Pilz PNOZmulti Mini Operating Manual page 26

Configurable compact control systems
Hide thumbs Also See for PNOZmulti Mini:
Table of Contents

Advertisement

Technical details
Environmental data
Climatic suitability
In accordance with the standard
Humidity
Condensation during operation
EMC
Vibration
In accordance with the standard
Frequency
Acceleration
Shock stress
In accordance with the standard
Number of shocks
Acceleration
Duration
In accordance with the standard
Number of shocks
Acceleration
Duration
Max. operating height above sea level
Airgap creepage
In accordance with the standard
Overvoltage category
Pollution degree
Rated insulation voltage
Rated impulse withstand voltage
Protection type
In accordance with the standard
Mounting area (e.g. control cabinet)
Housing
Terminals
Potential isolation
Potential isolation between
Type of potential isolation
Rated surge voltage
Mechanical data
Mounting position
DIN rail
Top hat rail
Recess width
Max. cable length
Max. cable length per input
Sum of individual cable lengths at the test pulse
output
Operating Manual PNOZ mm0p-T
1002704-EN-02
EN 60068-2-30, EN 60068-2-78
93 % r. h. at 40 °C
Short-term (only with separated extra low voltage)
EN 61131-2
EN 60068-2-6
10,0 - 150,0 Hz
1 g
EN 60068-2-27
3
15 g
11 ms
EN 60068-2-27
500
25 g
6 ms
2000 m
EN 61131-2
II
2
30 V
2,50 kV
EN 60529
IP54
IP20
IP20
SC output and system voltage
Basic insulation
2500 V
Horizontal on top hat rail
35 x 7,5 EN 50022
27 mm
1,0 km
2 km
26