Lmc - janitza Procont-LMC User Manual And Technical Data

Load management controller
Table of Contents

Advertisement

Procont
-LMC | Procont
®
15.1
Regeln + Verknüpfung (Control types +
links) for Procont
10:00:00 MI 10.05.2022
10:00:00 MI 10.05.2022
HZ: 0.00 kW
HZ: 0.00 kW
10.0m
10.0m
HT/Wint.
HT/Wint.
Abg.LG: 0
Abg.LG: 0
Parameters
Designation
Nr(1):
Control number
001:
Global control number
Mn,Mx
Minimum, maximum value
V: Hptmss
Hptmss =Main measurement, I
O1-d, IO2-d,....
U:Lk
Lk=Local controller, 01, 02 (=station number), ...
A: Dig, Ana
Type: Digital or analog, DGw=Digital with limits
< oder >
smaller or larger: Exceeded or undershot
+ oder -
positive or negative value
Hys:10
Hysteresis 10 %
E: 5
Switch-on delay 5 s
A: 5
Switch off delay 5 s
W=>+000100.0
Limit value
M:
Minimum running time in minutes
40
-LMC-LITE
®

-LMC

®
Eingabeauswahl:
Eingabeauswahl:
* Lastkontrolle
* Lastkontrolle
* Master Ctrl.+ Subst.
* Master Ctrl.+ Subst.
* Regeln+Verknüpfung
* Regeln+Verknüpfung
www.janitza.de
Nr(1):
Nr(1):
->RG-001(Mn)
->RG-001(Mn)
V:Hptmss U:Lk A:Dig
V:Hptmss U:Lk A:Dig
W=>+000100.0 Hys: 10
W=>+000100.0 Hys: 10
E: 5 A: 5 M: 0,0
E: 5 A: 5 M: 0,0