Pilz PNOZ mmc3p Manual

Pilz PNOZ mmc3p Manual

Configurable, safe compact controllers
Hide thumbs Also See for PNOZ mmc3p:

Advertisement

Quick Links

PNOZ mmc3p
}
Configurable, safe compact controllers PNOZmulti Mini
Operating Manual-1002423-EN-04

Advertisement

Table of Contents
loading

Summary of Contents for Pilz PNOZ mmc3p

  • Page 1 PNOZ mmc3p Configurable, safe compact controllers PNOZmulti Mini Operating Manual-1002423-EN-04...
  • Page 2 We do assure you that all persons are regarded without discrim- ination and on an equal basis. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
  • Page 3: Table Of Contents

    Connecting the supply voltage....................PROFIBUS DP interface......................Setting the station address ....................... Download modified project to the control system PNOZmulti........... Connection example ......................... Operation ..........................Messages ..........................Technical details ........................Order reference ........................Product ............................. Accessories ..........................Operating Manual PNOZ mmc3p 1002423-EN-04...
  • Page 4: Introduction

    Introduction Introduction Validity of documentation This documentation is valid for the product PNOZ mmc3p. It is valid until new documenta- tion is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
  • Page 5 Introduction INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PNOZ mmc3p 1002423-EN-04...
  • Page 6: Overview

    24 - 127 are used they have different properties (see document entitled "Communication Interfaces"). Max. 1 PNOZ mmc3p can be connected to the base unit Plug-in connection terminals: Either spring-loaded terminal or screw terminal available as an accessory (see Order ref- erences for accessories).
  • Page 7: Front View

    Overview Front view Legend: 0 V, 24 V: Supply connections X1: PROFIBUS-DP interface (female 9-pin D-Sub connector) : Functional earth LED: – Power – Online – Offline – Fault Operating Manual PNOZ mmc3p 1002423-EN-04...
  • Page 8: Safety

    PNOZmulti and PROFIBUS-DP. PROFIBUS-DP is designed for fast data exchange at field level. The expansion module PNOZ mmc3p is a passive subscriber (Slave) of PROFIBUS-DP (DPV0). The basic func- tions of communication with PROFIBUS-DP conform to EN 50170. The central controller (Master) reads input information from the slaves and writes output information to the slaves as part of each cycle.
  • Page 9: Safety Regulations

    PNOZmulti Configurator's online help. Only use these functions once you have read and understood the documentations. Do not open the housing or make any unauthorised modifications. Please make sure you shut down the supply voltage when performing maintenance work (e.g. exchanging contactors). Operating Manual PNOZ mmc3p 1002423-EN-04...
  • Page 10: Function Description

    The station address is set via rotary switches. After the supply voltage is switched on or the PNOZmulti control system is reset, the expansion module PNOZ mmc3p is configured and started automatically. LEDs indicate the status of the expansion module on PROFIBUS.
  • Page 11: Assigning The Inputs/Outputs In The Pnozmulti Configurator To The Profibus-Dp Inputs

    The number of virtual inputs and outputs can be extended to 128 (see document "Commu- nication Interfaces" in the section entitled "Fieldbus modules") Block diagram 24 V 0 V 24 V 0 V Operating Manual PNOZ mmc3p | 11 1002423-EN-04...
  • Page 12: Installation

    Damage due to electrostatic discharge! Electrostatic discharge can damage components. Ensure against discharge before touching the product, e.g. by touching an earthed, conductive sur- face or by wearing an earthed armband. Dimensions in mm Operating Manual PNOZ mmc3p | 12 1002423-EN-04...
  • Page 13: Connect The Base Unit And Expansion Modules

    Please refer to the document "PNOZmulti System Expansion" for details of the number of modules that can be connected to the base unit and the module types. Operating Manual PNOZ mmc3p | 13 1002423-EN-04...
  • Page 14: Commissioning

    4: CNTR-P 5: DGND 6: VP 7: n.c. 8: A (RxD/TxD-N) 9: n.c. n.c. = not connected Please note the following when connecting to PROFIBUS-DP: Only use metal plugs or metallised plastic plugs Operating Manual PNOZ mmc3p | 14 1002423-EN-04...
  • Page 15: Setting The Station Address

    Twisted pair, screened cable must be used to connect the interfaces Setting the station address The station address of the expansion module PNOZ mmc3p is set between 0 ... 99 (decimal) via two rotary switches x1 and x10. On the upper rotary switch x10, use a small screwdriver to set the tens digit for the ad- dress (“3”...
  • Page 16: Connection Example

    Commissioning Connection example PROFIBUS-DP PROFIBUS-DP Slave n PROFIBUS-DP Slave 1 Slave 3 PROFIBUS-DP Master PNOZ mmc3p PROFIBUS PROFIBUS-DP Slave 2 Operating Manual PNOZ mmc3p | 16 1002423-EN-04...
  • Page 17: Operation

    LINE" and "OFFLINE" LEDs indicate the status of the PNOZ mmc3p on PROFIBUS-DP. If the expansion module PNOZ mmc3p does not receive a configuration from the base unit for a period of 30 s, the expansion module PNOZ mmc3p connects to PROFIBUS-DP and "ONLINE"...
  • Page 18: Technical Details

    Max. operating height above sea level 2000 m EN 61131-2 Vibration In accordance with the standard EN 60068-2-6 Frequency 10 - 150 Hz Acceleration Shock stress In accordance with the standard EN 60068-2-27 Acceleration Duration 11 ms Operating Manual PNOZ mmc3p | 18 1002423-EN-04...
  • Page 19 Spring-loaded terminals: Terminal points per connec- tion Stripping length with spring-loaded terminals 9 mm Dimensions Height 100 mm Width 22,5 mm Depth 115 mm Weight 95 g Where standards are undated, the 2011-09 latest editions shall apply. Operating Manual PNOZ mmc3p | 19 1002423-EN-04...
  • Page 20: Order Reference

    Screw terminals, 10 pieces 793543 PNOZ mmcxp 10 pcs. Terminator, jumper Product type Features Order No. PNOZ s terminator plug Terminator, yellow, 10 pieces 750 010 PNOZ s connector Jumper, 10 pieces 750 020 Operating Manual PNOZ mmc3p | 20 1002423-EN-04...
  • Page 21 We are represented internationally. Please refer to our homepage www.pilz.com for further details or contact our headquarters. Headquarters: Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com, Internet: www.pilz.com...

This manual is also suitable for:

Pnozmulti mini

Table of Contents