Instruction Manual Supplement
D104306X012
ATEX Hazardous Area Approvals
Fisher
4320 Wireless Position Monitor
Hazardous Area Classifications and Special Instructions for "Safe Use" and
Installation in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring
requirements and/or conditions of "safe use". These special instructions for "safe use" are in addition to, and may
override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the nameplate markings affixed to the product and the 4320 instruction manual (D103621X012),
available from your
Emerson sales
Always refer to the nameplate itself to identify the appropriate certification.
WARNING
Failure to follow these conditions of "safe use" could result in personal injury or property damage from fire or explosion,
and area re‐classification.
II 1 G
Intrinsically Safe
Monitor Version
Battery Sourced Power Module w/out Pneumatic Output
Ex ia IIC T3/T4/T5 Ga
Install per control drawing GE59530
 as shown in figure 1 and 2
Enclosure: Type 4X, IP66 & IP67
T3(Tamb ≤ 85_C), T4(Tamb ≤ 75_C), T5(Tamb ≤ 40_C)
Temperature Range: -40_C to 85_C
www.Fisher.com
office, Local Business Partner, or www.Fisher.com.
4320 Wireless Position Monitor - ATEX
External Power w/out Pneumatic Output
Ex ia IIC T5 Ga
Install per control drawing GE59530
 as shown in figure 1 and 3
Enclosure: Type 4X, IP66 & IP67
T5(Tamb ≤ 80_C)
Temperature Range: -40_C to 80_C
January 2018

Advertisement

loading

Summary of Contents for Emerson Fisher 4320

  • Page 1 Note This information supplements the nameplate markings affixed to the product and the 4320 instruction manual (D103621X012), available from your Emerson sales office, Local Business Partner, or www.Fisher.com. Always refer to the nameplate itself to identify the appropriate certification. WARNING Failure to follow these conditions of “safe use”...
  • Page 2 Instruction Manual Supplement 4320 Wireless Position Monitor - ATEX January 2018 D104306X012 Control Version Battery Sourced Power Module with Pneumatic Output External Power with Pneumatic Output Ex ia IIC T4/T5/T6 Ga Ex ia IIC T5 Ga Install per control drawing GE59530 Install per control drawing GE59530  as shown in figure 1 and 2  as shown in figure 1 and 3...
  • Page 3 Instruction Manual 4320 Wireless Position Monitor - ATEX D104306X012 January 2018 Figure 2. Installation Drawing for Battery Module Assembly; See Notes in Figure 1 HAZARDOUS LOCATION NON-HAZARDOUS LOCATION INTRINSICALLY SAFE HART COMM TERMINALS CLASS I DIV 1 GP ABCD WP1/WP2 CLASS I, ZONE 0 GP IIC 4320 POSITION MONITOR BATTERY...
  • Page 4 Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co.