Siemens SINAMICS S120 Equipment Manual page 326

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor Modules Booksize
4.2 Motor Modules with internal air cooling
Table 4-2
Terminal block Single Motor Module 45 A to 200 A
Terminals
U2
V2
W2
+ (BR+)
- (BR-)
PE connection
1) For ring cable lugs to DIN 46234
2) The circuit for protecting the brakes against overvoltage is in the Motor Module and does not need to be installed externally. The max. load
current is 2 A, the min. load current 0.1 A.
Note
The total length of the shielded power cables (motor supply cables and DC link cables) must
not exceed 350 m.
Note
The motor brake must be connected via connector X11. The BR - cable must not be
connected directly to electronic ground (M).
Only protective extra-low voltages (DVC A) that comply with EN60204-1 must be connected
to all connections and terminals between 0 and 48 V DC.
The voltage tolerances of the motor holding brakes must be taken into account.
326
Technical specifications
45 A to 60 A:
Threaded bolt M6/6 Nm
85 A:
Threaded bolt M8/13 Nm
132 A to 200 A:
Threaded bolt M8/13 Nm
X11 brake connector
Voltage 24 V DC
Max. load current 2 A
Min. load current 0.1 A
Max. connectable cross-section 2.5 mm
Type: Spring-loaded terminal 2 (see Connection System)
Manufacturer: Wago; Order No.: 721-102/026-000/56-000
The brake connector is part of the prefabricated cable.
Single Motor Module with a rated output current of 45 A to 60:
Threaded bolt for motor cables: M6/6 Nm
Threaded hole for PE: M6/6 Nm
Single Motor Module with a rated output current of 85 A
Threaded bolt for motor cables: M8/13 Nm
Threaded hole for PE: M6/6 Nm
Single Motor Module with a rated output current of 132 A to 200 A
Threaded bolt for motor cables: M8/13 Nm
Threaded hole for PE: M8/13 Nm
WARNING
1)
1)
1)
:
2)
2
1)
1)
1)
1)
1)
1)
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
Booksize power units

Advertisement

Table of Contents
loading

Table of Contents