Input Values - Carrier TruVu UCXP683T Installation And Startup Manual

Table of Contents

Advertisement

To adjust input and output properties

Input values

Input
Analog (BAI)
0-5 Vdc
0-10 Vdc
2-10 Vdc
Thermistor
Pulse to Analog (BPTA)
Pulse Counter
Binary (BBI)
Dry Contact
1
The sensor reads a value and sends a corresponding signal (Volts) to the TV-UCXP683T's physical input. The
Analog Input microblock uses the Min and Max values to linearly translate the signal into the engineering value
used in subsequent control logic.
2
You can set up a custom translation table on the driver's Custom Translation Tables pages in the i-Vu®
interface.
3
The control program must have one Pulse to Analog Input microblock for each pulse counting input.
TruVu™ UCXP683T
Installation and Start-up Guide
I/O Type
Sensor/Actuator Type
0–5 Volt
Linear Full Range
No Translation
0–10 Volt
Linear Full Range
No Translation
0–10 Volt
Linear w/Offset,
2–10 Volts
Thermistor
Select your Thermistor type or
set up and select a Non-Linear,
Custom Table
3
Dry Contact or
N/A
Binary Input
Dry Contact
N/A
Min/Max
Engineering values associated with 0
Vdc (Min) and 5 Vdc (Max)
N/A. The input microblock's value will be
the raw voltage of the input.
Engineering values associated with 0
Vdc (Min) and 10 Vdc (Max)
N/A. The input microblock's value will be
the raw voltage of the input.
Engineering values associated with 2
Vdc (Min) and 10 Vdc (Max)
N/A
2
N/A
N/A
28
1
1
1
CARRIER CORPORATION ©2022
All rights reserved