Acceleration/Deceleration Pattern - Mitsubishi Electric FR-CS82S-025 Instruction Manual

Hide thumbs Also See for FR-CS82S-025:
Table of Contents

Advertisement

5.4.2

Acceleration/deceleration pattern

The acceleration/deceleration pattern can be set according to the application.
Pr.
Name
29
Acceleration/deceleration pattern
F100
selection
 Linear acceleration/deceleration (Pr.29 = "0" initial value)
• When the frequency is changed for acceleration, deceleration, etc. during inverter operation, the output frequency is
changed linearly (linear acceleration/deceleration) to reach the set frequency without straining the motor and inverter.
Linear acceleration/deceleration has a uniform frequency/time slope.
Setting value "0"
[Linear acceleration
/ deceleration]
Time
 S-pattern acceleration/deceleration B (Pr.29 = "2")
• This is useful for preventing collapsing stacks such as on a conveyor. S-pattern acceleration/deceleration B can reduce
the impact during acceleration/deceleration by accelerating/decelerating while maintaining an S-pattern from the present
frequency (f2) to the target frequency (f1).
[S-pattern acceleration
/deceleration B]
f1
f2
Time
NOTE
• When the RT signal turns ON during acceleration or deceleration with the S-pattern acceleration/deceleration B enabled, a
pattern of acceleration or deceleration changes to linear at the moment.
Initial
Setting range
value
0
Linear acceleration/deceleration
0
2
S-pattern acceleration/deceleration B
5.4 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Description
5. PARAMETERS
2
2
3
4
5
6
7
8
9
10
95

Advertisement

Table of Contents
loading

Table of Contents