Meaning Of The Leds On The Smart Line Module - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

3.7.3.7

Meaning of the LEDs on the Smart Line Module

Table 3-57
Smart Line Module 16 kW - Description of the LEDs
State
Ready (H200) DC link (H201)
OFF
OFF
Green
OFF
Orange
Red
Orange
Orange
Red
Green/red
(0.5 Hz)
Green/red
-
(2 Hz)
Green/orange
or
Red/orange
Hazardous DC link voltages may be present at any time regardless of the status of the
"DC link" LED.
The warning information on the components must be carefully observed!
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
Electronics power supply is missing or outside
permissible tolerance range.
The component is ready for operation and cyclic
DRIVE-CLiQ communication is taking place.
The component is ready for operation and cyclic
DRIVE-CLiQ communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic
DRIVE-CLiQ communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON.
Component detection via LED is activated (p0124).
Note:
Both options depend on the LED status when
component recognition is activated via p0124 = 1.
DANGER
3.7 Smart Line Modules Booksize Compact
Description, cause
Line Modules Booksize
Remedy
Check line voltage
Remedy and acknowledge
fault
Carry out a POWER ON
285

Advertisement

Table of Contents
loading

Table of Contents