13.2
Controller type: Controller
(analog 0-100%)
LG-Nr.:1
LG-Nr.:1
Par-1:
Par-1:
Prio: 1
Prio: 1
Min-Wert: 20 %
Min-Wert: 20 %
Sprung / Schaltg: 3%
Sprung / Schaltg: 3%
Name
Default
LG-Nr.
Par-1
Prio
1
Min-Wert
20 %
Sprung/Schltg
3%
13.3

Early warning

Each consumer can be assigned to an early
warning contact. The early warning contact is
activated when the respective consumer needs to
be switched off. The switch-off of the respective
consumer (group) is delayed by the time set here.
During this early warning time, a load group de-
fi ned as an early warning contact is switched on.
(Setting range, 0 - 255 seconds).
Setting
Description
As many consumers can be set as have been defi ned in the sys-
tem settings. If the same priority is assigned to 2 or more loads,
they are equal and the order of disconnection is changed with
each disconnection cycle according to a fi xed schema.
Reglerfunktion (Con-
Control for electronic load relays (pulse-pause control)
troller function)
1, 2, ... x (x = num-
Shutdown priority
ber of load groups)
The priorities are already preset and correspond to the respective
load group number LG-1 = priority 1, LG-2 = priority 2 and so on.
Priority 1 means the most important consumer; this is the last to
be switched off and the fi rst to be switched back on.
The load program calculates the switch-off time of the individual
loads provided that min./max. times that have been set do not
infl uence the timer and logical links do not infl uence the switching
operations.
0 – 99 %
Minimum required switch-on power: This value indicates the mini-
mum "%" with which the consumer remains switched on.
0 – 9%
Jump per switching cycle: This value specifi es at what intervals
(speed) the consumer is switched off.
Possible setting: 0 – 9%