Mitsubishi Electric FR-CS82S-025 Instruction Manual page 155

Hide thumbs Also See for FR-CS82S-025:
Table of Contents

Advertisement

 PID action
PID action is a combination of PI and PD action, which enables control that incorporates the respective strengths of these
actions.
Set point
Measured value
P action
I action
D action
PID action
(Note) PID action is the result of all P, I and D actions being added together.
 Reverse action
When deviation X = (set point - measured value) is a plus value, the manipulated amount (output frequency) is increased, and
when the deviation is a minus value, the manipulated amount is decreased.
 Forward action
When deviation X = (set point - measured value) is a minus value, the manipulated amount (output frequency) is increased,
and when the deviation is a plus value, the manipulated amount is decreased.
Relationship between deviation and manipulated amount (output frequency)
PID action setting
Reverse action
Forward action
154
5. PARAMETERS
5.10 (A) Application parameters
Deviation
Time
Time
Time
Time
[Heating]
+
X>0
Cold
Set
Hot
X<0
point
-
Feedback signal
(measured value)
[Cooling]
X>0
+
Too cold
Set
Hot
X<0
point
-
Feedback signal
(measured value)
Deviation
Plus
Minus
Deviation
Increase
Decrease
Measured value
Measured value
Decrease
Increase
Deviation
Set point
Set point

Advertisement

Table of Contents
loading

Table of Contents