4310 Wireless Position Monitor
December 2011
3. Insert the cable gland into the housing. Install the nut on the inside of the housing and tighten to a torque of 2.5
N•m (22.1 in•lb).
4. Insert the wires through the cable gland.
5. Connect the wires to the connections as shown in figure 5. The terminals and electronics connections are
polarity-insensitive; ie., you can connect the positive or negative wire to either terminal screw.
6. Tighten the wiring terminal screws.
7. Pull the wires back through the cable gland to reduce the amount of wires in the housing cavity and hand-tighten
the cable gland.
8. Close the cover and tighten the instrument cover screws.
Figure 4. Cable Gland Assembly
O-RING
X0309
Figure 5. Installing the External Power Option
J1 PWR TERMINAL
HART
TERMINALS
COVER SCREWS
WIRING
CONNECTIONS
X0308
8
NUT
CABLE GLAND
J2 GND
TERMINAL
CABLE GLAND
POWER
WIRES
ELECTRICAL CONNECTION SCREWS (4 TOTAL)
MECHANICAL MOUNTING SCREWS (4 TOTAL)
Instruction Manual
D103391X012
NUT