 Fault output after deceleration to stop (Pr.573 = "3")
• When the analog current input becomes 2 mA or lower, the inverter output decelerates the motor to a stop, and then the
protective function E.LCI (4 mA input fault) is activated and the output is shut off.
• When the analog current input is restored during the deceleration, the motor is accelerated again and operates according
to the current input.
• The following is the operation example during PID control (reverse action) operation.
Output frequency
20mA
Set point (fixed)
Measured value
4mA
STF
LF signal
PID signal
• The following is the operation example when the analog input current is restored during deceleration under PID control
(reverse action).
Output frequency
20mA
Set point (fixed)
Measured value
4mA
STF
LF signal
PID signal
Decelerates as the input current is lost
Normal operation after the current is restored
Input current
decrease
Return
3mA
2mA
OFF during
deceleration
Decelerates as the input current is lost
Normal operation after the current is restored
Input current
decrease
Return
3mA
2mA
OFF during
deceleration
Time
Time
5. PARAMETERS
5.8 (T) Multi-function input terminal parameters
2
2
3
4
5
6
7
8
9
10
141