Siemens SINAMICS S120 Equipment Manual page 346

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor Modules Booksize
4.3 Motor Module with external air cooling
Cable shields and unused power cable conductors (e.g. brake conductors) must be
connected to PE potential to prevent capacitive cross-talk charges.
Non-observance can cause lethal shock voltages.
It is essential to apply the shield for the motor holding brake. Furthermore, only Motion-
Connect cables must be used for integrated motor holding brakes, as otherwise insulation
of the wires is not guaranteed. Risk of electric shock.
CAUTION
Only cables from Siemens must be used for DRIVE-CLiQ connections.
CAUTION
Connecting cables to temperature sensors must always be installed with shielding. The
cable shield must be connected to the chassis potential at both ends over a large surface
area. Temperature sensor cables that are routed together with the motor cable must be
twisted in pairs and shielded separately.
NOTICE
The external air cooling can cause the fans and the heat sink to become heavily
contaminated, which may trigger the temperature monitor in the power unit. The fans and
heat sink must be checked for contamination at regular intervals and, if necessary, cleaned.
Note
After installation, the seal on the rear of the device must be checked to ensure that it is tight.
Additional sealing can be used, if necessary.
Note
The mounting frames can only be used if the cabinet has an unpainted metal surface.
346
WARNING
DANGER
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6

Advertisement

Table of Contents
loading

Table of Contents