Mitsubishi Electric FR-CS82S-025 Instruction Manual page 123

Hide thumbs Also See for FR-CS82S-025:
Table of Contents

Advertisement

 Adjusting the stall prevention operation signal and output timing (OL
signal, Pr.157)
• If the output current exceeds the stall prevention operation level and stall prevention is activated, the Overload warning
(OL) signal turns ON for 100 ms or more. The output signal turns OFF when the output current falls to the stall prevention
operation level or less.
Pr.157 OL signal output timer
time period.
• This function also operates during regeneration avoidance operation ("
Pr.157 setting
0 (initial value)
Output immediately.
0.1 to 25
Output after the set time (s).
9999
Not output.
Overload state
(OL operation)
OL output signal
NOTE
• For the OL signal, set "3 (positive logic)" or "103 (negative logic)" in Pr.195 (Output terminal function selection) to assign
the function.
• If the stall prevention operation lowers the output frequency to 0.5 Hz and kept the level for 3 seconds, the stall prevention stop
(E.OLT) is activated to shut off the inverter output.
• Changing the terminal assignment using Pr.195 (Output terminal function selection) may affect the other functions. Set
parameters after confirming the function of each terminal.
122
5. PARAMETERS
5.6 (H) Protective function parameter
can be used to set whether to output the OL signal immediately, or to output it after a certain
Description
Pr.157 Set time(s)
" overvoltage stall).