Cabinet Design and EMC Booksize
9.4 Arrangement of components and equipment
The inlet temperature of the air sucked in for cooling the module must not exceed 40°C (with
derating, the inlet temperature must not exceed 55°C). This must be ensured by means of
suitable air guidance, the clearance between the module rows, or by air baffle plates.
The distance between the rows also depends on the required bending radii of the power
cables to be connected.
CAUTION
Signal cables must not be routed parallel to power cables.
Wiring rules for DRIVE-CLiQ
See the Commissioning Manual
Table 9-10
Overview of the DC link rectifier adapter and DC link adapter
DC link rectifier adapter (cable outlet on top)
6SL3162-2BD00-0AAx
6SL3162-2BM00-0AAx
DC link adapter (cable outlet on side)
6SL3162-2BM01-0AAx
Note
The current carrying capacity of the DC link busbars must be taken into account. For the
specifications, see the technical data for the components.
516
Suitable for module width
50 mm, 100 mm
150 mm, 200 mm, 300 mm
all
Max. connectable cross-
section
10 mm
2
95 mm
2
95 mm
2
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
Max. current carrying
capacity
36 A
240 A
240 A
Booksize power units