Procont
-LMC | Procont
®
5.

Assembly and installation

Risk of injury due to electrical voltage!
Severe bodily injury or death can result from:
· Touching bare or stripped leads that are ener-
gized.
· Device inputs that pose a hazard when
touched.
Switch off your installation before commencing
work! Check to be sure it is de-energized!
The installation of the load management controller
Procont
-LMC-LITE, Procont
®
as follows:
1. Install an isolation device (switch or circuit
breaker) and an overcurrent protective device
(2-10 A).
INFORMATION
As an alternative to the isolation device or
fuse, you can use a line circuit breaker.
2. Mount the measurement device in switchboard
cabinets or small distribution boards according
to DIN 43880 (any mounting orientation) on a
35 mm (1.38 in) DIN rail.
3. Press the bottom bolt into the device. Check
the device for a fi rm fi t. The mounting orienta-
tion is arbitrary.
4. Connect the device to your local network
using a standard RJ45 patch cable.
18
-LMC-LITE
®
DANGER
-LMC is carried out
®
Press
5. Connect the supply voltage.
Refer to the rating plate for the proper supply
voltage for your device. After connecting the
supply voltage, the display becomes active. If
no display appears, check whether the supply
voltage is within the nominal voltage range.
PE L L N N
L1
L2
L3
N
PE
Fig. Power supply connection
ATTENTION
Material damage due to disregard of the instal-
lation instructions!
Disregard of the installation instructions can
damage or destroy your device.
· Observe the information on the mounting orien-
tation in the sections "Mounting" and "Technical
Data".
· Provide adequate air circulation in your installa-
tion environment and, as needed, cooling when
the temperatures are high!