24. Technical data

General
Net weight (with attached plug-in connectors)
Device dimensions
Integrated memory
Mounting orientation
Installation mounting, suitable DIN rail-
35 mm (1.38 in)
LCD graphic design
Transport and storage
The following information applies to devices that are transported or stored in their original packaging.
Temperature
Relative air humidity (non-condensing)
Environmental conditions during operation
The device:
· Is for weather-protected and stationary use.
· Has protection class I;
for safe operation, the protective conductor must be connected!
Rated temperature range
Relative air humidity (non-condensing)
Operating elevation
Pollution degree
Ventilation
Protection against foreign matter and water
- Front
- Rear
Supply voltage
Nominal range
Frequency
Power consumption
Recommended overcurrent protective device for
line protection
Network types
Digital inputs/outputs
12 channels, not short-circuit proof
Inputs
Meter frequency
Outputs
Analog inputs
4 channels
Function
Procont
approx. 550 g (1.21 lbs)
W = 210 mm (8.27 in),
H =  100 mm (3.94 in),
D = 72 mm (2.83 in)
1 MB RAM
+ 8 GB micro SD card
8 MB flash
horizontal
TS 35/7.5 according to EN 60715 (12TE)
40 x 20 mm
-20 °C (-4 °F) to +60 °C (140 °F)
0 to 90% RH
0 °C (32 °F) .. +40 °C (104 °F)
0 to 80% RH
0 .. 2000 m (6562 ft) above sea level
PD 2
No forced ventilation required.
IP20 according to EN60529
IP20 according to EN60529
AC: 100V - -240V
50 - 60 Hz
22 VA
2-10 A, (Char. B), IEC-/UL approval
(TN-S / TN-C / TN-C-S)
24 V DC, max. 6 mA delay 10 ms
25 Hz
(max. 8 channels configurable as outputs) 24 V DC, max. 50 mA
Optionally 0..10 V / 0 (4)..20 mA, Pt1000,
Ni1000 (configurable via jumper)