Operating Manual 24685034, Rev. AE Hydrastep 2468 June 2011 Hydrastep 2468CB and 2468CD lectronic Gauging System (Dual Power Supply Version) www.emersonprocess.com...
Page 4
About this manual This manual describes the Hydrastep 2468CB and 2468CD Electronic Gauging Systems along with the recommended options. Except where stated otherwise, the information contained in this manual can be assumed to apply to either system. This manual is divided into three parts; the first covers the electrical/electronic system; the second describes the pressure parts;...
Page 5
SYMBOLS USED IN THIS MANUAL AND ON THE UNIT Symbol Meaning Direct Current Alternating Current Earth (ground) terminal Protective conductor terminal Caution (refer to accompanying documents)
Page 7
Part 1 Hydrastep 2468CB & 2468CD Electronic Gauging System Pt.1 24685034...
Page 9
DANGEROUS VOLTAGES ARE PRESENT IN THIS EQUIPMENT. ANY WARNING NOTICES PROCEDURES CONTAINED THIS MANUAL OR ON THE EQUIPMENT SHOULD BE STRICTLY OBSERVED TO MAINTAIN SAFETY. THE USE OF THIS EQUIPMENT IN A MANNER NOT SPECIFIED IN THIS MANUAL MAY IMPAIR PROTECTION PROVIDED THIS...
Hydrastep 2468CB and 2468CD Manual Introduction to the Hydrastep 2468 Electronic Gauging System Introduction to the Hydrastep 2468 Electronic Gauging System Contents Page No. WATER LEVEL MEASUREMENT ............3 HYDRASTEP 2468 ELECTRONIC GAUGING SYSTEM ....... 5 1.2.1 INPUT BOARDS .................. 5 1.2.2 DISPLAY BOARDS ................
Introduction to the Hydrastep 2468 Electronic Gauging System Hydrastep 2468CB and 2468CD Manual 0040 Figure 1.1 - Front panel of the Hydrastep 2468 gauging system 24685034...
Hydrastep 2468CB and 2468CD Manual Introduction to the Hydrastep 2468 Electronic Gauging System WATER LEVEL MEASUREMENT The Hydrastep 2468 Electronic Gauging System is designed as an electronic alternative to water level gauges on boilers, giving a more reliable and safer water level indication than conventional visual gauges.
Introduction to the Hydrastep 2468 Electronic Gauging System Hydrastep 2468CB and 2468CD Manual Figure 1.3 - Typical Hydrastep 2468 System Installation 24685034...
Hydrastep 2468CB and 2468CD Manual Introduction to the Hydrastep 2468 Electronic Gauging System HYDRASTEP 2468 ELECTRONIC GAUGING SYSTEM The Hydrastep 2468 is a sophisticated and flexible electronic gauging system. It is supplied in two main versions: A Single Power Supply System with Local Level Display ...
Introduction to the Hydrastep 2468 Electronic Gauging System Hydrastep 2468CB and 2468CD Manual 1.2.3 SYSTEM FAULTS (2468CB OR 2468CD) System fault indication, a yellow LED and an opto-isolated output, is provided for a ‘water above steam’ condition, an electrode fault or wiring failure and the detection of an internal fault.
Hydrastep 2468CB and 2468CD Manual Introduction to the Hydrastep 2468 Electronic Gauging System HYDRASTEP 2468 UPGRADE PATHS AND AVAILABLE OPTIONS Table 1.1 describes the available versions of the Hydrastep 2468 Electronic Gauging System and their possible options. Available Options Existing System Comments Description Part No.
Page 20
Introduction to the Hydrastep 2468 Electronic Gauging System Hydrastep 2468CB and 2468CD Manual 24685034...
Page 21
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version 2468CB & 2468CD Dual Power Supply Version Contents Page No. INTRODUCTION ..................2-3 ELECTRODE CABLING SYSTEM ............2-3 ELECTRONIC ENCLOSURE ..............2-3 2.3.1 INPUT BOARD (PCB 24680501 AND PCB 24680516) ......2-5 2.3.1.1 Analogue Output Drive Capability ...........
Page 22
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual 2.5.2 DISPLAY BOARD 24680515 ............... 2-20 2.5.2.1 Link LK1 Setting ..............2-20 2.5.2.2 Configuring the ‘Number of Electrodes’ Switch ....2-20 2.5.2.3 ‘Switching Threshold’ Setting ..........2-22 2.5.2.4 ‘Compatibility’...
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version INTRODUCTION This chapter introduces the dual power supply version of the Hydrastep 2468 Electronic Gauging System, its mechanical installation, system configuration, simple fault analysis/corrective action capability and its specification. ELECTRODE CABLING SYSTEM This system can have 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30 or 32 electrodes and uses 18-core electrode cables.
Page 24
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual Figure 2.1: Outline drawing showing PCB layout and interconnections 24685034...
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version 2.3.1 INPUT BOARD (PCB 24680501 AND PCB 24680516) The input board processes the electrode inputs to provide water level data for display purposes and a current output representing the water level. Fault detection is also carried out where the condition of the electrode inputs are examined and a FAULT is indicated when: 1.
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual 2.3.3 DISPLAY BOARD (PCB 24680515) The display board receives its power supplies and electrode data from the input boards. This data is decoded and used to illuminate the required LEDs mounted on the display board.
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version 2.3.3.2 Links LK2, LK3, LK4 and LK5 These links are used to select either the 8 - 16 display mode (two LEDs per electrode) or the 18 - 32 display mode (one LED per electrode). Two link headers are provided with the unit and must be fitted in either LK2 and LK4, to enable the 8 - 16 electrode mode, or LK3 and LK5, to enable the 18 - 32 electrode mode.
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual INSTALLATION This section deals with the mechanical installation of the electronic enclosure and the electrical connections required for the basic system. Any installation dealing with the options available for use on this version of the system are covered in Chapters 3 & 4. Notes: 1.
Page 29
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version Figure 2.2: Installation diagram for Hydrastep 2468 Electronic Gauging System unit 24685034...
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual 2.4.2 ELECTRICAL INSTALLATION This section deals with the interconnection between the electrodes and the electronic enclosure, the connection of the ac mains power supply to the electronic enclosure and the analogue output connections from the electronic enclosure.
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version 2.4.2.2 Connecting Cables to Water Column Electrodes (16 Electrode System - See Page 2-WD.7) The following assumes that the electrodes have been fitted to the water column. 1. Gain access to the electrodes mounted on the water column. 2.
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual Figure 2.3: Enclosure cable layout for 16 electrode system 2.4.2.3 Connecting the Electrode Cable Assemblies to 2468 Enclosure WARNING Mains voltages are present in this instrument when power is connected.
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version Wiring to the ‘hinge-side’ 24680501 board (even-numbered electrodes) should not be pressed hard against the ribbon cables, but instead run forward of the connectors and away from the side of the casing. Do not route them over the board. Wiring to the ‘catch-side’...
Page 34
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual With power disconnected release voltage selection plug PL9 by squeezing lugs. Insert appropriate selector plug. Remove fuse and fit 200mA ceramic anti-surge fuse for 240Vac nominal and 400mA ceramic anti-surge fuse for 110Vac nominal.
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version 2.4.2.5 Analogue Output Connection WARNING Mains voltages are present in this instrument when power is connected. De-energise before opening front cover. Plug PL1 on each input board is used for the analogue output. A 2-core screened cable is required and is connected into a 2-way socket such that: ...
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual 2.4.2.6 Opto-Isolated Fault Output Connection WARNING Mains voltages are present in this instrument when power is connected. De-energise before opening front cover. Plug PL4 is used for the FAULT output. A 2-core screened cable, capable of taking 1A and 30V is required and is connected into its 2-way terminal block such that: Note: No fault present = Short circuit, <...
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version This concludes the electrical installation requirements for the basic instrument configuration. Connections within the enclosure for the options available will be covered in the Installation sections of the appropriate Chapter 3a (Relay Outputs), 3b (Relay with time delay Outputs), 3c (Opto-isolated Outputs) or Chapter 4 (Remote Display).
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual 2.5.1.2 Pulsed Output Setting As configured at the factory, the analogue output pulses if a fault condition occurs. 1. To disable this feature the split pad SP10 must be broken by cutting the track that passes between the pads.
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version 2.5.1.4 Configuring the Unit to Detect Electrode Error WARNING Mains voltages are present in this instrument when power is connected. De-energise before opening front cover. 1. Disconnect the power supply. Gain access to the input PCB by opening the cover and removing the option board.
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual 2.5.2 DISPLAY BOARD 24680515 The Display Board needs to know how many electrodes are being used and if one or two input boards are being used. A centrally mounted dual-in-line switch assembly, SW1 (titled “Number of Electrodes”) uses four individual switch channels to select between an 8 and 32 electrode operation as shown in Table 2.2 below.
Page 41
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version Note: When two input boards are fitted, odd electrodes use one input board, even electrodes use the other input board, and switch SW1 is set to the number of electrodes per input board.
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual 2.5.2.3 ‘Switching Threshold’ Setting WARNING Mains voltages are present in this instrument when power is connected. De-energise before opening front cover. 1. Disconnect the power supply. Gain access to PCB 24680515 by opening the cover. 2.
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version FAULT ANALYSIS & CORRECTIVE ACTION Faults in the system will generally be indicated by the YELLOW LED on the front panel and by the fault output on the display board. The main faults, which are catered for, are: ...
Page 44
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual Indication Fault(s) Analysis and Corrective Action Check ac voltage on electrodes with a true r.m.s. State 1 (contd.) Incorrect wiring, voltmeter. A voltage of less than 0.1V ac indicates a fault broken connection condition.
Page 45
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version Indication Fault(s) Analysis and Corrective Action State 1 (contd.) 3. Insert these sockets in place of the electrode cable sockets in the input boards, the level display should now show an all steam state and no fault indication.
Page 46
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual Indication Fault(s) Analysis and Corrective Action State 3 (contd.) Dirt on electrode If the wiring checks carried out as described above have not located a fault, then dirt on an electrode insulator may Affected electrode be the cause of the problem giving an effective short- alternates...
Page 47
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version Indication Fault(s) Analysis and Corrective Action State 5 Electrode wiring or Check that all odd numbered electrodes indicating internal fault water have the correct pair of conductors connected. Bottom half of Check the connections to the right hand input board.
Page 48
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual Indication Fault(s) Analysis and Corrective Action State 5 (contd.) Integral circuit fault If the wiring checks carried out as described above on right hand circuit have not located the fault, then it is possible and board or the display internal fault exists.
Page 49
Hydrastep 2468CB and 2468CD Manual 2468CB & 2468CD Dual Power Supply Version Indication Fault(s) Analysis and Corrective Action State 7 No power to one Only odd LEDs illuminating indicates a problem with input board or a the left hand input board. Only even LEDs illuminating Only odd or power supply fault indicates a problem with the right hand input board.
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual 2.6.1 COMPONENT REPLACEMENT The Hydrastep 2468 contains no user-replaceable components. Board failure requires the replacement of the entire printed circuit board. WARNING Mains voltages are present in this instrument when power is connected.
2468CB & 2468CD Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual SPECIFICATION Enclosure: 425mm x 325mm x 163mm (16.7in x 12.8in x 6.4in) Brushed stainless steel Wall-mounting lP65 / NEMA4X Gland plate - stainless steel 250mm x 120mm (9.8in x 4.7in) Weight of unit: 12kg (26.4lb) Operating temperature:...
Page 53
Hydrastep 2468CB and 2468CD Manual Wiring Diagrams for Dual Power Supply Version Wiring Diagrams for Dual Power Supply Version Contents Page No. Figure 2.1 Electrode cable connections to 8 port column ........2-WD.3 Figure 2.2 Electrode cable connections to 10 port column ........2-WD.4 Figure 2.3 Electrode cable connections to 12 port column ........
Page 54
Wiring Diagrams for Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual 2-WD. 24685034...
Page 55
Hydrastep 2468CB and 2468CD Manual Wiring Diagrams for Dual Power Supply Version Figure 2.1 - Electrode cable connections to 8 port column 2-WD.3 24685034...
Page 56
Wiring Diagrams for Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual Figure 2.2 - Electrode cable connections to 10 port column 2-WD. 24685034...
Page 57
Hydrastep 2468CB and 2468CD Manual Wiring Diagrams for Dual Power Supply Version Figure 2.3 - Electrode cable connections to 12 port column 2-WD.5 24685034...
Page 58
Wiring Diagrams for Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual Figure 2.4 - Electrode cable connections to 14 port column 2-WD. 24685034...
Page 59
Hydrastep 2468CB and 2468CD Manual Wiring Diagrams for Dual Power Supply Version Figure 2.5 - Electrode cable connections to 16 port column 2-WD.7 24685034...
Page 60
Wiring Diagrams for Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual Figure 2.6 - Electrode cable connections to 18 port column 2-WD. 24685034...
Page 61
Hydrastep 2468CB and 2468CD Manual Wiring Diagrams for Dual Power Supply Version Figure 2.7 - Electrode cable connections to 20 port column 2-WD.9 24685034...
Page 62
Wiring Diagrams for Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual Figure 2.8 - Electrode cable connections to 22 port column 2-WD. 24685034...
Page 63
Hydrastep 2468CB and 2468CD Manual Wiring Diagrams for Dual Power Supply Version Figure 2.9 - Electrode cable connections to 24 port column 2-WD.11 24685034...
Page 64
Wiring Diagrams for Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual Figure 2.10 - Electrode cable connections to 26 port column 2-WD. 24685034...
Page 65
Hydrastep 2468CB and 2468CD Manual Wiring Diagrams for Dual Power Supply Version Figure 2.11 - Electrode cable connections to 28 port column 2-WD.13 24685034...
Page 66
Wiring Diagrams for Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual Figure 2.12 - Electrode cable connections to 30 port column 2-WD. 24685034...
Page 67
Hydrastep 2468CB and 2468CD Manual Wiring Diagrams for Dual Power Supply Version Figure 2.13 - Electrode cable connections to 32 port column 2-WD.15 24685034...
Page 68
Wiring Diagrams for Dual Power Supply Version Hydrastep 2468CB and 2468CD Manual 2-WD. 24685034...
Hydrastep 2468CB and 2468CD Manual Relay Output Board Option 3A.1 GENERAL DESCRIPTION The Relay Output Board (PCB 24680504) has four relays and is mounted on top of the input board using 3 nylon spacers. Electrical connection between the two boards is via plug and socket (SK1 on the input board and PL1 on the relay output board).
Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3a.2.2.1 Fitting the Nylon Spacers to the Relay Output Board The spacers fit into the holes within the white-bordered areas on the output board (see Figure 3a.1 on page 3a-6). 1. Fit the nylon spacers into their prepared holes on the output board and lock in position using the nylon washer and M4 nut, see inset diagram.
Hydrastep 2468CB and 2468CD Manual Relay Output Board Option 3A.2.3 ELECTRICAL INSTALLATION This sub-section deals with the output of the states of the four relays. Two 8-way sockets are provided with each output board through which the relay outputs are delivered to their external destinations.
Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3A.3 RELAY BOARD CONFIGURATION The 24680504 Relay Output Board has three configuration switches: SW6: Selects Electrode or Alarm state for RL1. SW1 - SW4: Selects individual electrode for relays RL1 to RL4. ...
Hydrastep 2468CB and 2468CD Manual Relay Output Board Option 3A.3.1 RELAY OUTPUT BOARD 3a.3.1.1 Configuring the Relay Output Board WARNING Mains voltages are present in this instrument when power is connected. De-energise before opening front cover. 1. Isolate the 2468 electronics enclosure from its power supplies. 2.
Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3a.3.1.3 Relay Energisation (‘In Steam’ or ‘In Water’) - SW5 This is a four-channel switch, one channel allocated per relay. The switch selects whether the relay is energised when the selected electrode is in water or is in steam. This switch is highlighted in Figure 3a.1 (on page 3a-6) to provide additional information on channel identity and the switch ‘electrode state’.
Hydrastep 2468CB and 2468CD Manual Relay Output Board Option 3A.3.2 ALARM AND TRIPPING FACILITIES The relay boards provide high and low water level alarm and trip facilities for the 2468 Hydrastep system. Four to eight relays can be made available for each input board fitted. 3a.3.2.1 Philosophy A requirement in regulations concerning steam raising plant is the provision of an automatic low water level shut-down or trip device.
Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3a.3.2.3 ‘One out of Two’ Relay Alarm System Either of the relays involved can cause an alarm when their assigned electrode registers an alarm condition. The alarm condition is selected by switch SW5 to provide relay energisation in water EW or energisation in steam ES.
Hydrastep 2468CB and 2468CD Manual Relay Output Board Option 3a.3.2.4 ‘Two out of Two’ Relay Alarm System This system requires both relays to operate to cause an alarm when their assigned electrodes register an alarm condition. Case A - Relays normally energised, de-energise both to trip (Relays shown in de-energised state) RL 1 RL 1...
Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3a.3.2.5 ‘Two out of Four’ Relay Alarm System In the following diagrams (5A & 5B) indicate the electrode channel selected for each relay. A fully functioning system (NO FAULTS) will perform a low level trip at electrode level 3.
Page 81
Hydrastep 2468CB and 2468CD Manual Relay Output Board Option In the following diagrams (6A & 6B) indicate the electrode channel selected for each relay. A fully functioning system (NO FAULTS) will perform a low level trip at electrode level 2. For a high level trip, using electrode channels 9,10, 11 and 12 respectively and switch SW5 set for ES, a healthy system would trip at level 11.
Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3a.3.2.6 ‘Two out of Three’ Relay Alarm System In the following diagrams (7A & 7B) indicate the electrode channel selected for each relay. A fully functioning system (NO FAULTS) will cause a low level trip at electrode level 2. Using high-level electrode channels and SW5 set to ES, the circuit can perform a high level trip.
Hydrastep 2468CB and 2468CD Manual Relay Output Board Option 3A.4 COMPONENT REPLACEMENT The relay board contains no replaceable circuit components, failure of the board requires replacement of the entire board. The only component that can be replaced is the nylon spacer. 3A.4.1 REPLACEMENT OF NYLON SPACERS The replacement of nylon spacers fitted to the output board requires access to the non-...
Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3A.5 SPECIFICATION Outputs: 4 x Alarm/Trip Relays Relay Contact Rating: Maximum voltage: 250V 125V Maximum current: Maximum switching power: 1500VA 240W ( 30V) ( 60V) ( 125V) For type nA safety: 100mA at 30Vdc Maximum initial contact resistance: 30m...
Hydrastep 2468CB and 2468CD Manual Delay Relay Output Board Option 3B.1 GENERAL DESCRIPTION The Delay Relay Output Board (PCB 24680509) is mounted on top of the input board using 3 nylon spacers. Electrical connection between the two boards is via plug and socket (SK1 on the input board and PL1 on the delay relay output board).
Delay Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3B.2.2 MECHANICAL INSTALLATION The output board is mounted directly on top of the input board. The input board is supplied with three nylon spacers fitted. The output board is then aligned on its Berg socket/plug interconnection (PL1/SK1) and input board-mounted spacers and pressed home on to the spacers.
Hydrastep 2468CB and 2468CD Manual Delay Relay Output Board Option 3B.2.3 ELECTRICAL INSTALLATION This sub-section deals with the output of the states of the four relays. Two 8-way sockets are provided with each output board through which the relay outputs are delivered to their external destinations.
Delay Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3B.3 DELAY RELAY BOARD CONFIGURATION The 24680509 Delay Relay Output Board has three configuration switches and twenty split pad links for delay time selection. The switches are: SW6: Selects Electrode or Alarm state for RL1. ...
Hydrastep 2468CB and 2468CD Manual Delay Relay Output Board Option 3B.3.1 DELAY RELAY OUTPUT BOARD 3b.3.1.1 Configuring the Delay Relay Output Board WARNING Mains voltages are present in this instrument when power is connected. De-energise before opening front cover. 1. Isolate the 2468 electronics enclosure from its power supplies. 2.
Delay Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3b.3.1.3 Relay Energisation (‘In Steam’ or ‘In Water’) - SW5 This is a four-channel switch, one channel allocated per relay. The choice presented by each channel switch is whether the relay is energised when the particular electrode is in water or energised when that electrode is in steam.
Hydrastep 2468CB and 2468CD Manual Delay Relay Output Board Option 3b.3.1.6 Delay Circuit Configuration By means of split pad links incorporated in each of the relay delay circuits, delays can be introduced or bypassed and the following delays are made available (see also Figure 3b.2): Table 3b.2 - Split pad functions on relay delay circuits 3b-9 24685034...
Delay Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3b.3.1.7 Configuring the Delay Circuit Split Pads WARNING Mains voltages are present in this instrument when power is connected. De-energise before opening front cover. 1. Isolate the 2468 electronics enclosure from its power supplies. 2.
Hydrastep 2468CB and 2468CD Manual Delay Relay Output Board Option 3B.3.2 ALARM AND TRIPPING FACILITIES The relay boards provide high and low water level alarm and trip facilities for the 2468 Hydrastep system. Four to eight relays can be made available for each input board fitted. 3b.3.2.1 Philosophy A requirement in regulations concerning steam raising plant is the provision of an automatic low water level shut-down or trip device.
Delay Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3b.3.2.3 ‘One out of Two’ Relay Alarm System Either of the relays involved can cause an alarm when their assigned electrode registers an alarm condition. The alarm condition is selected by switch SW5 to provide relay energisation in water EW or energisation in steam ES.
Hydrastep 2468CB and 2468CD Manual Delay Relay Output Board Option 3b.3.2.4 ‘Two out of Two’ Relay Alarm System This system requires both relays to operate to cause an alarm when their assigned electrodes register an alarm condition. Case A - Relays normally energised, de-energise both to trip (Relays shown in de-energised state) RL 1 RL 1...
Delay Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3b.3.2.5 ‘Two out of Four’ Relay Alarm System In the following diagrams (5A & 5B) indicate the electrode channel selected for each relay. A fully functioning system (NO FAULTS) will perform a low level trip at electrode level 3.
Hydrastep 2468CB and 2468CD Manual Delay Relay Output Board Option 3b.3.2.6 ‘Two out of Four’ Relay Alarm System (contd.) In the following diagrams (6A & 6B) indicate the electrode channel selected for each relay. A fully functioning system (NO FAULTS) will perform a low level trip at electrode level 2.
Delay Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3b.3.2.7 ‘Two out of Three’ Relay Alarm System In the following diagrams (7A & 7B) indicate the electrode channel selected for each relay. A fully functioning system (NO FAULTS) will cause a low level trip at electrode level 2. Using high-level electrode channels and SW5 set to ES, the circuit can perform a high level trip.
Hydrastep 2468CB and 2468CD Manual Delay Relay Output Board Option 3B.4 COMPONENT REPLACEMENT The delay relay board contains no replaceable circuit components, failure of the board requires replacement of the entire board. The only component that can be replaced is the nylon spacers.
Page 102
Delay Relay Output Board Option Hydrastep 2468CB and 2468CD Manual 3B.5 SPECIFICATION Outputs: 4 x Alarm/Trip Relays Relay Contact Rating: Maximum voltage: 250V 125V Maximum current: Maximum switching power: 1500VA 240W ( 30V) ( 60V) ( 125V) For type nA safety: 100mA at 30Vdc Maximum initial contact resistance: 30m...
Hydrastep 2468CB & 2468CD Manual Opto-isolated Output Board Option 3C.1 GENERAL DESCRIPTION The Opto-isolated Output Board (PCB 24680505) has four opto-isolated outputs and is mounted on top of the input board using 3 nylon spacers. Electrical connection between the two boards is via a plug and a socket (SK1 on the input board and PL1 on the opto-isolated output board).
Opto-isolated Output Board Option Hydrastep 2468CB & 2468CD Manual 3C.2.2 MECHANICAL INSTALLATION The output board is mounted directly on top of the input board. The input board is supplied with three nylon spacers fitted. The output board is then aligned on its Berg socket/plug interconnection (PL1/SK1) and input board-mounted spacers and pressed home on to the spacers.
Hydrastep 2468CB & 2468CD Manual Opto-isolated Output Board Option 3C.2.3 ELECTRICAL INSTALLATION 3c.2.3.1 PCB Interconnections Signal interconnection between the input board (PCB 1) and the output board (PCB 5) is direct via the SK1/PL1 12-way Berg connectors. Similarly, interconnection between the dual- mounted output boards uses the same type connectors but the top board’s plug PL1 engages in the first output board’s socket SK1.
Hydrastep 2468CB & 2468CD Manual Opto-isolated Output Board Option 3C.3.1 CONFIGURING THE OPTO-ISOLATED OUTPUT BOARD WARNING Mains voltages are present in this instrument when power is connected. De-energise before opening front cover. Gain access to the printed circuit board assemblies inside the Hydrastep 2468 enclosure as follows: 1.
Opto-isolated Output Board Option Hydrastep 2468CB & 2468CD Manual 3c.3.1.2 Electrode/Alarm Operation (output 1 function only) - SW6 Opto-isolated output from TR2 can be configured to receive either an electrode input or it can be used as the ‘system fault’ output. The two positions are detailed in Figure 3c.1 (on page 3c-6).
Hydrastep 2468CB & 2468CD Manual Opto-isolated Output Board Option 3C.3.2 ALARM AND TRIPPING FACILITIES The output boards provide high and low water level alarm and trip facilities for the 2468 Hydrastep system. Four to eight opto-isolated outputs can be made available for each input board fitted.
Opto-isolated Output Board Option Hydrastep 2468CB & 2468CD Manual 3c.3.2.3 ‘One out of Two’ Opto-output Alarm System Either of the opto-outputs involved can signal an alarm when their assigned electrode detects a water/steam interface change. The alarm condition is selected by switch SW5 to provide an opto-output in conducting mode in water W or in a conducting mode in steam S.
Hydrastep 2468CB & 2468CD Manual Opto-isolated Output Board Option 3c.3.2.4 ‘Two out of Two’ Opto-output Alarm System This system requires both opto-outputs to operate to cause an alarm when their assigned electrodes register an alarm condition. Case A - Opto-output circuit normally open circuit, short circuit both to trip To alarm annunciator or tripping device + VE...
Opto-isolated Output Board Option Hydrastep 2468CB & 2468CD Manual 3c.3.2.5 ‘Two out of Four’ Opto-output Alarm System In the following diagrams (5A & 5B) indicate the electrode channel selected for each opto-output. A fully functioning system (NO FAULTS) will perform a low level trip at electrode level 3.
Hydrastep 2468CB & 2468CD Manual Opto-isolated Output Board Option 3c.3.2.6 ‘Two out of Three’ Opto-output Alarm System In the following diagrams (6A & 6B) indicate the electrode channel selected for each opto- output. A fully functioning system (NO FAULTS) will cause a low level trip at electrode level 2. Using high-level electrode channels and SW5 set to S, the circuit can perform a high level trip.
Opto-isolated Output Board Option Hydrastep 2468CB & 2468CD Manual 3C.4 COMPONENT REPLACEMENT The components used on the opto-isolated output board are fitted using ‘surface mount technology’ and fault remedial action is by the replacement of the whole output board. The only components fitted to the board that the general user can replace are the nylon spacers.
Page 119
Hydrastep 2468CB & 2468CD Manual Remote Display Options 24683B, C & D Remote Display Options 24683B, C, & D Contents Page No. REMOTE DISPLAY OPTIONS ..............4-3 CONFIGURATION ..................4-4 4.2.1 RECONFIGURING THE 24683B AND 24683C REMOTE DISPLAY ..4-4 4.2.2 RECONFIGURING THE 24683D REMOTE DISPLAY ......
Page 120
Remote Display Options 24683B, C & D Hydrastep 2468CB & 2468CD Manual Illustrations Figure 4.1 - Location of link headers for selecting the display mode ........4-4 Figure 4.2 - Interconnection cable for a single remote display ..........4-7 Figure 4.3 - Star and daisy chain connections of remote displays ........4-8 Figure 4.4 - Star connection example for two remote displays ..........
Hydrastep 2468CB & 2468CD Manual Remote Display Options 24683B, C & D REMOTE DISPLAY OPTIONS The 24683B, C, and D Remote Display Units give a repeat display of the water level state and fault alarm state of the Hydrastep 2468 Electronic Gauging System. Each type of remote display operates in the same way.
Remote Display Options 24683B, C & D Hydrastep 2468CB & 2468CD Manual CONFIGURATION All remote displays can be configured for operation with 8 to 16 electrodes (two LEDs per electrode) or 18 to 32 electrodes (one LED per electrode). Remote displays are supplied ready for operation with 8 to 16 electrodes.
Hydrastep 2468CB & 2468CD Manual Remote Display Options 24683B, C & D 4.2.2 RECONFIGURING THE 24683D REMOTE DISPLAY The procedure for reconfiguring the 24683D for operation with 18 to 32 electrodes is: Undo the four screws securing the transparent cover and remove the cover. Undo the four screws securing the front panel and lay the panel carefully away from the top of the box, still connected by the ribbon cable.
Remote Display Options 24683B, C & D Hydrastep 2468CB & 2468CD Manual MECHANICAL INSTALLATION Of the three types of remote display units, types 24683B and 24683C are intended for panel mounting and type 24683D is intended for wall mounting. The installation procedures for panel and wall mounting are described below.
Hydrastep 2468CB & 2468CD Manual Remote Display Options 24683B, C & D ELECTRICAL INSTALLATION Up to six remote displays may be driven by the Hydrastep 2468 unit. One remote display can be powered from the main unit, but all the others must have a local supply. A remote display has a dual serial data input and a dual power input.
Remote Display Options 24683B, C & D Hydrastep 2468CB & 2468CD Manual 4.4.1 STAR AND DAISY CHAIN CONNECTIONS Multiple remote display units can be connected to the main 2468 unit in two ways: ‘star’ or ‘daisy chain’. (See Figure 4.3) You can use either or both of these, in whichever way best suits the relative locations of the 2468 unit and the remote displays.
Hydrastep 2468CB & 2468CD Manual Remote Display Options 24683B, C & D 4.4.2 EXAMPLE OF A ‘STAR CONNECTED’ SYSTEM Figure 4.4 shows two remote displays connected in a ‘star’. Where more than one remote display is in use, local supplies with isolated outputs must be used to power the extra unit(s). Up to six remote displays can be supported (less their power requirements): with the full complement of units in use, three signal carrying conductors must be connected to each terminal.
Remote Display Options 24683B, C & D Hydrastep 2468CB & 2468CD Manual 4.4.3 EXAMPLE OF A `DAISY CHAIN' SYSTEM Figure 4.5 shows two remote displays connected in a `daisy chain'. Where more than one remote display is in use, local supplies with isolated outputs must be used to power the extra unit(s). To prevent signal reflections from corrupting the data, it may be necessary to fit termination resistors to the last unit in the chain.
Hydrastep 2468CB & 2468CD Manual Remote Display Options 24683B, C & D 4.4.4 CONNECTING CABLES TO THE REMOTE DISPLAY The following procedure can be used for each remote display that is to be connected: Gain access to the remote display terminal block. On the 24683B and 24683C remote displays the terminal block is located at the rear of the unit.
Remote Display Options 24683B, C & D Hydrastep 2468CB & 2468CD Manual 4.4.5 CONNECTING THE DISPLAY CABLES TO HYDRASTEP 2468 WARNING: Mains voltages are present in the 2468 Hydrastep unit when power is connected. De-energise before opening the front cover. The connection procedure is: Ensure a stress-free cable run between the remote display unit and Hydrastep 2468.
Hydrastep 2468CB & 2468CD Manual Remote Display Options 24683B, C & D SYSTEM OPERATION When the system is brought on line check for complete agreement between the remote display and the Hydrastep level indicator display. FAULT ANALYSIS AND CORRECTIVE ACTION Indication Fault Analysis and Corrective Action...
Page 132
Remote Display Options 24683B, C & D Hydrastep 2468CB & 2468CD Manual Indication Fault Analysis and Corrective Action Bottom half of fault Power present, but Check that the wiring to connector PL1 in the remote LED illuminated and loss of serial data. display unit is correct.
Page 133
Hydrastep 2468CB & 2468CD Manual Remote Display Options 24683B, C & D Indication Fault Analysis and Corrective Action Flickering Display Corruption of signal Most probably caused by bad shielding (screening) of the remote data display cabling or by bad shield connections to ground. Check shielding and shield connections.
Remote Display Options 24683B, C & D Hydrastep 2468CB & 2468CD Manual COMPONENT REPLACEMENT Hydrastep remote display units contain no user-replaceable electronic components. Board failure requires the faulty PCB to be removed and returned for service and a serviceable PCB to be fitted in its place. A list of replacement parts is given in Table 4.2. The procedure for replacing a PCB in a remote display is: Ensure that the Hydrastep 2468 unit is switched off.
Page 139
About this manual This manual describes various procedures involved in the installation of the Hydrastep water columns, their attachments and the electrodes used in determining the level of water in the column. Part 2 - Pressure Parts Chapter 1 is a general introduction to the Hydrastep system of water level determination. Chapter 2 describes the water column and its components.
Page 141
R E M I N D E R ELECTRODE INSTALLATION THREADED ELECTRODE(S), PART Nos. 459600602 & 459600802 MAKE SURE THAT THE COMPRESSION GASKET IS REGISTERED IN THE PROBE RECESS PRIOR TO TIGHTENING THE ELECTRODE. THIS CENTRES THE GASKET TO THE PROBE. GASKET ELECTRODE SEAT SURFACE...
Page 143
N O T I C E HYDRASTEP VESSEL PROBE SYSTEM PROVIDES A SELF-FLUSHING FEATURE THAT PREVENTS THE ACCUMULATION OF DEBRIS IN THE VESSEL. THIS ELIMINATES THE NEED FOR PERIODIC BLOWING DOWN OF THE VESSEL. DO NOT BLOW DOWN THE HYDRASTEP VESSEL IF A BLOCKAGE IS SUSPECTED.
Page 147
Hydrastep Pressure Parts General Introduction General Introduction PRINCIPLE OF OPERATION ..............1-3 WATER LEVEL INDICATION ..............1-3 Illustrations Figure 1.1 - Schematic of high pressure resistance measuring cell and electrodes ..... 1-3 Figure 1.2 - Low pressure water column (120bar, 1740psi) ..........1-4 Figure 1.3 - High pressure water column (210 bar, 3045psi and 300 bar, 4350psi) .....
Page 148
General Introduction Hydrastep Pressure Parts 24675030...
Page 149
Hydrastep Pressure Parts General Introduction PRINCIPLE OF OPERATION The Hydrastep systems have been designed as electronic alternatives to conventional visual water gauges on boilers, giving more reliable and safer water level indication. The system is based on the significant differences in resistivities of water and steam over the range 100C (212F) to 370C (698F).
Page 150
General Introduction Hydrastep Pressure Parts Figure 1.2 - Low pressure water column (120bar, 1740psi) 24675030...
Page 151
Hydrastep Pressure Parts General Introduction Figure 1.3 - High pressure water column (210 bar, 3045psi and 300 bar, 4350psi) 24675030...
Page 152
General Introduction Hydrastep Pressure Parts 24675030...
Page 153
Hydrastep Pressure Parts Installation Procedures Installation Procedures Contents Page No. SCOPE OF PROCEDURES ..............2-3 STORAGE ....................2-3 2.2.1 AMBIENT CONDITIONS ................. 2-3 2.2.2 PHYSICAL PROTECTION ..............2-3 2.2.3 INSPECTION ................... 2-3 2.2.4 HANDLING PRECAUTIONS ..............2-3 INSTALLATION OF WATER COLUMN ........... 2-3 INSPECTION OF MECHANICAL INSTALLATION WORK ......
Page 154
Installation Procedures Hydrastep Pressure Parts 24675030...
Installation Procedures Hydrastep Pressure Parts SCOPE OF PROCEDURES The procedures apply to the Hydrastep Boiler Drum Water Level Equipment supplied by Rosemount Measurement, who are responsible, under their supply contract, for delivery of all items of the above equipment listed in the delivery schedules. Rosemount Measurement are not responsible for handling, storage, installation and protection of equipment on-site.
Page 156
Installation Procedures Hydrastep Pressure Parts The water column is delivered along with the correct number of electrodes of the relevant pressure type (high or low) and complete with gaskets or ferrules and fixing nuts, where applicable. The electrodes should only be fitted to the column after all erection and electrical work is completed and the water column is ready to be commissioned.
Page 157
Installation Procedures Hydrastep Pressure Parts 45° 1.5mm For HP (210 bar) Material: SA106B Size: 1" N.B, Sch. 160 pipe dim. For HP (300 bar) Material: SA479 - 316 Size: 1" N.B, Sch. XXS PPE For LP Material: SA106B Size: 1" N.B, Sch. 80 pipe dim. Figure 2.1 - Universal weld profile The Steam and Water connections on the water column must be set to position the water column at the correct level before they are welded in place, Figure 2.2 gives an example of...
Installation Procedures Hydrastep Pressure Parts The water connection to the water column must be fully insulated by lagging. The steam connection must also be lagged, but a minimum length of 0.5 metre of the steam leg must be left unlagged where the steam leg joins the water column (see Figure 2.2). Lagging the water column will reduce the density error, provided that 0.5 metre minimum of the steam leg is left unlagged.
Page 159
Installation Procedures Hydrastep Pressure Parts Figure 2.2 - Typical water column installation, showing optional column lagging. 24675030...
Page 160
Installation Procedures Hydrastep Pressure Parts Figure 2.3 - Typical water column suspension 24675030...
Page 161
Hydrastep Pressure Parts Fault Repair and Commissioning Fault Repair and Commissioning Contents Page No. BACKGROUND 3.1.1 SAFETY PRECAUTIONS ................3-3 3.1.2 WATER COLUMN ISOLATION ..............3-4 3.1.3 ELECTRODE AND ELECTRODE SEAL LEAKS ........3-4 3.1.3.1 LOW PRESSURE ELECTRODES ............3-4 3.1.3.2 HIGH PRESSURE ELECTRODES ............
Page 162
Fault Repair and Commissioning Hydrastep Pressure Parts 24675030...
Hydrastep Pressure Parts Fault Repair and Commissioning BACKGROUND With any steam/water detection gauge, a partial blockage or leak within the pressurised system may result in incorrect water level indication. The Hydrastep water column design is such that density errors in water level indication (due to the water temperature in the column being lower than the water temperature in the boiler drum) are minimised for the temperatures and pressures specified.
Fault Repair and Commissioning Hydrastep Pressure Parts 3.1.2 WATER COLUMN ISOLATION After obtaining authority to isolate the column: Close off the steam and water isolating valves. Where the column is connected to a closed drain, open the drain valve and, when the pressure equalises, close the drain valve.
Hydrastep Pressure Parts Fault Repair and Commissioning Where scoring or erosion of the electrode port seat has occurred in the water column, the seat can be re-cut to acceptable standards using a service tool as listed below. Service Tool 246791AA – for use with electrodes 246781A* and 246781Z* only ...
Fault Repair and Commissioning Hydrastep Pressure Parts Refit the electrical lead(s) and guard. Recommission as detailed later in this Chapter. 3.1.5 PROCEDURE FOR CHANGING HIGH PRESSURE ELECTRODES Carry out the isolation procedure as detailed in sub-section 3.1.2. Ensure that the tripping is disabled (see ‘Safety Precautions’, sub-section 3.1.1).
Hydrastep Pressure Parts Fault Repair and Commissioning 3.2.2 WATER COLUMN TRANSIENT RESPONSE Starting with the water level at or below mid-gauge, note the lowest ‘steam’ indicating channel at this stage and fully close the water isolating valve nearest the water column quickly.
Page 168
Fault Repair and Commissioning Hydrastep Pressure Parts 24675030...
Page 169
Hydrastep Pressure Parts Unit Description Unit Description Contents Page No. LOW PRESSURE ELECTRODES ............4-3 HIGH PRESSURE ELECTRODES ............4-4 WATER COLUMN (L.P.) ................4-5 WATER COLUMN (H.P.) ................4-6 WATER COLUMN (H.P. SUPERCRITICAL) ..........4-7 Illustrations Figure 4.1 - Low pressure electrode ..................4-3 Figure 4.2 - High pressure electrode..................
Page 170
Unit Description Hydrastep Pressure Parts 24675030...
Hydrastep Pressure Parts Unit Description LOW PRESSURE ELECTRODES These electrodes can be used for pressures of 50bar (725psi) for 459600802 units, and up to 120bar (1740psi) for 459600602 units - see Chapter 5 for Specifications. They are used with the low pressure version of the Hydrastep water column shown in Figure 1.2 (in Chapter 1, Part 2 of the manual).
Unit Description Hydrastep Pressure Parts HIGH PRESSURE ELECTRODES High pressure electrodes can be used for pressures in the range 50bar (725psi) to 300bar (4350psi) see Chapter 5 for Specifications. These electrodes are used with the high pressure water column shown in Figure 1.3 (in Chapter 1, Part 2 of the manual). The fitting instructions for high pressure electrodes are included within the electrode package.
Hydrastep Pressure Parts Unit Description WATER COLUMN (L.P.) The low pressure water column is manufactured from carbon steel, extruded rectangular hollow bar. The electrode ports are drilled and fitted with ‘helicoil’ inserts to accept the electrodes. This thread system gives greater strength than if the electrodes were mounted directly into tapped ports.
Unit Description Hydrastep Pressure Parts WATER COLUMN (H.P.) The high pressure water column is manufactured from 2” NB SCH S carbon steel pipe. The inserts used are made from high grade stainless steel and are welded into position on the water column body. The top cap and the drain components of the water column are manufactured from forged carbon steel bar, the drain components being available in ¾”...
Hydrastep Pressure Parts Unit Description WATER COLUMN (H.P. SUPERCRITICAL) The high pressure water column is manufactured from 2” NB SCH S stainless steel pipe. The inserts used are made from Stainless steel and are welded into position on the water column body.
Page 176
Unit Description Hydrastep Pressure Parts 24675030...
Page 177
Hydrastep Pressure Parts Unit Specifications - Hydrastep Unit Specifications - Hydrastep ELECTRODES Type 459600602 Complete with sealing gasket: Metaflex. Screw in type M18 x 1.5 Insulator: Zirconia ceramic Rating 120 bar (1740 psi) at 370C (698 F) pH range 7-11 Hydrostatically tested to 180 bar (2610 psi) at ambient temp.
Page 178
Unit Specifications - Hydrastep Hydrastep Pressure Parts Manual WATER COLUMNS Type Low Pressure: Rating 120bar (1740psi) at 343 C (650 F) Type High Pressure: Rating 210bar (3045psi) at 370 C (698 F) (Series III) Type High Pressure: Rating 300bar (4350psi) at 560 C (1040 F) (Super III) 24675030...
Page 179
Part 3 Hydrastep 2468CA, CB, CC & CD Electronic Gauging System Pt.3...
Page 181
Hydrastep 2468 - Technical Manual Appendix A: CSA Approval CSA Certified GENERAL All drawings in this manual are given here for planning purposes only. Before commencing with implementation, reference should always be made to the current issue of the appropriate drawings. Contact the factory for details.
Page 186
24685034, Rev. AE Hydrastep 2468 June 2011 The Emerson logo is a trade mark and service mark of Emerson Electric Co. Mobrey is a registered trademark of Rosemount Measurement Ltd. All other marks are the property of their respective owners.