2.2 Structure of PROFIBUS networks
Selection criteria for networking
The table below includes selection criteria for electrical and optical networking of PROFIBUS
devices:
Table 2- 3
Criteria
Transmission
medium
Distances
Topology
Transmission
protocols
Connection of
devices by means
of
Electrical network
segments can be
connected
● Suitable
– Not relevant for this application
1) Depending on data rate and type of service used
2) Depending on cable type used
Installation guideline for PROFIBUS networks
A PROFIBUS segment must be terminated at the start and end; passively with a connector
or actively with a bus terminating resistor.
The same principles apply to the installation of a PROFIBUS network as described in the
SIMATIC NET PROFIBUS networks
(http://support.automation.siemens.com/WW/view/en/35222591) manual.
18
Selection criteria for electrical and optical networking
Shielded two-wire
line
POF
PCF
Glass
Max. network span
Between two devices up to 1 km
Bus
Linear
Tree
Ring
OLM
Integrated interfaces
Bus terminal
Bus connector
Electrical
Optical network
PROFIBUS
with OLM
PROFIBUS DP:
90 km
9.6 km
PROFIBUS PA:
1.9 km
up to 15 km
1)
DP, PA
DP, PA
Function Manual, 12/2014, A5E03775446-AC
Optical network
with OBT
9.6 km
up to 300 m
2)
2)
DP
PROFIBUS with STEP 7 V13