janitza Procont-LMC User Manual And Technical Data page 56

Load management controller
Table of Contents

Advertisement

Procont
-LMC | Procont
®
Error
E-Mobility/storage
Network
No connection to the PC
Sub-meter, e.g.: from the utility company
Meter value is incorrect
No meter value display
Eco controller
No control
Incorrect control
Despite the above mea-
sures, the device does
not function
56
-LMC-LITE
®
Cause
Communication to the e-charging
station/storage unit fault,
Network cable not plugged into
controller/PC
Incorrect network data (IP address,
subnet mask, gateway) set on
controller/PC
Controller and PC are not in the
same network
DHCP set on the controller
Antivirus/Firewall blocked
Pulse valency set incorrectly
Cable was connected to the wrong
input
Wrong output selected
Eco controller not linked to output
Incorrect connected load
Device defective
Remedy
Check settings, check network connection of the
controller and the charging station
Check connection at controller/PC and correct if
necessary.
Check network data on controller/PC and correct if
necessary
Check network data
on controller/PC and correct if necessary, otherwise
contact network administrator (forwarding)
Set DHCP to "deactivated" and assign fixed IP ad-
dress, see „11. Ethernet adapter/ network settings"
on page 28
Create exception rule for Procont
Check pulse valency on controller/ external meter
and correct if necessary, see „10.3 Pulse valency for
external meters" on page 26
Check connection of cable at controller/external meter
and correct if necessary
Check output and correct if necessary
Check the settings in the "Eco-Regler (Eco controller)"
/ "Ein/Ausgänge (Inputs/outputs)" menu and correct if
necessary
Check connected load and correct if necessary
Send the device to the manufacturer for inspection
with an exact description of the fault