Refer to table 6 for additional information and figure 31 for the ATEX/IECEx approvals nameplate.
Table 6. Hazardous Area Classifications—ATEX and IECEx
Certification
ATEX
Intrinsically Safe
IECEx
Ex ia IIC T3/T4/T5 Ga
IECEx
Special Conditions of Use
Intrinsically Safe
The apparatus must be only connected to a certified associated intrinsically safe equipment and this combination
must be compatible regarding intrinsic safety rules: Ui v 6.1V, liv 5mA, Pi = 30.5mW, Ci v 2.5nF, Li = 0,
Uo v 5.9V, Io v 14mA, Po = 20.7mW, Co v 42nF, Lo v 150mH
The equipment can only powered with a module type GE42058X012 or GE42052X012
Temperature classification: T5 to Ta = +40_C , T4 to Ta = +75_C , T3 to Ta = +80_C
Refer to table 6 for additional information and figure 31 for the ATEX/IECEx approvals nameplate.
INMETRO
Standards Used for Certification
IEC 60079-1:2007
IEC 60079-11:1999
Special Conditions of Use
Intrinsically Safe
No conditions of safe use.
Refer to table 7 for approval information and figure 32 for the INMETRO approvals nameplate.
Table 7. Hazardous Area Classifications—INMETRO
Certification
Intrinsically Safe
INMETRO
BR-Ex ia IIC T3/T4/T5 Gb
12
Certification Obtained
Certification Obtained
Entity Rating
HART Terminals WP1/WP2
Ui = 6.1V
Uo = 5.9V
Ii = 5mA
Io = 14mA
Pi = 30.5mW
Po = 20.7mW
Ci = 2.5nF
Co = 42nF
Li = 0
Lo = 150mH
Entity Rating
HART Terminals WP1/WP2
Ui = 6.1Vcc
Uo = 5.9Vcc
Ii = 5mA
Io = 14mA
Pi = 30.5mW
Po = 20.7mW
Ci = 2.5nF
Co = 42nF
Li = 0
Lo = 150mH
Instruction Manual
D103391X012
Temperature Code
Enclosure Rating
T3(Tamb v 80_C)
4X & IP66
T4(Tamb v 75_C)
T5(Tamb v 40_C)
Temperature Code
Enclosure Rating
T3(Tamb v 80_C)
4X & IP66
T4(Tamb v 75_C)
T5(Tamb v 40_C)