2.13 Line connection variants
2.13.3.7

Operating line connection components via an isolating transformer

The isolating transformer converts the network configuration of the system (e.g. IT/TT
system) to a TN system. Additional voltage adaptation to the permissible voltage tolerance
range is possible.
An isolating transformer must be used in the following cases:
● The insulation of the Motor Module and/or the motor is not suitable for the voltages that
● There is no compatibility with an existing residual-current protective device.
● The installation altitude is higher than 2000 m above sea level.
● A line filter should be used in a line supply system that is not a TN line supply system
134
occur.
with grounded neutral conductor.
Note
In IT systems and when a Basic Line Filter is used, the connection bracket for the
interference-suppression capacitor must be removed when a 80 kW or 120 kW Active
Interface Module is used.
CAUTION
If the supply voltage is greater than 480 V +10 %, it is not permissible to use an
autotransformer.
An isolating transformer must be used to ensure protective separation.
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6