14.1

Sollwerte (Setpoints)

Eingabeauswahl:
Eingabeauswahl:
* Ethernet-Adapter
* Ethernet-Adapter
* Lastgruppen
* Lastgruppen
* Lastkontrolle
* Lastkontrolle
Up to 12 different setpoints can be preset for the
power with the Procont
-LMC
®
and up to 4 with the Procont
Setpoints can be assigned for each tariff. These
are:
High tariff/winter (HT/Wi)
Low tariff/winter (NT/Wi)
High tariff/summer (HT/So)
Low tariff/summer (NT/So)
With the Procont
-LMC, there is an additional
®
function of a special tariff (ST) for each of the
above mentioned tariffs. This allows 8 setpoints to
be specifi ed.
If the 12 setpoints function is activated, a setpoint
for HT/ NT/ ST can be entered for each month.
The setpoints for the powers can be activated by
switching different inputs or by the automatic tariff
switching.
These setpoint settings depend on which tariffs are
active and whether the "12 Sollwerte (setpoints)"
setting is activated.
The only default setting to be set is the setpoint
(HT/Wi).
A maximum power limit can be activated to
protect main fuses or supply lines from overload.
All setpoints and the maximum value are to be
entered in kW.
A second nominal curve (curve 2) can be defi ned.
This is always lower than the normal curve (adjust-
able in percent).
During high-demand periods, loads that can be
turned off for extended periods of time can be
assigned to this lower power curve.
Possible settings: 0.0. – 999 999.9 kW
Sollwerte:
Sollwerte:
HT:
HT:
Wi: 000020.0 kW
Wi: 000020.0 kW
-LMC-LITE.
®
Procont
-LMC | Procont
®
14.2

Max. values

The max. values are assigned to the maximum
value (instantaneous value limit).
4 max. values can be entered for the following
tariffs:
High tariff/winter (HT/Wi)
Low tariff/winter (NT/Wi)
High tariff/summer (HT/So)
Low tariff/summer (NT/So)