Meaning Of The Leds On The Control Supply Module - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Booksize DC Link Components
6.3 Control Supply Module
The Control Supply Module (CSM) is connected to the line supply (3-ph. 380 V AC –10 % up
to 480 V +10 %) via the appropriate screw terminals (0.2 to 4 mm
preferably be made without using an isolating device (e.g. contactor).
The CSM is protected corresponding to the data provided in the Equipment Manual for
Booksize power units. The CSM has an internal line filter (Class A for TN line supplies), and
the pre-charging circuit for the DC link inside the unit is electrically isolated from the 24 V
supply.
Note
When engineering the line supply of the CSM, it should be noted that the CSM may not be
connected to the line supply after the line module is connected to the line supply. When
charging, this prevents the DC link from being immediately loaded by the CSM.
NOTICE
If a selectively tripping AC/DC-sensitive residual-current circuit-breaker is used, the Control
Supply Module must be connected downstream of this.
6.3.3.3

Meaning of the LEDs on the Control Supply Module

Table 6-8
Control Supply Module – description of the LEDs
LED
Color
READY
-
off
Green
Continuous
DC LINK
-
off
Orange
Continuous
Red
Continuous
424
Status
Electronics power supply is missing or outside permissible
tolerance range.
Component is ready to operate.
Electronics power supply is missing or outside permissible
tolerance range.
DC link voltage within permissible tolerance range.
DC link voltage outside permissible tolerance range.
Description, cause
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6