Load Management Controller Procont ® -LMC Procont -LMC-LITE ® User manual and technical data Janitza electronics GmbH Vor dem Polstück 6 35633 Lahnau | Germany Support tel. +49 6441 9642-22 info@janitza.de | www.janitza.de...
Page 2
Procont -LMC | Procont -LMC-LITE ® ® Procont -LMC ® Procont -LMC-LITE ® Load Management Controller Doc. no.: 2.100.141.1.a 08/2023 The German version is the original edition of the documentation.
Page 3
Nonetheless, we wish to point out that updates of this document are not always possible at the same time as technical refinements are implemented in our products. Information and specifications are subject to change at any time. Please check for the latest version at www.janitza.de.
· When doing so, please bear the terms for trans- portation in mind. INFORMATION Please return defective or damaged devices to Janitza electronics GmbH in accordance with the shipping instructions for air or road freight (complete with accessories). Observe special regulations for devices with built-in...
Procont -LMC | Procont -LMC-LITE ® ® Safety The chapter on Safety contains information which Hazard levels must be observed to ensure your personal safety Warning and safety information is marked by a and avoid material damage. warning symbol, and the hazard levels are shown...
Procont -LMC | Procont -LMC-LI ® ® Product safety Therefore, when handling our devices, always observe the following: The device reflects current engineering practice · do not exceed the limit values specified in the and accepted safety standards, but hazards can user manual and on the rating plate! This must nonetheless arise.
Procont -LMC | Procont -LMC-LITE ® ® Electrically qualified personnel Warranty in the event of damage To avoid bodily injury and material damage, only Any unauthorized tampering with or use of the electrically qualified personnel are permitted to device constitutes "misuse" and/or "negligence"...
Please see the EU declaration of conformity post- · Its flawless mechanical condition by visual in- ed at www.janitza.de for the laws, standards and spection. directives applied by Janitza electronics GmbH for · The scope of delivery for completeness.
35633 Lahnau / Germany 35633 Lahnau / Germany PROCONT-LMC • 6000300 10/2021 • 16.0f Made in Austria Power consumption in VA PROCONT-LMC-008-IO • 6000303 10/2021 • 002 Made in Austria Aux: 100..240V, 50/60Hz 9-15VA Aux: 230V, 50Hz PROCONT-LMC • 6000300 10/2021 •...
Procont -LMC | Procont -LMC-LITE ® ® Assembly and installation 5. Connect the supply voltage. DANGER Refer to the rating plate for the proper supply Risk of injury due to electrical voltage! voltage for your device. After connecting the Severe bodily injury or death can result from: supply voltage, the display becomes active.
Procont -LMC | Procont -LMC-LI ® ® Connection and PC connections Establish the connection to the PC ATTENTION Material damage due to security vulnerabili- Possible connections for communication between ties in programs, IT networks and protocols. the PC and the device: Example circuit diagrams/...
Procont -LMC | Procont -LMC-LITE ® ® Screen on Display The following screen appears on the display after an initialization routine has been completed: 10:00:00 10:00:00 10.05.2022 10.05.2022 HZ: 0.00 kW HZ: 0.00 kW 10.0m 10.0m HT/Wint. HT/Wint. Abg.LG: 0 Abg.LG: 0...
Procont -LMC | Procont -LMC-LITE ® ® Instantaneous value alarm (limit values) Alarmeinstell.( 1) Alarmeinstell.( 1) Art:Moment. Art:Moment. Prio: 0 Prio: 0 Hptmss>+00000.00 Hptmss>+00000.00 E:000.000 E:000.000 A:000.000 A:000.000 Instantaneous value alarm: An alarm is output when a value is exceeded or not reached.
Procont -LMC | Procont -LMC-LI ® ® Eco-Regler (Eco controller) The eco controller ensures that excess energy is not fed into the power grid. The connected load for the photovoltaic system can be found in the "Eco controller" submenu.
Procont -LMC | Procont -LMC-LITE ® ® 10.3 Pulse valency for external meters Please select 'Input' or 'Output' in the upper right panel. · Function: Input (meter) -> Select 'Input' and set parameters · Function: Output (meter) -> Select 'Input' and set parameters 10:00:00 MI 10.05.2022...
Procont -LMC | Procont -LMC-LI ® ® 10.4 Function modules Various function modules are available that can be linked with an output in series or in parallel. There are 4 modules available per output, which can be linked either all in series or 2 each in parallel.
Procont -LMC | Procont -LMC-LITE ® ® 11. Ethernet adapter/ network settings The settings of the controller related to the network can be found in the submenu "Ethernet adapter". Eingabeauswahl: Eingabeauswahl: 10:00:00 MI 10.05.2022 10:00:00 MI 10.05.2022 * Ethernet-Adapter * Ethernet-Adapter HZ: 0.00 kW...
Page 30
Procont -LMC | Procont -LMC-LITE ® ® Modbus settings Designation Default Setting Function Aktivierung Deaktiv (Deactivated) Deactivated, Modbus, MBus The meter can be activated Activation) here Comm (C) Ser. Schnittstelle (interface) Ser. Schnittstelle (interface) (1), Interface type TCP/IP (2) Adresse Number of the meter, e.g.: 1...
Procont -LMC | Procont -LMC-LITE ® ® 13.1 Controller type: Normal (digital -> on/off e.g. with relay) LG-Nr.:1 LG-Nr.:1 Par-1: Par-1: Prio: 1 Prio: 1 EE: 0.0 m EE: 0.0 m ZA:: 0.0 m ZA:: 0.0 m EA: 0.0 m TgA: 0 m EA: 0.0 m TgA: 0 m...
Procont -LMC | Procont -LMC-LITE ® ® 14.3 Main meter (HZ): Selection of the main meters. With the Procont -LMC, several meters can be ® selected. Name Default Setting Description + or - The following meter is added or subtracted IO1, IO2, …...
Procont -LMC | Procont -LMC-LI ® ® 14.5 Gas ALS: Gas load control With the gas load control, the setpoints and the input from the meter must be set to activate gas optimization. In addition, each load group used for gas load control must have the function set to Gas load group.
Procont -LMC | Procont -LMC-LITE ® ® 14.7 Progressive maximum: In the event of a max. overrun, the highest value obtained from the utility is adopted as the setpoint, since the costs must be borne until the end of the month.
Procont -LMC | Procont -LMC-LI ® ® Example: Blocking time = 5 min, i.e. no new 20.3 Niedertarif (Low tariff) period can start in the fi rst 5 minutes of the period. Active low tariff This limits the number of false pulses.
Procont -LMC | Procont -LMC-LI ® ® Mom. Lstg: Instantaneous power determined 21.2 Kontrollen und Momentanwerte (Con- trols and instantaneous values) Trendwert (Trend value): The trend value average 10:00:00 MI 10.05.2022 10:00:00 MI 10.05.2022 shows the average consumption of the cur- HZ: 0.00 kW...
Procont -LMC | Procont -LMC-LI ® ® 21.3 Data You can enter the data menu by pressing the but- DATA . Use the buttons to switch to the next and previous view, respectively: Time and date, current power, period time, current tariff, switched-off load groups Use the cursor keys (""...
Procont -LMC | Procont -LMC-LI ® ® 22. Procedure in the event of a malfunction Error Cause Remedy Display dark or image Power supply missing or processor Reset the device (red button under the "Mini-USB" in- frozen. error terface), or disconnect from the mains and reconnect,...
Page 56
Procont -LMC | Procont -LMC-LITE ® ® Error Cause Remedy E-Mobility/storage Communication to the e-charging Check settings, check network connection of the station/storage unit fault, controller and the charging station Network No connection to the PC Network cable not plugged into...
Procont -LMC | Procont -LMC-LI ® ® 23. FAQ · How do I change the setpoint and the pulse valency? See „10.3 Pulse valency for external meters“ on page 26. · The controller is displaying an alarm, what could be the cause? See „8.
Page 58
Procont -LMC | Procont -LMC-LITE ® ® · Why can't I get a connection to my subdevices? For subdevices with IP interface there are the following possible error sources: 1. The devices are not on the same network or the network cable is not connected 2.
You can reach us from: Monday to Thursday between 07:45 am and 5:00 pm and on Friday between 07:45 am and 3:00 pm Janitza electronics GmbH Vor dem Polstück 6 35633 Lahnau, Germany Support. Tel.: +49 6441 9642-22 Email: support@janitza.de...