Function description
4
Function description
4.1
Integrated protection mechanisms
The relay conforms to the following safety criteria:
}
The circuit is redundant with built-in self-monitoring.
}
The safety function remains effective in the case of a component failure.
}
The safety outputs are tested periodically using a disconnection test.
4.2
Functions
The function of the safety system's inputs and outputs depends on the safety circuit created
using the PNOZmulti Configurator. A chip card is used to download the safety circuit to the
base unit. The base unit has 2 microcontrollers that monitor each other. They evaluate the
input circuits and switch the outputs accordingly.
The LEDs indicate the status of the safety system plus the inputs and outputs.
The online help on the PNOZmulti Configurator contains descriptions of the operating
modes and all the functions of the PNOZmulti safety system, plus connection examples.
4.3
System reaction time
Calculation of the maximum reaction time between an input switching off and a linked out-
put in the system switching off is described in the document "PNOZmulti System Expan-
sion".
4.4
Diagnostics
The status and error messages displayed by the LEDs are saved in an error stack. This er-
ror stack can be read out from PNOZmulti Configurator via the USB interface.
4.5
Block diagram
T0M20
IM0
IM1
Operating Manual PNOZ mm0p-T
1002704-EN-02
T1M21
T2M22 T3M23
Configurable
output
Configurable
input/output
IM2
IM3 IM16
IM17
IM18
IM19
O0 O1
O2
O3
24 V 0 V
24 V 0 V
Input
I4
I5
I6
I7
I8
I9
I10
I11
A1 A2
=
=
Power
I12 I13 I14 I15
12