ELECTRICAL CONNECTIONS
4
Figure 4-7: Wiring a flowmeter with a pulse output transistor switch (sinking) counter input with external power supply
and pull-up resistor
1 1/2 NPT or M20 conduit connection (2 places)
2 Internal ground terminal (connect a ground wire in accordance with local practice)
3 PE ground (required for explosion-proof applications)
4 External ground terminal
5 HART Communicator or PC-based configurator (at least 250 Ω total resistance between configurator
and power supply
6 Optional shielded wire (if used, terminate the shield at the negative terminal of the power supply)
7 Optional ground (grounding the loop at the negative terminal of the power supply is recommended but not required)
8 Receiver
9 Power supply
10 Load resistor (max. pulse output current is 20 mA; load resistor must be sized accordingly)
Figure 4-8: Wiring a flowmeter with a pulse output transistor switch (sinking) counter input with external power supply
and pull-up resistor
1 1/2 NPT or M20 conduit connection (2 places)
2 Internal ground terminal (connect a ground wire in accordance with local practice)
3 PE ground (required for explosion-proof applications)
4 External ground terminal
5 HART Communicator or PC-based configurator (at least 250 Ω total resistance between configurator
and power supply
6 Optional shielded wire (if used, terminate the shield at the negative terminal of the power supply)
7 Optional ground (grounding the loop at the negative terminal of the power supply is recommended but not required)
8 Receiver
9 Power supply
10 Load resistor (max. pulse output current is 20 mA; load resistor must be sized accordingly)
40
www.krohne.com
OPTISWIRL 5080
04/2020 - 4005615602 - MA OPTISWIRL 5080 R02 en