To get a Module Status report

A Module Status report provides information about the controller and verifies proper network communication with
the controller. You can get this report:
In the i-Vu® application—Right-click the controller on the navigation tree, then select Module Status.
In the Field Assistant application—Right-click the controller in the navigation tree and select Module Status.
On the controller setup ModStat tab—See To set up the controller through the Service Port (page 46).
See Module Status field descriptions (page 65) in the Appendix.

Troubleshooting inputs and outputs

The i-Vu® interface shows if you have I/O errors resulting from:
A misconfigured microblock
A misconfiguration on the expander
A missing or disconnected expander
To check for errors:
In the i-Vu® navigation tree, select the equipment controlled by the .
1
On the Properties page, select the I/O Points tab.
2
Click the Name of any input or output whose name is red (indicates an error) to open its dialog box.
3
On the Details tab, scroll down to see the Reliability field under BACnet Configuration.
4
TruVu™ UCXP683T