see Screw Terminals chapter)
1)
1)
Line Connection Booksize
75