Table 3. EMC Summary Results—Emissions
Frequency Range
Port
(MHz)
30 to 230
230 to 1000
Enclosure
1000 to 3000
3000 to 6000
NOTES:
The 4310 is considered as a Group 1 device.
Industrial, Scientific, and Medial (ISM) radio frequency (RF) equipment is rated according to its Group and Class as follows;
Group I - Equipment in which there is intentionally generated and/or used conductively coupled radio‐frequency energy which is necessary for the internal functioning of the equipment itself.
Group II - Equipment in which radio‐frequency energy is intentionally generated and/or used in the form of electromagnetic radiation for the treatment of material, and EDM and arc welding
equipment.
Class A - Equipment suitable for use in industrial and commercial environments
Class B - Equipment suitable for use in domestic environments
Table 4. Device Variables
DEVICE VARIABLE
INDEX
DD
1
Closed Limit Switch
2
Open Limit Switch
3
Temperature
4
Supply Voltage
6
Switch States
243
Battery Life Remaining
244
PV Output State
245
Loop Current

Educational Services

For information on available courses for the 4310 wireless position monitor, as well as a variety of other products,
contact:
Emerson Process Management
Educational Services, Registration
P.O. Box 190; 301 S. 1st Ave.
Marshalltown, IA 50158-2823
Phone: 800-338-8158 or
Phone: 641-754-3771
FAX: 641-754-3431
e‐mail: education@emerson.com

Installation

WARNING
Before installing the 4310 wireless position monitor:
D Always wear protective clothing, gloves, and eyewear when performing any installation procedures to avoid personal
injury or property damage.
Basic Standard
Group 1 Class A: 40 dB (μV/m) measured at 10 m distance
Group 1 Class B: 30 dB (μV/m) measured at 10 m distance
Group 1 Class A: 47 dB (μV/m) measured at 10 m distance
Group 1 Class B: 37 dB (μV/m) measured at 10 m distance
EN 55011
Group 1 Class B
50 dB (μV/m) measured at 3 m distance, peak limit not to exceed 70 dB (μV/m)
Group 1 Class B
54 dB (μV/m) measured at 3 m distance, peak limit not to exceed 74 db (μV/m)
Gateway
CLOSED_TRIGGER
Reports 'Valve Closed' condition
OPEN_TRIGGER
Reports 'Valve Open' condition
DEVICE_TEMPERATURE
Electronics Module Temperature
BATTERY_VOLTAGE
Power Supply Output
SWITCH_STATE
Composite of Variables 1 and 2
BATTERY_LIFE
Estimated battery life remaining
PERCENT_RANGE
Copy of Variable 6
CURRENT
Always Indeterminate (not a number)
4310 Wireless Position Monitor
Emissions Level
DESCRIPTION
(1 = Tripped, 0 = Not Tripped)
(1 = Tripped, 0 = Not Tripped)
(Degrees C)
(Volts DC)
(0 = Partially Open, 1 = Closed, 2 = Open,
3 = Indeterminate)
(days) - meaningless with External Power option
(0 = Partially Open, 1 = Closed, 2 = Open,
3 = Indeterminate)
(mA)
December 2011
Given Rating
Class A & B
Class A & B
Class A &B
Class A & B
5