Technical Data - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.2.7

Technical data

Table 4-10
Technical data for Booksize Single Motor Modules (3 to 30 A)
Internal air cooling
Rated current
Voltage
Infeed:
DC link voltage
Electronics power supply
Output voltage
Overvoltage trip threshold
Undervoltage trip threshold
Electronics current consumption at 24 V
Total power loss
(including electronic losses)
Rated output current (l
)
n
Base load current (I
)
base
Intermittent duty current (l
Peak current (l
)
max
DC link busbar current carrying capacity
24 V busbar current carrying capacity
Rated power
(with DC link voltage of 600 V
frequency of 4 kHz)
Max. pulse frequency without derating
Max. pulse frequency with derating
Max. ambient temperature without derating
Max. ambient temperature with derating
DC link capacitance
Sound pressure level
Cooling type
Cooling air requirement
Weight
1) For an overview, see the power loss tables in Chapter Cabinet design
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
1)
) 40 %
s6
and pulse
DC
4.2 Motor Modules with internal air cooling
6SL3120–
1TE13-
0AAx
A
3
V
510 – 720
DC
V
24 (20.4 - 28.8)
DC
V
0 - 0.717 x DC link voltage
ACrms
V
820 ± 2 %
DC
V
380 ± 2 %
DC
A
0.85
DC
W
50.4
A
3
ACrms
A
2.6
A
3.5
ACrms
A
6
ACrms
A
100
DC
A
20
DC
kW
1.6
kHz
4
kHz
16
°C
40
°C
55
μF
110
dB(A)
<60
Internal
fan
m
/h
29.6
3
kg
5
Motor Modules Booksize
1TE15-
1TE21–
1TE21–
0AAx
0AAx
8AAx
5
9
18
0.85
0.85
0.85
75.4
100.4
185.4
5
9
18
4.3
7.7
15.3
6
10
24
10
18
36
100
100
100
20
20
20
2.7
4.8
9.7
4
4
4
16
16
16
40
40
40
55
55
55
110
110
220
<60
<60
<60
Internal
Internal
Internal
fan
fan
fan
29.6
29.6
29.6
5
5
5
1TE23-
0AAx
30
0.9
311.6
30
25.5
40
56
100
20
16
4
16
40
55
705
<60
Internal
fan
56
6.9
337

Advertisement