Siemens SINAMICS S120 Equipment Manual page 458

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Accessories
8.1 Shield connecting plates
Table 8-5
Electrical connection at the shield connecting plate for 200 mm component using as an example, internal air
cooling
Unlock and remove the cover of the
terminal block.
Adjust the shock-hazard protection
using a suitable tool
Close the cover of the terminal block.
458
Remove nuts M8 using a suitable tool
Attach the shock-hazard protection
Secure the earthing cable with
screwdriver T25 and the power cable
with torque spanner M8/13 Nm
Secure the shield clamp to the shield
connecting plate using a suitable tool
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6

Advertisement

Table of Contents
loading

Table of Contents