17.2

SS2 interface 2 RS-232

SS2: deactivated
Parameters
Default
1
M-Bus
9600 baud
SND_NKE
aktiv (active)
Fkt
MBus-Master
2
IR-Sensor
Art (Type)
AMIS
3
Logging
115200 baud
4
IEC-101
9600 baud
Data
8N1
17.3

SS3 interface 3 RS-485

SS3: deactivated
Parameters
Default
1
Sync-GW
B
38400 baud
2
ModbRTU
B
9600 baud
Adresse
1
(Address)
Data
8/N/1
Fkt
Modbus slave
HW
RS-232
3
Bus-Mst
MBus master
B
9600 baud
UModbus
Data
8N1
Fkt
Modbus master
4
IEC-101
9600 baud
Data
8N1
* SND-NKE bit procedure: This procedure starts on interruption or at the beginning of a communication if
this is required by the slave (meter).
The master (controller) sends this SND_NKE to the slave (e.g.: UMG96 meter). Once the slave sends an
acknowledgement, a connection can be established.
Range
Description
300, 2400, 9600 baud
Baud rate: M-Bus protocol
deaktiv/aktiv
*
(deactivated/activated)
Station is configured as bus master
Infrared sensor
AMIS
Manufacturer type of the meter
OBIS-Elster
OBIS-Iskra
OBIS
DLMS
not changeable
Message output for service application only
300, 2400, 9600, 19200,
Baud rate: Telecontrol protocol according to IEC-
38400, 115200 baud
60870-5-101
8N1, 8E1, 8O1, 8N2,
Data protocol: 8/none/1, 8/even/1, 8/odd/1,
8E2, 8O2
8/none/2, 8/even/2, 8/odd/2
Range
Description
Synch gateway: Connection of expansion devices
300, 2400, 9600, 19200,
Baud rate
38400, 115200 baud
The station is configured as a Modbus slave
2400, 9600, 19200,
Baud rate
38400, 115200 baud
1-255
Controller address
8N1, 8E1, 8O1, 8N2,
Data protocol: 8/none/1, 8/even/1, 8/odd/1,
8E2, 8O2
8/none/2, 8/even/2, 8/odd/2
Modbus slave
Interface as RS-232 or RS-485
Station is configured as bus master
300, 2400, 9600
Baud rate
8N1, 8E1, 8O1, 8N2,
Data protocol: 8/none/1, 8/even/1, 8/odd/1,
8E2, 8O2
8/none/2, 8/even/2, 8/odd/2
300, 2400, 9600, 19200,
Baud rate: Telecontrol protocol according to IEC-
38400, 115200 baud
60870-5-101
8N1, 8E1, 8O1, 8N2,
Data protocol: 8/none/1, 8/even/1, 8/odd/1,
8E2, 8O2
8/none/2, 8/even/2, 8/odd/2
Procont
-LMC | Procont
®
TE
-LMC-LI
®
43

Advertisement

Table of Contents
loading

This manual is also suitable for:

Procont-lmc-lite60 00 30060 00 301