OPTISWIRL 5080
Outputs
Output damping
Analogue output
General
Type
Supply current
Supply voltage effect
Ambient temperature effect
(amplifier only)
Response time (without
damping)
®
HART
Remote configurator /
Communicator
Communication rate
Communication distance
(rated)
Flow/Total measurement
update
Raw pulse measurement
update
04/2020 - 4005615602 - MA OPTISWIRL 5080 R02 en
Damping smooths the flow rate output and optimises the flowmeter's response time to
the control system.
Damping is an exponential filter with a selectable time constant; it can be set between 0
and 32 seconds.
An eight second damping factor will pass 64% of the step change in this time period.
Damping applies to all outputs except the raw pulse output where no damping is
applied to the direct vortex shedding frequency.
Flow rate available as a 4...20 mA signal with the 20 mA value being set by the
configured full range flow rate.
®
4...20 mA HART
22 mA DC maximum
Less than 0.005% per Volt
For +28°C / +50°F change in ambient temperature within operative limits.
Zero (4 mA): ±0.02% of span maximum
Span (16 mA): ±0.1% of span maximum
0.5 seconds or the vortex shedding period for frequencies less than 2 Hz.
HART analogue or digital multidrop mode
HART communicator or PC-Based configurator
1200 baud
1800 m / 6000 ft
5 times/s
Vortex shedding frequency
www.krohne.com
TECHNICAL DATA