14.5

Gas ALS: Gas load control

With the gas load control, the setpoints and the
input from the meter must be set to activate gas
optimization. In addition, each load group used for
gas load control must have the function set to Gas
load group.
Name
Default
T1, T2, T3, T4 0,0,0,0
Z
IO1
Hys
0
The possible numbers of load groups are as follows
· Procont
-LMC: 1 to 128
®
· Procont
-LMC-LITE: 1 to 16
®
14.6

Maximum power:

Activates the maximum power limitation.
Name
Default
Hysteresis
5
Ansprech-
0
verz.
Z1, Z2
HZ
Setting
Description
c
Load control value for the respective tariff
T1: High tariff/winter T2: Low tariff/winter
T3: High tariff/summer T4: Low tariff/summer
IO1 – IO12
Input from meter
0-99 %
Hysteresis
Setting
Description
0-999.9 kW
Hysteresis of the maximum power
0-255 s
Response delay of the maximum power
HZ, IO1-
Meter for the maximum power
IO12, P+
Procont