3. AD57G MONITORING FUNCTIONS
MELSEC-A
(c) Set report (Printing allocation) window
After selecting "Printing allocation" in the Set report (Printing alloca-
tion) window and displaying a report canvas screen, this window can
be displayed.
I
w
Sections 3.9(2), (6) and (8)(d) and (e) give details about item setting.
Set report (Printing allocation) window
Setting Item
'rint position
'rint type
Logging data
2)
1
Print type
3)
(
Common setting
Monitoring Condition Setting Description
Setting Contents
jet the printing position of the data selected in 2) on each report canvas screen.
;elect the type of print data to be printed to the position set in 1).
Print time
:
Printing the starting time and date of collected data
Log time
:
Time and date when print data were collected
Log data
: Data collected from the device set in 4) (Numerical value)
ipecify the storage location (report data file name and record number) of the data to be
~rinted out (see Section 3.9(8)(d), (e)).
Time
Set the number from the head or the end of a file to the set value of the
serles
: following Record No.
Old
:Number from the head
New
:Number from the end
Record
Set the record in which print data is stored.
No.
: (Head of the file and the relative record position from the end)
Nhen Log data is selected in 2), set the device that collects data to be printed to the
oosition set in 1) in the monitored device sening window.
If Print time or Log time are seleoted in 2), it is not necessary to set this item.
Nhen Log data is selected in 2), set the following in the display format (input) setting
~ i n d o w
Data type
:
Set the unit of data collected from the device of 4) to 16 bits (1 word) or
32 bits (2 words).
Number of
Set the number of numerical characters per line when the collected data
display
is printed out in decimal.
(input)
(If the data contains signs and decimal points, they must be included.)('l)
columns
:
16-bit data:l-8 columns
32-bit data:t-13 columns
Code
: Set collected data to coded or uncoded data
Decimal
If collected data is printed with a decimal point, set the printing position
point
of the decimal point.
position
:
16-bit data
:
0 to 5 digits from the lowest digit
When data is 0, it is
not necessary to set
32-bit data
:
0 to 10 digits from the lowest digit
the number of set columns, the columns for the irrelevant higher digits are ignored.
When the value in the collected data is more than the number of set columns, the printout
is executed for the actual value.