4310 Wireless Position Monitor
December 2011
This manual describes using the local interface to setup and calibrate the instrument.
Do not install, operate, or maintain a 4310 wireless position monitor without being fully trained and qualified in valve,
actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage, it is
important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions and
warnings. If you have any questions about these instructions, contact your Emerson Process Management sales office
before proceeding.

Description

The 4310 wireless position monitor is a non‐contacting wireless position switch. It is a rugged measurement device
that provides a wireless on/off feedback signal to indicate equipment position. The 4310 can be used to monitor the
on/off status of equipment such as valves, sliding‐stem regulators, displacement and float level sensors, and relief
valves. It is designed to be simple to use, compact, and easily mounted.
The wireless position monitor periodically reads the on/off position of a measured device and transmits that data over
the wireless network. The transmitted data includes two limit switch status indications, internal device temperature,
and power module voltage. It also checks for configuration and service instructions from host systems such as
distributed control systems (DCS), asset management systems (AMS), and supervisory control and data acquisition
(SCADA) systems.

Terminology

Local Interface—All 4310 wireless position monitors come standard with a Liquid Crystal Display (LCD) and two (2)
pushbuttons. The local interface provides the capability to setup and calibrate the monitor.
Magnet Assembly—This is the feedback component that is mounted directly to the valve stem. It supplies a magnetic
field that is sensed by the wireless position monitor. This component is typically part of most mounting kit assemblies.

Specifications

Specifications for the 4310 wireless position monitor are shown in table 1.

FCC Compliance

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of
the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in
which case the user will be required to correct the interference at his own expense.
This product is an FCC approved device. Changes or modifications to the 4310 wireless position monitor that are not
expressly approved by the party responsible for compliance may void your authority to operate the device.
WARNING
This product is intended for a specific temperature range and other application specifications. Failure to adhere to these
specification could result in the malfunction of the product, property damage, or personal injury.