Reactive Power Controller

Hints for installation

Mounting place

The reactive power controller Prophi is suited for mount-
ing and operation in reactive power compensation sys-
tems.
The connection is carried out on the back side via touch
proof spring power terminals.
Einspeisung
Verbraucher
Supply
Consumer
EVU-
Prophi
Messung
Electricity-
Meter
Einspeisung
Verbraucher
Supply
Consumer
EVU-
Messung
Electricity-
Meter
Einspeisung
Verbraucher
Supply
Consumer
EVU-
Prophi
Messung
Electricity-
Meter
Verbraucher
Einspeisung
Consumer
Supply
Prophi
Page 8
Richtig
Correct
Falsch
False
Prophi
Falsch
False
Falsch
EVU-
False
Messung
Electricity-
Meter

Measurement and supply voltage

The measurement is suited for 3 phase systems with or
without neutral conductor. Measurement and supply
voltage are taken from the measurement voltage and
must be connected to the building installation via a
separation (switch or power switch) and an overcurrent
protection (2A...10A).
Attention!
m
The operating voltage for the contactors
should be taken from an outer conductor con-
nected to the reactive power controller.
The reactive power controller measures and supervises
the voltage between two outer conductors. If one of
those two fails, the reactive power controller gets no
more measurement and operating voltage, and switches
on the capacitive stages after net return according to
the programmed times.
If the third outer conductor is missing, this will not be
recognized by the reactive power controller. If the con-
tactors are supplied by this outer conductor, the contac-
tors can attract simultaneously and without considera-
tion of the discharge time after net return.
Prophi
Messung
Measurement
L/L
siehe Typenschild
see type label
0,01 .. 5A
k
l
L2 L3
2 .. 10A
k
l
L1
L2
../5(1)A
L3
PE
Abb.: Anschluss der Mess- und Hilfsspannung zwischen
L2-L3 und der Strommessung über Stromwandlers.
= Key 1
= Key 2
Verbraucher
Consumer
= Key 3