Control Series Editor - janitza Prophi 15T-III Manual

Power factor controller
Table of Contents

Advertisement

Prophi
15T-III
®
AUTO-MODE 1/2
j
cos
0.869 IND
L1
j
cos
0.869 IND
L2
j
cos
0.869 IND
L3
L1
L2
L3
1 2 3 4
1
LINE VOLTAGE
L1-N
230 V
L2-N
230 V
L3-N
230 V
PE-N
0 V
2
APPAR.CURRENT
L1
123 A
L2
239 A
L3
167 A
3
REACTIVE POWER
L1
88 kvar
L2
88 kvar
L3
88 kvar
S
264 kvar
4
ACTIVE POWER
L1
88 kW
L2
88 kW
L3
88 kW
S
264 kW
5
APPARENT POWER
L1
88 kVA
L2
88 kVA
L3
88 kVA
S
264 kVA
6
DIFF. TO PF
L1
12 kvar
L2
24 kvar
L3
16 kvar
N
52 kvar
7
TEMPERATURE
25 °C
8
HARMONICS [ 3.]
L1
V 0.5% I 1.0%
L2
V 0.8% I 1.0%
L3
V 0.5% I 1.0%
9
HARMONICS THD
L1
V 0.3% I 0.2%
L2
V 0.3% I 0.2%
L3
V 0.3% I 0.2%
10
COMP.- POWER
100 kvar / 7%
11
TIME / DATE
12:56:07
TUESDAY
05/26/2016
12 SOFTWAREVERSION
VERSION 1.2
BACK TO 1
40
===== PROGRAM-MODE =====
1
LANGUAGE [ 2 ]
[ ENGLISH ]
2 CONTROL-MODE [ 1 ]
[ 3 ] PHASE MEASURING
max. [ 3x5 single ph ]
capacitors PH-N
3 I-CONVERTER PRIM
L1 [ 1000 ] A / 5 A
L2
1000 A / 5 A
L3
1000 A / 5 A
4 I-CONVERTER SEC.
L1
1000 A / [5] A
L2
1000 A / [5] A
L3
1000 A / [5] A
5
END STOP L... -N
L1-N
[ 5 ]
L2-N
5
L3-N
5
6
CONT.SERIES L...-N
L1-N
1 1 1 1 1
[ 1 ]
L2-N
1 1 1 1 1
1
L3-N
1 1 1 1 1
1
7
CONTR. PRINC. [ 3 ]
[ INTELLIGENT ]
8
POWER 1st STAGE
L1
[ 25 ]. 00 kvar
L2
25 . 00 kvar
L3
25 . 00 kvar
9
TARGET cos j
[ 0.98 IND ]
10
TARGET 2nd cos j
[ NO ]
11
TARGET 2nd cos j
[ 0.98 IND ]
12 SWITCH ON TIME j2
ON [ 16 ] : 00
MO-FR
OFF 07 : 00
MO-FR
13 SWITCH OFF TIME j2
ON
16 : 00
MO-FR
OFF [ 07 ] : 00
MO-FR
- 39 -
14 MEASUR. VOLTAGE
L - L [ 400 ] V
L - N
230 V
15
V- CONVERTER
[ NO ]
16
FREQUENCY
[ 50 ]Hz
17 - 19
... TIME
C-ON
[ 1000 ] ms
C-OFF
1000 ms
C-DIS
1000 ms
20 ALARMTEMPERATURE
[ 55 °C ]
21 FAN TEMPERATURE
[ 30 °C ]
22 MESSAGE RELAY [ 1 ]
[ ENERGY SUPPLY ]
23
EXT. INPUT [ 1 ]
[ NO ]
2
24 - 37
Values 2nd parameter set
( if selected at item 23 )
38 HARMONICS
THD-V [ 7.0 ] %
39 CLOCK / DATE
[HH] : MM
WEEKDAY
TT : MM : JJJJ
40 CONTRAST
****** [ 6 ] ******
41 BASIC SETTINGS
BACK TO 1
only available if control
serie "ED" is selected
CONTROL SERIES
EDITOR
VALENCY C01 [ 1 ]
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
selection until (max.) C15
with button ENTER
VALENCY C15 [ 1 ]
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
BACK TO 1
Changing
of values
by buttons:

Advertisement

Table of Contents
loading

Table of Contents